Heatiator CR36D, CL36D owner manual Chimney Requirements, Height of Chimney Components

Page 26

A. Chimney Requirements

Measure vertical distances from the base of the fireplace as shown in Figure 8.2.

Minimum overall straight height

14 ft

(4.27 m)

Minimum height with offset/return

14.5 ft

(4.42 m)

• Maximum height

50 ft

(15.24 m)

• Maximum chimney length between an offset

20 ft

(6.1 m)

 

and return

 

 

• Maximum distance between chimney

35 ft

(10.67 m)

 

stabilizers

 

 

Double offset/return minimum height

20 ft

(6.1 m)

• Maximum unsupported chimney length

6 ft

(1.83 m)

 

between the offset and return

 

 

• Maximum unsupported chimney height above

35 ft

(10.67 m)

 

the fireplace

 

 

• Maximum unsupported chimney above roof

6 ft

(1.83 m)

WARNING! Risk of Fire! You must maintain 2 in. (51

mm)air space clearance to insulation and other combus- tible materials around the chimney system. Failure to do so may cause overheating and fire.

Table 8.1

HEIGHT OF CHIMNEY COMPONENTS

in.

mm

Chimney Stabilizer

 

 

 

SL3

4-3/4

121

 

 

 

 

Ceiling Firestops

 

 

 

FS338

0

0

 

FS339

0

0

 

 

 

 

 

FS340

0

0

Offsets/Returns

 

 

 

SL315

13-3/8

340

 

SL330

15-1/2

394

Roof Flashing

 

 

 

RF370

0

0

 

RF371

0

0

 

 

 

 

Chimney Sections*

 

 

 

SL306

4-3/4

121

 

SL312

10-3/4

273

 

 

 

 

 

SL318

16-3/4

425

 

SL324

22-3/4

578

 

SL336

34-3/4

883

 

 

 

 

 

SL348

46-3/4

1187

* Dimensions reflect effective height.

 

 

Determine the chimney components needed to complete your particular installation:

Measure the total vertical height of the fireplace installation from the base of the fireplace assembly to the approximate location of the bottom of the termination cap.

Subtract the effective height of the fireplace assembly (see Figure 8.2) from the total vertical height to determine the overall height of the chimney installation.

Create a schematic for your application similar to Figure 8.2 showing components required (referring to Table 8.1). Figure 8.1 identifies those components and where used.

Install a ceiling firestop whenever the chimney penetrates a floor/ceiling.

NOTICE: A maximum of two pairs of offsets and returns may be used.

CAUTION! Risk of Fire and/or Asphyxiation! DO NOT connect this fireplace to a chimney flue servicing another appliance. DO NOT connect to any air distribu- tion duct or system. These actions could cause over- heating/fire in the chimney flue, or release of exhaust fumes into the living areas.

6 ft (1.83 m) max. unsupported chimney above roof

20 ft (6.10 m) max. pipe between an offset & return

 

 

 

 

 

 

 

 

 

 

35 ft (10.7 m)

Ceiling firestop

max. straight

unsupported

 

 

 

 

 

 

 

 

 

 

chimney height

 

 

 

 

 

 

 

 

 

 

 

14 ft (4.27 m) min. height

38 1/2 in. (978 mm)

 

 

(no offset-return)

Effective Height

 

50 ft (15.24 m) max. height

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 8.2 Chimney Requirements

26

Heatilator • CL36D, CR36D • 12538 • Rev V • 05/09

Image 26
Contents Fire Risk Wood Burning FireplaceHot screen/mesh and glass doors will cause burns Number Listing Label Information/LocationGrate User Guide Table of ContentsInstaller Guide Limited Warranty Heatilator CL36D, CR36D 12538 Rev V 05/09 Non-Combustible Materials Listing and Code ApprovalsAppliance Certification Combustible MaterialsHot glass will cause burns Operating InstructionsYour Fireplace Grate Seasoned WoodStarting a Fire FirescreenVented Gas Log Sets & Gas Log Lighters Glass DoorsOutside Air optional Optional ComponentsWood Fuel Hardwood vs SoftwoodDisposal of Ashes Maintenance and ServiceChimney Inspection/Cleaning Inspect Grate Glass CleaningCheck Firebox Refractory Frequency As desiredTroubleshooting Guide Start Fire Problems Possible Cause SolutionGetting Started Typical Fireplace SystemNegative Pressure Design and Installation ConsiderationsDraft Locating Fireplace & Chimney Frequently open doors Central heat outlets or returnsInspect Fireplace and Components Tools and Supplies NeededFireplace System Requirements Framing & Clearances Select Fireplace LocationClearances Clearances to Combustible MaterialsSidewalls/Surrounds Mantel Leg or Wall ProjectionsFrame the Fireplace RequiredPosition the Fireplace Installation of FireplaceThings to Consider Place Protective Metal Hearth StripsYES Install Outside Air Kit Outside Air InstallationChimney Assembly Chimney Requirements Height of Chimney ComponentsUsing Offsets/Returns ExampleAssemble Chimney Sections Install Chimney Air KitInstall Ceiling Firestops Install Attic Insulation Shield Mm overlapCut out Hole in Roof Complete InstallationInstall Flashing Chimney Termination Requirements Flat RoofsChase Installations Construct the ChaseInstall Termination Cap Install Fireplace & ChimneyInstall Chase Top ST375 Square Termination Cap Field Constructed Shrouds ShroudsRadiation Shield Mailbox Style Shroud radiation shield required = 1/k x inches of thickness FinishingHearth Extension Finishing Material In. Micore or equivilent insulationCombustible Mantel Mantel50 deg 16 3/4 in. Minimum 14-1/2 39 deg 18 in. Min Wood Burning Inserts AccessoriesGas Log/Lighter Provision Gas Code, Ansi Z223.1Fireplace Dimensions Reference MaterialsChimney Components Catalog #14-1/2 10-7/8 276 mm Service Parts CL36DParts Contact Information