Samsung AQ24UGAN, AQ09UGDN Outer Diameter Torque kgfcm, DO not Wall UP the Pipe Connection

Page 12

INSTALLING THE AIR CONDTIONER

Installing and Connecting the Assembly Pipe of the Indoor Unit

A B

C

E-12

Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.

There are 2 refrigerant pipes of different diameters:

The smaller one is for the liquid refrigerant

The larger one is for the gas refrigerant

A short pipe is already fitted to the air conditioner. You may need to extend the pipe using the assembly pipe (optional).

The connection procedure for the refrigerant pipe varies according to the exit position of the pipe when facing the wall:

Right(A)

Left(B)

Underside(C)

Rear

1 Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor unit unless you connect the pipe directly from the rear.

2Smooth the cut edges.

3Remove the protection caps of the pipes and connect the assembly pipe to each pipe. Tighten the nuts first with your hands, and then with a torque wrench, applying the following torque:

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

Note If you want to shorten or extend the pipes, refer to page 14.

4Cut off the remaining foam insulation.

5If necessary, bend the pipe to fit along the bottom of the indoor unit. Then pull it out through the appropriate hole.

The pipe should not project from the rear of the indoor unit.

The bending radius should be 100 mm or more.

6Pass the pipe through the hole in the wall.

7For further details on how to connect to the outdoor unit and purge the air, refer to page 18.

Note The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test; refer to page 20,21 for further details.

CAUTION

Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

DO NOT WALL UP THE PIPE CONNECTION !

All refrigerant pipe connection must be easy accessible and serviceable.

Vivaldi_IM_30271A_E_11.07.09.indd 12

2009-11-7 13:57:03

Image 12
Contents Vivaldi IM30271AE11.07.09.indd 2009-11-7 Contents Safety Precautions EnglishMinor personal injury or property Choosing the Installation Location Model Figure Description Top view Side viewWhen installing more than 1 outdoor unit Accessories Accessories in the Indoor Unit CaseAccessories in the Outdoor Unit Case Following accessories are supplied with the air conditionerFixing the Installation Plate Direction of pipeConnecting the Assembly Cable Model Power cable Interconnection Type GLIndoor unit Outdoor unitOuter Diameter Torque kgfcm DO not Wall UP the Pipe ConnectionPurging the Indoor Unit Cutting or Extending the Pipe Depth a Flaring Size BInstalling and Connecting the Drain Hose of the Indoor Unit Drain hose installationChange the direction only when it is necessary Changing Direction of the Drain Hose Direction of the drained water Installing and Connecting the Drain Hose of the Outdoor Unit Purging the Connected Pipes With a Global Warming Potential GWP =You should purge the air in the indoor unit and in the pipe Reduction of cooling capacity and malfunctionAdd refrigerant charge according to table below  If you use a pipe ThenGWP value 1975Performing the Gas Leak Tests To check for gas leaks onLeak Test with Nitrogen before opening valves Leak Test with R410A after opening valvesFixing the Indoor Unit in Place Fixing the Outdoor Unit in PlaceFinal Check and Trial Operation Pump Down Procedure When removing the product Providing Information for UserStorage in a handy and safe place Vivaldi IM30271AE11.07.09.indd 2009-11-7 Installation Manual Cooling and Heating