Heatiator CR36D, CL36D Installation of Fireplace, Things to Consider, Position the Fireplace

Page 22

7 Installation of Fireplace

CAUTION! Risk of Cuts/Abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges are sharp.

A. Things to Consider

Location of chimney air kit (see Figure 7.4)

Location of outside air kit

Electrical connections and/or wall switch

Gas line piping

B. Position the Fireplace

Place the fireplace on a continuous flat surface.

Follow framing instructions in Section 6.

WARNING! Risk of Fire! Prevent contact with sag- ging, loose insulation.

DO NOT install against vapor barriers or exposed insulation.

Secure insulation and vapor barriers.

Provide minimum air space clearances at the sides and back of the fireplace assembly as outlined in Section 6.

C. Place Protective Metal Hearth Strips

WARNING! Risk of Fire! Protective metal hearth strips MUST be installed. DO NOT cover metal strips with com- bustible materials. Sparks or embers may ignite flooring.

Refer to Figures 7.1 and 7.2.

Locate the two protective metal hearth strips measuring approximately 26 in. x 4 in. (660 mm x 102 mm) included with this fireplace.

Slide each metal strip 2 in. (51 mm) under front edge of fireplace.

Overlap strips in the middle of the front fireplace opening by 1 in. (25 mm) minimum.

Metal strips must extend beyond the front and sides of the fireplace opening by at least 2 in. (51 mm).

Protect the front of a platform elevated above the hearth extension with metal strips (not included with fireplace) per Figure 7.2. See Section 11 for hearth extension instructions.

D. Level Fireplace

Level fireplace side-to-side and front-to-back.

Shim with non-combustible material as necessary.

Secure fireplace to framing with nailing flanges with a minimum of two fasteners per nailing flange.

Check fireplace opening for square to ensure proper fit of glass doors. Measure diagonals of fireplace opening to make sure they are equal.

1" OVERLAP

Metal strip 2 in. (51 mm) under edge of fireplace openings and hearth extension.

Figure 7.1 Position the Protective Metal Hearth Strips

 

Top piece must overlap

 

bottom piece

 

Raised Platform

2 in.

1 in. (25 mm) min.

(51 mm)

overlap

Floor

2 in. (51 mm)

Figure 7.2 Protect the Front of an Elevated Platform

22

Heatilator • CL36D, CR36D • 12538 • Rev V • 05/09

Image 22
Contents Hot screen/mesh and glass doors will cause burns Wood Burning FireplaceFire Risk Grate Listing Label Information/LocationNumber Installer Guide Table of ContentsUser Guide Limited Warranty Heatilator CL36D, CR36D 12538 Rev V 05/09 Non-Combustible Materials Listing and Code ApprovalsAppliance Certification Combustible MaterialsYour Fireplace Operating InstructionsHot glass will cause burns Grate Seasoned WoodStarting a Fire FirescreenVented Gas Log Sets & Gas Log Lighters Glass DoorsOutside Air optional Optional ComponentsWood Fuel Hardwood vs SoftwoodChimney Inspection/Cleaning Maintenance and ServiceDisposal of Ashes Inspect Grate Glass CleaningCheck Firebox Refractory Frequency As desiredTroubleshooting Guide Start Fire Problems Possible Cause SolutionGetting Started Typical Fireplace SystemDraft Design and Installation ConsiderationsNegative Pressure Locating Fireplace & Chimney Frequently open doors Central heat outlets or returnsFireplace System Requirements Tools and Supplies NeededInspect Fireplace and Components Framing & Clearances Select Fireplace LocationClearances Clearances to Combustible MaterialsSidewalls/Surrounds Mantel Leg or Wall ProjectionsFrame the Fireplace RequiredPosition the Fireplace Installation of FireplaceThings to Consider Place Protective Metal Hearth StripsYES Install Outside Air Kit Outside Air InstallationChimney Assembly Chimney Requirements Height of Chimney ComponentsUsing Offsets/Returns ExampleInstall Ceiling Firestops Install Chimney Air KitAssemble Chimney Sections Install Attic Insulation Shield Mm overlapInstall Flashing Complete InstallationCut out Hole in Roof Chimney Termination Requirements Flat RoofsChase Installations Construct the ChaseInstall Chase Top Install Fireplace & ChimneyInstall Termination Cap ST375 Square Termination Cap Radiation Shield ShroudsField Constructed Shrouds Mailbox Style Shroud radiation shield required Hearth Extension Finishing= 1/k x inches of thickness Finishing Material In. Micore or equivilent insulationCombustible Mantel Mantel50 deg 16 3/4 in. Minimum 14-1/2 39 deg 18 in. Min Wood Burning Inserts AccessoriesGas Log/Lighter Provision Gas Code, Ansi Z223.1Fireplace Dimensions Reference MaterialsChimney Components Catalog #14-1/2 10-7/8 276 mm Service Parts CL36DParts Contact Information