Final Check and Trial Operation

To complete the installation, perform the following checks and tests to ensure that the air conditioner operates correctly.

Check the followings:

Strength of the installation site

Tightness of pipe connection to detect gas leak

Electric wiring connection

Heat-resistant insulation of the pipe

Drainage

Grounding conductor connection

Correct operation (follow the steps below)

1. Press the Power button and check the following:

The indicator on the indoor unit lights up.

The airflow blade opens and the fan gears up for operation.

2. Press the Mode button to select Cool or Heat (ARJS model) mode.

In Cool mode, use Temp + or - button and set the temperature at 16°C.

In Heat mode, use Temp + or - button and set the temperature at 30°C.

• Approximately 3~5 minutes later, outdoor unit will start to operate and the

Cool or Warm air will blow out.

• After 12 minutes of stationary condition check the indoor unit air treatment.

Cooling mode (indoor unit check) Inlet air temp. - Outlet air temp : From 10°K to 12°K ( indicative delta T)

Heating mode (indoor unit check) Outlet air temp. - Inlet air temp : From 11°K to 14°K (indicative delta T)

In heating mode, the indoor fan motor can remain off to avoid cold air blown into conditioned space.

3.Press the Air swing button and check the following:

The airflow blades work properly.

4.Press the Power button to stop the operation.

• When you complete the installation successfully, hand over this manual to the user for storage in a handy and safe

place.

Pump down procedure (when removing the product)

1.Press the Power button on the indoor unit for 5 seconds. Beep will sound immediately to let you know that the product is ready for pump down procedure. Please let the compressor run for more than 5 minutes.

2 . Release the valve caps on High and Low pressure side.

3 . Use L wrench to close the valve on the high pressure side.

4 . Approximately 2 minutes after, close the valve on the low pressure side.

5 . Stop operation of the air conditioner by pressing the power button on the indoor unit or remote controller.

6 . Disconnect the pipes.

English-44

MAX4 AR30JV&JS_IB&IM_DB68-04541A_EN.indd 44

2014/9/26 16:39:05

Image 44
Contents MAX4 AR30JV&JSIB&IMDB68-04541AEN.indd 2014/9/26 Contents Safety precautions English-3For Power Supply English-4For Using English-5English-6 Do not place objects or devices under the indoor unit English-7For Cleaning English-8English-9 Checking before useOperation ranges English-10 Checking the name of the partsMain parts English-11 Checking the remote controllerRemote controller buttons Remote controller display Battery changing timeStoring the remote controller Inserting the batteriesBasic function English-14 Press the button to adjust the temperaturePress the button to set the desired fan speed Adjusting the air flow direction Using the Turbo functionVertical air flow Horizontal air flowPress the button on the remote controller ModeEnglish-16 Press the Time Up or Time Down button to set the timeSetting the On/Off timer Press the On Timer/Off Timer buttonAdditional options available in On timer mode English-17Using the Smart Saver function From the moment you have set the timerEnglish-18 If the air conditioner is on If the air conditioner is offUsing the Auto Clean function Using the Quiet functionWhen the air conditioner is turned on Cool/Heat modeCleaning the air conditioner Cleaning the indoor unitCleaning the outdoor unit heat exchanger Opening the panelCleaning the air filter Removing the Air filterEnglish-21 Dry the Air filter in a ventilated areaBio filter sky-blue Bio filterEnglish-22 Deodorizing filter black Deodorizing filterEnglish-23 Maintaining the air conditioner English-24Troubleshooting Air conditionerDoes not come out English-25Check if you press the Set/Cancel button on the remote Press the Power button or disconnect the power plugMode for 1~2 hours. We do not use smelly components Check the Drains have been cleared Regular MaintenanceGeneral information English-27Choosing the installation location Installing the unitPower supply line, fuse or circuit breaker Indoor unitEnglish-29 Where sulfide gas existsOutdoor Unit When installing more than 1 outdoor unit When the air outlet is towards the wallEnglish-30  Figure DescriptionAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case English-31Fixing the installation plate Optional accessoriesTools required for installation General Tools Tools for test operationsConnecting the cable Connecting the assembly cableCable specification English-34 Extend the assembly cable if necessaryEach wire is labeled with the corresponding terminal number English-35 Smooth the cut edgesTorque Cut off the remaining foam insulationEvacuating the indoor unit Cutting or extending the pipeEnglish-36 Unscrew the caps at the end of each pipeEnglish-37 Correct InclinedCracked Wall Indoor unit Drain hose Drain hose must notDrain hose installation English-38Two hoses are firmly connected, there is no water leakage Hose tightEvacuating the connected pipes English-39Adding Refrigerant English-40Outer Torque If you use a pipe longer than 5 mEnglish-41 Please fill in with indelible ink the factory refrigerant charge of the product 1975Performing the gas leak tests English-42Outdoor unit installed on the wall by rack Fixing the indoor unit in placeFixing the outdoor unit in place English-43Final Check and Trial Operation English-44How to connect your extended power cables English-45Apply heat to the contraction tube to contract it After tube contraction work is completed, wrap it withTechnical Specifications English-46English-47 Questions or COMMENTS? 0211Air Conditioner