Evacuating the indoor unit

The indoor unit is supplied with inert gas (nitrogen).

Before installing the unit, check if nitrogen gas flow out of indoor unit.

If this one isn’t true, DO NOT INSTALL THE UNIT since leakage could be inside the indoor unit.

1.Unscrew the caps at the end of each pipe.

All inert gas exhausts from the indoor unit.

• To prevent dirt or foreign substances from getting into the pipes during

installation, do NOT remove the caps completely until you are ready to connect the pipes.

The remaining air in the Refrigeration cycle, which contains moisture,

 

 

 

 

may cause malfunction on the compressor.

 

 

 

 

 

 

 

Always contact the service center or a professional installation agency

Pipes

 

Unscrew the caps

 

for product installation.

 

 

 

Cutting or extending the pipe

The length of the pipe can be:

Extended up to : see table page 29

Shorten up to: see page 29

If you need a pipe longer than 5 meters:

• You must add refrigerant to the pipes; otherwise, the indoor unit may freeze.

1.Make sure that you have all the required tools (pipe cutter, reamer, flaring tool and pipe holder).

2.If you want to shorten the pipe, cut it using a pipe cutter, ensuring that the cut edge remains at 90° with the side of the pipe (see below examples of correct and incorrect cut edges).

Pipe cutter

Pipe

Oblique Rough Burr

3. To prevent a gas leak, remove all burrs at the cut edge of the pipe using a reamer.

• Face the pipe down while removing the burrs to make sure that burrs do not get in to the pipe.

4. Put a flare nut slightly into the pipe and modify the flare.

90°±2°

 

 

Outer Diameter (D)

Depth (A)

Flaring Size (B)

 

 

 

 

 

 

 

 

ø6.35 mm

1.3 mm

8.7

- 9.1 mm

 

B

 

 

 

 

 

ø9.52 mm

1.8 mm

12.8

- 13.2 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ø12.70 mm

2.0 mm

16.2

- 16.6 mm

 

 

 

 

 

 

R0.4~0.8

ø15.88 mm

2.2 mm

19.3

- 19.7 mm

Pipe Flare

English-36

MAX4 AR30JV&JS_IB&IM_DB68-04541A_EN.indd 36

2014/9/26 16:38:57

Image 36
Contents MAX4 AR30JV&JSIB&IMDB68-04541AEN.indd 2014/9/26 Contents Safety precautions English-3For Power Supply English-4For Using English-5English-6 Do not place objects or devices under the indoor unit English-7For Cleaning English-8Checking before use Operation rangesEnglish-9 Checking the name of the parts Main partsEnglish-10 Checking the remote controller Remote controller buttonsEnglish-11 Remote controller display Battery changing timeStoring the remote controller Inserting the batteriesBasic function Press the button to adjust the temperature Press the button to set the desired fan speedEnglish-14 Adjusting the air flow direction Using the Turbo functionVertical air flow Horizontal air flowPress the button on the remote controller ModeEnglish-16 Press the Time Up or Time Down button to set the timeSetting the On/Off timer Press the On Timer/Off Timer buttonAdditional options available in On timer mode English-17Using the Smart Saver function From the moment you have set the timerEnglish-18 If the air conditioner is on If the air conditioner is offUsing the Auto Clean function Using the Quiet functionWhen the air conditioner is turned on Cool/Heat modeCleaning the air conditioner Cleaning the indoor unitCleaning the outdoor unit heat exchanger Opening the panelCleaning the air filter Removing the Air filterEnglish-21 Dry the Air filter in a ventilated areaBio filter English-22Bio filter sky-blue Deodorizing filter English-23Deodorizing filter black Maintaining the air conditioner English-24Troubleshooting Air conditionerDoes not come out English-25Check if you press the Set/Cancel button on the remote Press the Power button or disconnect the power plugMode for 1~2 hours. We do not use smelly components Check the Drains have been cleared Regular MaintenanceGeneral information English-27Choosing the installation location Installing the unitPower supply line, fuse or circuit breaker Indoor unitWhere sulfide gas exists Outdoor UnitEnglish-29 When installing more than 1 outdoor unit When the air outlet is towards the wallEnglish-30  Figure DescriptionAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case English-31Fixing the installation plate Optional accessoriesTools required for installation General Tools Tools for test operationsConnecting the assembly cable Cable specificationConnecting the cable Extend the assembly cable if necessary Each wire is labeled with the corresponding terminal numberEnglish-34 English-35 Smooth the cut edgesTorque Cut off the remaining foam insulationEvacuating the indoor unit Cutting or extending the pipeEnglish-36 Unscrew the caps at the end of each pipeEnglish-37 Correct InclinedCracked Wall Indoor unit Drain hose Drain hose must notDrain hose installation English-38Two hoses are firmly connected, there is no water leakage Hose tightEvacuating the connected pipes English-39Adding Refrigerant English-40Outer Torque If you use a pipe longer than 5 mEnglish-41 Please fill in with indelible ink the factory refrigerant charge of the product 1975Performing the gas leak tests English-42Outdoor unit installed on the wall by rack Fixing the indoor unit in placeFixing the outdoor unit in place English-43Final Check and Trial Operation English-44How to connect your extended power cables English-45Apply heat to the contraction tube to contract it After tube contraction work is completed, wrap it withTechnical Specifications English-46English-47 Questions or COMMENTS? 0211Air Conditioner