Samsung AR30JVFUCWKNMG manual English-35, Smooth the cut edges, Torque

Page 35

Installing and connecting the assembly pipe of the indoor unit

Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.

There are 2 refrigerant pipes of different diameters:

• The smaller one is for the liquid refrigerant

• The larger one is for the gas refrigerant

A short pipe is already fitted to the air conditioner. You may need to extend the pipe using the assembly pipe (optional).

The connection procedure for the refrigerant pipe varies

A

B

according to the exit position of the pipe when facing the wall:

 

 

ENGLISH

Right(A)

Left(B)

Underside(C)

Rear

1.Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor unit unless you connect the pipe directly from the rear.

2.Smooth the cut edges.

3.Remove the protection caps of the pipes and connect the assembly pipe to each pipe. Tighten the nuts first with your hands, and then with a torque wrench, applying the following torque:

C

Outer Diameter

Torque

N•m

kgf•cm

 

ø6.35 mm

14~18

140~180

 

 

 

ø9.52 mm

34~42

350~430

 

 

 

ø12.70 mm

49~61

500~620

 

 

 

ø15.88 mm

68~82

690~830

 

 

 

• If you want to shorten or extend the pipes, refer to page 36~37.

4.Cut off the remaining foam insulation.

5.If necessary, bend the pipe to fit along the bottom of the indoor unit. Then pull it out through the appropriate hole.

The pipe should not project from the rear of the indoor unit.

The bending radius should be 100 mm or more.

6.Pass the pipe through the hole in the wall.

7.For further details on how to connect to the outdoor unit and purge the air, refer to page 39~41.

• The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test;

refer to page 43 for further details.

Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

DO NOT WALL UP THE PIPE CONNECTION !

All refrigerant pipe connection must be easy accessible and serviceable.

English-35

MAX4 AR30JV&JS_IB&IM_DB68-04541A_EN.indd 35

2014/9/26 16:38:56

Image 35
Contents MAX4 AR30JV&JSIB&IMDB68-04541AEN.indd 2014/9/26 Contents English-3 Safety precautionsEnglish-4 For Power SupplyEnglish-5 For UsingEnglish-6 English-7 Do not place objects or devices under the indoor unitEnglish-8 For CleaningEnglish-9 Checking before useOperation ranges English-10 Checking the name of the partsMain parts English-11 Checking the remote controllerRemote controller buttons Inserting the batteries Remote controller displayBattery changing time Storing the remote controllerBasic function English-14 Press the button to adjust the temperaturePress the button to set the desired fan speed Horizontal air flow Adjusting the air flow directionUsing the Turbo function Vertical air flowPress the Time Up or Time Down button to set the time Press the button on the remote controllerMode English-16English-17 Setting the On/Off timerPress the On Timer/Off Timer button Additional options available in On timer modeIf the air conditioner is on If the air conditioner is off Using the Smart Saver functionFrom the moment you have set the timer English-18Cool/Heat mode Using the Auto Clean functionUsing the Quiet function When the air conditioner is turned onOpening the panel Cleaning the air conditionerCleaning the indoor unit Cleaning the outdoor unit heat exchangerDry the Air filter in a ventilated area Cleaning the air filterRemoving the Air filter English-21Bio filter sky-blue Bio filterEnglish-22 Deodorizing filter black Deodorizing filterEnglish-23 English-24 Maintaining the air conditionerEnglish-25 TroubleshootingAir conditioner Does not come outCheck the Drains have been cleared Regular Maintenance Check if you press the Set/Cancel button on the remotePress the Power button or disconnect the power plug Mode for 1~2 hours. We do not use smelly componentsEnglish-27 General informationIndoor unit Choosing the installation locationInstalling the unit Power supply line, fuse or circuit breakerEnglish-29 Where sulfide gas existsOutdoor Unit  Figure Description When installing more than 1 outdoor unitWhen the air outlet is towards the wall English-30English-31 AccessoriesAccessories in the indoor unit case Accessories in the outdoor unit caseTools for test operations Fixing the installation plateOptional accessories Tools required for installation General ToolsConnecting the cable Connecting the assembly cableCable specification English-34 Extend the assembly cable if necessaryEach wire is labeled with the corresponding terminal number Cut off the remaining foam insulation English-35Smooth the cut edges TorqueUnscrew the caps at the end of each pipe Evacuating the indoor unitCutting or extending the pipe English-36Wall Indoor unit Drain hose Drain hose must not English-37Correct Inclined CrackedHose tight Drain hose installationEnglish-38 Two hoses are firmly connected, there is no water leakageEnglish-39 Evacuating the connected pipesIf you use a pipe longer than 5 m Adding RefrigerantEnglish-40 Outer Torque1975 English-41Please fill in with indelible ink  the factory refrigerant charge of the productEnglish-42 Performing the gas leak testsEnglish-43 Outdoor unit installed on the wall by rackFixing the indoor unit in place Fixing the outdoor unit in placeEnglish-44 Final Check and Trial OperationAfter tube contraction work is completed, wrap it with How to connect your extended power cablesEnglish-45 Apply heat to the contraction tube to contract itEnglish-46 Technical SpecificationsEnglish-47 0211 Questions or COMMENTS?Air Conditioner
Related manuals
Manual 49 pages 24.33 Kb