Gas Piping

Pipe Sizing Procedure - Example

The gas supply must be capable of handling the entire gas load at the location. Gas line sizing is based on gas type, the pressure drop in the system, the gas pressure supplied, and gas line type. For gas pipe sizing in the United States, refer to the National Fuel Gas Code, NFPA 54. For Canadian gas pipe sizing, refer to the Natural Gas and Propane Installation Code CAN/CSA B149.1. The below information is provided as an example. The appropriate table from the applicable code must be used.

1.For some tables, you will need to determine the cubic feet per hour of gas required by dividing the gas input by the heating value of the gas (available from the local gas company). The gas input needs to include all gas products at the location and the maximum BTU usage at full load when all gas products are in use.

Gas Input of all gas products (BTU / HR)

Cubic Feet per Hour (CFH) =

Heating Value of Gas (BTU / FT 3 )

2.Use the table for your gas type and pipe type to find the pipe size required. The pipe size must be able to provide the required cubic feet per hour of gas or the required BTU/hour.

Example: The gas input of the RL94e is 199,000 BTU/HR using propane. Additional appliances at the location require 75,000 BTU/hr. Therefore the maximum BTU usage will be 274,000 BTU/hr.

If using propane gas with Schedule 40 metallic pipe, 100 ft in length, then the 1 inch pipe size will be capable of supplying 372,000 BTU/hr of propane gas..

Length

 

Pipe Size (inches)

 

3/4

1

1 1/4

1 1/2

 

10

273

514

1060

1580

20

188

353

726

1090

30

151

284

583

873

40

129

243

499

747

50

114

215

442

662

60

104

195

400

600

70

95

179

368

552

80

89

167

343

514

 

 

 

 

 

90

83

157

322

482

 

 

 

 

 

100

79

148

304

455

 

 

 

 

 

125

70

131

269

403

 

 

 

 

 

150

63

119

244

366

 

 

 

 

 

175

58

109

224

336

 

 

 

 

 

200

54

102

209

313

 

 

 

 

 

Length

 

Pipe Size (inches)

 

 

 

 

 

1/2

3/4

1

1 1/4

 

 

 

 

 

 

10

291

608

1150

2350

 

 

 

 

 

20

200

418

787

1620

 

 

 

 

 

30

160

336

632

1300

 

 

 

 

 

40

137

287

541

1110

 

 

 

 

 

50

122

255

480

985

 

 

 

 

 

60

110

231

434

892

 

 

 

 

 

80

101

212

400

821

 

 

 

 

 

100

94

197

372

763

 

 

 

 

 

125

89

185

349

716

 

 

 

 

 

150

84

175

330

677

 

 

 

 

 

175

74

155

292

600

 

 

 

 

 

200

67

140

265

543

 

 

 

 

 

VB Series Outdoor LS Manual

19

Image 19
Contents REU-VB2528WD-US Table of Contents RL75e RL94e R98LSe R98LSe-ASME SpecificationsSafety Definitions Consumer Safety InformationSafety Behavior and Practices Safety Features Operating Instructions Features Available on Temperature ControllersFeatures Description of OperationMC-91-1US & MCC-91-1US Temperature ControllerTemperature Controller Settings How to Set the TemperatureMCC-91 Temperature Controller Temperature Options Without a Temperature ControllerSetting the Sound Volume Voice Prompt Re-setting the Maximum Temperature RL75 and RL94 onlySetting the Water Volume Using the Water Smart / Bath Fill FunctionOverview Models MC-91 and MCC-91 Setting Controller to MuteSetting the Clock Filling the TubMaintenance Code Fault Remedy Error CodesCode Accessing Operating Information Trouble Shooting for Common IssuesWater Quality Circulating Pump Flushing the Heat Exchanger Error Code LC orGeneral Instructions Installation InstructionsAttachment of the Water Heater Clearances from ApplianceGas Piping Electrical ConnectionGeneral Instructions Pipe Sizing Procedure Example Water Piping Isolation Valves Installation InstructionsPressure Relief Valve Installation Instructions Pressure Relief Valve MaintenanceFreeze Protection Pressure Relief ValveFreeze Protection When the water heater or external piping has frozenManual draining of the water heater KEY Freeze Protection PipingRinnai Water Heater Recommended Piping for Basic InstallationFor this application Recommended Piping for Circulation SystemsFlue Terminal Clearances ANS Z21.10.3, CSA Description Canadian Installations US Installations Additional Clearances Guidelines Connecting Multiple Water HeatersHigh Altitude Installations Number Connected Accessories Necessary Water HeatersCanada only Cable Lengths and Size Temperature Controller InstallationConfigurations LocationOutline of Remote Mounting the ControllerOperating Instructions For Your Safety Read Before OperatingPressure Drop Curve Technical DataOutlet Flow Data Pumps Temperature SettingReplacement Space HeatingDimensions Ladder Diagram for RL75e and RL94e HOT Ladder Diagram for R98LSe and R98LSe-ASMEConsumer Support Warranty InformationLimited Warranty What is covered?What will Rinnai do? How do I get service? What is not covered?Limitation on warranties Important In the State of Massachusetts 248 CMR 4.00 State RegulationsOu lappel 1-866-RINNAI1 Temp. d’eau Instructions dutilisationOptions de température sans contrôleur à distance Plages de température avec un contrôleur de températureLes températures suggérées sont de Entretien Instructions générales Fixation du chauffe-eau Écartements par rapport à lappareilRaccordement électrique Tuyauterie de gaz Installations à haute altitudeInstructions générales Tuyauterie deau Valve de dégagement de pression Instructions d’InstallationSoupape de sûreté Qualité de leauNiveau maximum Espacements pour terminaisons de cheminée ANS Z21.10.3, CSA Réf Description Installations Canada Installations USA Légende Tuyauterie recommandée pour installation de baseVanneMa ualmanuelleValve Instructions dutilisationPhase Diagramme en escalier RL75e, RL94eB C Diagramme en escalier R98LSe, R98LSeASMECombien de temps dure la couverture ? Support à la clientèleInformations sur la garantie Quest-ce qui est couvert ?Limitation sur les garanties Que fait Rinnai pour exercer la garantie ?VB2528W VB2735W VA3237W