E. Combustible Mantel

Ε Refer to the shaded areas of Figure 11.4 for locations and dimensions of a combustible mantel.

Ε A combustible mantel may be positioned no lower than 12 5/8 in. (321 mm) above the top of the fireplace opening.

Ε A combustible mantel may have a maximum depth of 10 in. (254 mm).

Ε Combustible trim and materials cannot be placed within 6 in. (152 mm) of the fireplace opening (top or sides).

Ε Combustible materials projecting more than 1 1/2 in. (38 mm) shall not be placed within 12 in. (305 mm) above the top of the fireplace opening.

Combustible trim must not cover the metal surfaces of the fireplace.

Mantel clearance is in accordance with Section 7-3.3.3of ANSI/NFPA211.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7 ft (2134 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

minimum

Combustible wall

 

 

 

 

 

 

 

 

 

 

 

Combustible

 

 

 

base of fireplace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

decorative facing

 

 

 

 

to ceiling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Grid represents

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 in. squares.

 

2 x 4 stud wall

 

 

 

 

 

 

10 in./254 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standoffs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mantel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12 5/8 in./321 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12 in./305 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

minimum

 

 

 

 

 

 

 

 

 

1 1/2 in./38 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

maximum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 in./152 mm

 

 

 

 

 

 

 

 

 

 

Non-combustible

 

 

 

 

 

 

 

 

 

 

 

 

 

minimum

 

 

 

 

 

 

 

 

 

 

decorative facing

 

 

 

 

 

 

 

 

 

 

 

 

 

such as steel, iron,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

brick, tile, concrete,

 

 

Measured from top of fireplace opening

 

slate, glass, plasters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Seal joint with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

non-combustible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sealant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ÎFigure 11.4 Clearances to Mantels or other Combustibles above Fireplace

Heatilator • CL36D, CR36D • 12538 • Rev V • 05/09

39

Image 39
Contents Wood Burning Fireplace Hot screen/mesh and glass doors will cause burnsFire Risk Listing Label Information/Location GrateNumber Table of Contents Installer GuideUser Guide Limited Warranty Heatilator CL36D, CR36D 12538 Rev V 05/09 Combustible Materials Listing and Code ApprovalsAppliance Certification Non-Combustible MaterialsOperating Instructions Your FireplaceHot glass will cause burns Firescreen Seasoned WoodStarting a Fire GrateOptional Components Glass DoorsOutside Air optional Vented Gas Log Sets & Gas Log LightersHardwood vs Softwood Wood FuelMaintenance and Service Chimney Inspection/CleaningDisposal of Ashes Frequency As desired Glass CleaningCheck Firebox Refractory Inspect GrateStart Fire Problems Possible Cause Solution Troubleshooting GuideTypical Fireplace System Getting StartedDesign and Installation Considerations DraftNegative Pressure Frequently open doors Central heat outlets or returns Locating Fireplace & ChimneyTools and Supplies Needed Fireplace System RequirementsInspect Fireplace and Components Select Fireplace Location Framing & ClearancesClearances to Combustible Materials ClearancesMantel Leg or Wall Projections Sidewalls/SurroundsRequired Frame the FireplacePlace Protective Metal Hearth Strips Installation of FireplaceThings to Consider Position the FireplaceYES Outside Air Installation Install Outside Air KitChimney Assembly Height of Chimney Components Chimney RequirementsExample Using Offsets/ReturnsInstall Chimney Air Kit Install Ceiling FirestopsAssemble Chimney Sections Mm overlap Install Attic Insulation ShieldComplete Installation Install FlashingCut out Hole in Roof Flat Roofs Chimney Termination RequirementsConstruct the Chase Chase InstallationsInstall Fireplace & Chimney Install Chase TopInstall Termination Cap ST375 Square Termination Cap Shrouds Radiation ShieldField Constructed Shrouds Mailbox Style Shroud radiation shield required Finishing Hearth Extension= 1/k x inches of thickness In. Micore or equivilent insulation Finishing MaterialMantel Combustible Mantel50 deg 16 3/4 in. Minimum 14-1/2 39 deg 18 in. Min Gas Code, Ansi Z223.1 AccessoriesGas Log/Lighter Provision Wood Burning InsertsReference Materials Fireplace DimensionsCatalog # Chimney Components14-1/2 10-7/8 276 mm CL36D Service PartsParts Contact Information