Samsung AQ24UGAN, AQ09UGDN manual Cutting or Extending the Pipe, Depth a Flaring Size B

Page 14

INSTALLING THE AIR CONDTIONER

Cutting or Extending the Pipe

A 5-meter pipe is supplied with the air conditioner (optional NOT FOR ITALY).

The length of the pipe can be:

Extended up to : see table page 5

Shorten up to: see page 5

CAUTION If you need a pipe longer than 5 meters: You must extend the assembly cable.

You must add refrigerant to the pipes; otherwise, the indoor unit may freeze.

1Make sure that you have all the required tools (pipe cutter, reamer, flaring tool and pipe holder).

Pipe cutter

Pipe

2If you want to shorten the pipe, cut it using a pipe cutter, ensuring that the cut edge remains at 90° with the side of the pipe (see below examples of correct and incorrect cut edges).

ObliqueRoughBurr

3To prevent a gas leak, remove all burrs at the cut edge of the pipe using a reamer.

CAUTION Face the pipe down while removing the burrs to make sure that burrs do not get in to the pipe.

Pipe Flare

Flare nut

 

 

 

 

 

 

 

 

 

Indoor

 

outlet pipe

 

 

Connecting pipe

 

 

4Put a flare nut slightly into the pipe and modify the flare.

Outer Diameter (D)

Depth (A)

Flaring Size (B)

ø6.35 mm

1.3 mm

9.0 mm

ø9.52 mm

1.8 mm

13.0 mm

ø12.70 mm

2.0 mm

16.2 mm

ø15.88 mm

2.2 mm

19.3 mm

ø19.05 mm

2.2 mm

22.5 mm

ø22.23 mm

2.2 mm

25.7 mm

5Check if you flared the pipe correctly (see examples of incorrectly flared pipes below).

Correct

Inclined

Damaged

Cracked

Uneven

 

 

Surface

 

Thickness

6Align the pipes to connect them easily. Tighten the flare nuts first with your hands, and then with a torque wrench, applying the following torque:

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

Note Excessive torque can be cause of gas leakage.

In case brazing the pipe, the nitrogen gas must be blown into the pipe (50 Pa). The joint must be accessible and serviceable.

E-14

7For further details on how to connect to the outdoor unit and purge the air, refer to page 18.

CAUTION

Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

Vivaldi_IM_30271A_E_11.07.09.indd 14

2009-11-7 13:57:05

Image 14
Contents Vivaldi IM30271AE11.07.09.indd 2009-11-7 Contents Safety Precautions EnglishMinor personal injury or property Choosing the Installation Location Model Figure Description Top view Side viewWhen installing more than 1 outdoor unit Accessories in the Outdoor Unit Case AccessoriesAccessories in the Indoor Unit Case Following accessories are supplied with the air conditionerFixing the Installation Plate Direction of pipeConnecting the Assembly Cable Model Power cable Interconnection Type GLIndoor unit Outdoor unitOuter Diameter Torque kgfcm DO not Wall UP the Pipe ConnectionPurging the Indoor Unit Cutting or Extending the Pipe Depth a Flaring Size BInstalling and Connecting the Drain Hose of the Indoor Unit Drain hose installation Direction of the drained water Change the direction only when it is necessaryChanging Direction of the Drain Hose Installing and Connecting the Drain Hose of the Outdoor Unit You should purge the air in the indoor unit and in the pipe Purging the Connected PipesWith a Global Warming Potential GWP = Reduction of cooling capacity and malfunctionGWP value Add refrigerant charge according to table below If you use a pipe Then 1975Leak Test with Nitrogen before opening valves Performing the Gas Leak TestsTo check for gas leaks on Leak Test with R410A after opening valvesFixing the Indoor Unit in Place Fixing the Outdoor Unit in PlaceFinal Check and Trial Operation Storage in a handy and safe place Pump Down Procedure When removing the productProviding Information for User Vivaldi IM30271AE11.07.09.indd 2009-11-7 Installation Manual Cooling and Heating