Samsung AQ24UGAN manual Connecting the Assembly Cable, Model Power cable Interconnection Type GL

Page 10

INSTALLING THE AIR CONDTIONER

Connecting the Assembly Cable

Cable specification

Model

Power cable

Interconnection

Type GL

cable

 

 

 

 

09/12

3G, 1.0mm2

5G, 1.0mm2

20A

H07RN-F

H07RN-F

 

 

 

3G, 1.5mm2

2G, 0.75mm2

 

18

3G, 1.5mm2

 

H07RN-F

 

 

H07RN-F

 

 

 

25A

 

3G, 2.5mm2

3G, 2.5mm2

 

 

24

2G, 0.75mm2

 

H07RN-F

 

 

H07RN-F

 

 

 

 

Note Connect the power cable to the auxiliary circuit breaker.

If every pole fails to connect to the power supply, it must be incorporated in a wire with a contact opening of ≥3mm.

Connecting the cable

 When you install the unit, make first refrigerant connections and then elec- trical connections. Connect the air conditioner to grounding system before performing the electrical connection. If unit is uninstalled first disconnect electrical cables, then refrigerant connections.

If the outdoor unit is more than 5 meters away from the indoor unit, you must extend the cable. The maximum length of the cable is 15(09/12)/100( 18/24) meters.

1Extend the assembly cable if necessary.

CAUTION Do not connect two or more different cables to extend the length. It may cause fire.

2Open the front grille.

3Remove the screw securing the connector cover.

4Pass the assembly cable through the rear of the indoor unit and connect the assembly cable to terminals. (Refer to the picture in page 11.)

Note Each wire is labeled with the corresponding terminal number.

5Pass the other end of the cable through the 65mm hole in the wall.

6Close the connector cover by tightening the screw carefully.

7Close the front grille.

8Remove the terminal board cover on the side of the outdoor unit.

E-10

Vivaldi_IM_30271A_E_11.07.09.indd 10

2009-11-7 13:57:00

Image 10
Contents Vivaldi IM30271AE11.07.09.indd 2009-11-7 Contents Safety Precautions EnglishMinor personal injury or property Choosing the Installation Location Model Figure Description Top view Side viewWhen installing more than 1 outdoor unit Accessories in the Outdoor Unit Case AccessoriesAccessories in the Indoor Unit Case Following accessories are supplied with the air conditionerFixing the Installation Plate Direction of pipeConnecting the Assembly Cable Model Power cable Interconnection Type GLIndoor unit Outdoor unitOuter Diameter Torque kgfcm DO not Wall UP the Pipe ConnectionPurging the Indoor Unit Cutting or Extending the Pipe Depth a Flaring Size BInstalling and Connecting the Drain Hose of the Indoor Unit Drain hose installationChanging Direction of the Drain Hose Change the direction only when it is necessary Direction of the drained water Installing and Connecting the Drain Hose of the Outdoor Unit You should purge the air in the indoor unit and in the pipe Purging the Connected PipesWith a Global Warming Potential GWP = Reduction of cooling capacity and malfunctionGWP value Add refrigerant charge according to table below If you use a pipe Then 1975Leak Test with Nitrogen before opening valves Performing the Gas Leak TestsTo check for gas leaks on Leak Test with R410A after opening valvesFixing the Indoor Unit in Place Fixing the Outdoor Unit in PlaceFinal Check and Trial Operation Providing Information for User Pump Down Procedure When removing the productStorage in a handy and safe place Vivaldi IM30271AE11.07.09.indd 2009-11-7 Installation Manual Cooling and Heating