Adding Refrigerant

Add refrigerant charge according to table below:

 If you use a pipe...

Then...

 

 

longer than 5 meters,

'A'g of refrigerant R410A must

be added for each extra metre.

 

shorter than 5 meters,

The purge time is normal.

Refer to the Service Manual for further details.

CAUTION

COMPLETING THE INSTALLATION

ENGLISH

Model

A

09

10

12

20

18

20

24

25

The remaining air in the Refrigeration cycle, which contains moisture, may cause malfunction on the compressor.

Always contact the service center or a professional installation agency for product installation.

Important information regulation regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere.

Please fill in with indelible ink,

-the factory refrigerant charge of the product,

-the additional refrigerant amount charged in the field and

-+the total refrigerant charge.

on the refrigerant charge label supplied with the product.

Note a. Factory refrigerant charge of the product: see unit name plate

b.Additional refrigerant amount charged in the field

(Refer to the above information for the quantity of refrigerant replenishment.)

c.Total refrigerant charge

d.Refrigerant cylinder and manifold for charging

The filled-out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop valve cover).

Refrigerant type

GWP value

 

 

R410A

1975

 

 

 GWP=Global Warming Potential

Contains fluorinated greenhouse gases covered by the Kyoto Protocol.

Indoor unit

 

 

 

 

 

d

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a

 

 

 

Outdoor unit

= (

 

 

) kg

 

 

 

 

 

 

 

= (

 

 

) kg += (

 

) kg

 

 

 

 

b

 

 

 

c

Charging the refrigerant under conditions of liquid by using a liquid pipe

R410A is a mixed type of refrigerant. It is necessary for recharging under conditions of liquid. When recharging refrigerant from the refrigerant cylinder to the equipment, follow the instructions below.

Before recharging, check whether the cylinder has a siphon or not.

There are two ways to recharge the refrigerant.

Cylinder with siphon

Cylinder without siphon

siphon

Charge the refrigerant standing

Charge the refrigerant turning

 

the cylinder upright.

the cylinder upside down.

Note

If R410A refrigerant is charged with gas, the composition of the

charged refrigerant changes and the characteristics of the equipment vary.

During the measuring operation of refrigerant quantity added use an electronic balance. If cylinder doesn’t have syphon, upset it.

E-19

Vivaldi_IM_30271A_E_11.07.09.indd 19

2009-11-7 13:57:14

Image 19
Contents Vivaldi IM30271AE11.07.09.indd 2009-11-7 Contents English Safety PrecautionsMinor personal injury or property Model Choosing the Installation LocationTop view Side view  Figure DescriptionWhen installing more than 1 outdoor unit Following accessories are supplied with the air conditioner AccessoriesAccessories in the Indoor Unit Case Accessories in the Outdoor Unit CaseDirection of pipe Fixing the Installation PlateModel Power cable Interconnection Type GL Connecting the Assembly CableOutdoor unit Indoor unitDO not Wall UP the Pipe Connection Outer Diameter Torque kgfcmPurging the Indoor Unit Depth a Flaring Size B Cutting or Extending the PipeDrain hose installation Installing and Connecting the Drain Hose of the Indoor UnitChanging Direction of the Drain Hose Change the direction only when it is necessary Direction of the drained water Installing and Connecting the Drain Hose of the Outdoor Unit Reduction of cooling capacity and malfunction Purging the Connected PipesWith a Global Warming Potential GWP = You should purge the air in the indoor unit and in the pipe1975 Add refrigerant charge according to table below If you use a pipe Then GWP valueLeak Test with R410A after opening valves Performing the Gas Leak TestsTo check for gas leaks on Leak Test with Nitrogen before opening valvesFixing the Outdoor Unit in Place Fixing the Indoor Unit in PlaceFinal Check and Trial Operation Providing Information for User Pump Down Procedure When removing the productStorage in a handy and safe place Vivaldi IM30271AE11.07.09.indd 2009-11-7 Cooling and Heating Installation Manual