Annual startup (continued)
Clean condensate trap
1.Loosen condensate trap line hose clamps and remove trap line.
2.Empty water from trap line and inspect. Flush out if needed with fresh water.
3.Check condensate elbow and tee and condensate line to drain. Flush if necessary to clean.
4.Replace condensate trap line and tighten hose clamps.
5.Fill trap with fresh water by pouring into upturned end of PVC condensate tee.
Check water system
1.Verify all system components are correctly installed and operational.
2.Check the cold fill pressure for the system. Verify it is correct (usually around 12 psig).
3.Watch the system pressure as the boiler heats up (during testing) to ensure pressure doesn’t rise too high. Excessive pressure rise indicates expansion tank sizing or performance problem.
4.Inspect automatic air vents and air separators. Remove air vent caps and briefly press push valve to flush vent. Replace caps. Make sure vents do not leak. Replace any leaking vents.
Check all piping for leaks | Check expansion tank |
Eliminate all system or boiler leaks. Continual fresh
1.Inspect all water and gas piping and verify to be leak free.
2.Look for signs of leaking lines and correct any problems found.
3.Check gas line using procedure on page 21.
Check air openings
1.Verify that combustion and ventilation air openings to the boiler room and/or building are open and unobstructed. Check operation and wiring of automatic combustion air dampers, if used.
2.Verify that boiler vent discharge and air intake are clean and free of obstructions.
Flue vent system and air piping
1.Visually inspect entire flue gas venting system (and air piping, if installed) for blockage, deterioration or leakage. Repair any joints that show signs of leakage in accordance with vent manufacturer’s instructions. When air is ducted to boiler, verify that air inlet hose is connected and properly sealed.
Failure to inspect for the above conditions and have them repaired can result in severe personal injury or death.
1.Expansion tanks provide space for water to move in and out as the heating system water expands due to temperature increase or contracts as the water cools. Tanks may be open, closed or diaphragm or bladder type. See section 3 of this manual for suggested best location of expansion tanks and air eliminators.
•Make sure this type of tank is fitted with a tank fitting, such as the B & G
•Do not use automatic air vents in systems with
Diaphragm- or
•Systems with this type of expansion tank require at least one automatic air vent, preferably located on top of an air eliminator, as shown in examples in manual section 3.
2.If relief valve has tended to weep frequently, the expansion tank may be waterlogged or undersized.
Diaphragm- or