Quadra-Fire 839-1340, 839-1320, 839-1290, 844-4120 owner manual Gas Pressures

Page 25

E

D

F

Figure 6.9 Ensure that the rubber gasket (D) is properly posi- tioned and install the new HI/LO pressure regulator assem- bly to the valve using the new screws (E) supplied with the kit. Tighten screws securely. (Reference torque = 25 in./lb.) Install the enclosed identification label (F) to the valve body where it can be seen.

Fill out the conversion label and attach it to the valve cover.

WARNING

Fire Risk.

Explosion Risk.

Gas Leak Risk.

Rubber gasket must be seated properly on valve face.

Do no install a valve or regulator that has been dropped.

WARNING

Fire Risk.

Explosion Risk.

If the information in these instructions is not followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life.

The qualified service agency is responsible for the proper installation of this conversion kit. The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer’s instructions supplied with the kit.

B. Gas Pressures

Proper input pressures required for optimum appliance per- formance, gas line sizing requirements need to be followed from NFPA51.

WARNING

Fire Risk.

Explosion Hazard.

High pressure will damage valve.

Disconnect gas supply piping BEFORE pressure testing gas line at test pressures above 1/2 psig.

Close the manual shutoff valve BEFORE pressure testing gas line at test pressures equal to or less than 1/2 psig.

WARNING

Verify inlet pressures.

High pressure may cause overfire condition.

Low pressure may cause explosion.

Install regulator upstream of valve if line pressure is greater than 1/2 psig.

Pressure requirements for appliance are shown in the table below.

PRESSURE

NG

LP

Minimum Inlet Pressure

4.5 inches w.c.

11.0 inches w.c.

Maximum Inlet Pressure

7.0 inches w.c.

14.0 inches w.c.

Manifold Pressure on “HI”

3.5 inches w.c.

10.0 inches w.c.

If the pressure is not sufficient, ensure:

1)the piping used is large enough.

2)the supply regulator is adequately adjusted.

3)that the total gas load for the residence does not exceed the amount supplied.

The supply regulator (the regulator that attaches directly to the residence inlet or to the propane tank) should supply gas at the suggested input pressure listed above. Contact the local gas supplier if the regulator is at an improper pressure.

January 3, 2007

Quadra-Fire · Topaz · 7009-113E

Page 25

Image 25
Contents Do not Discard this Manual What to do if you smell gasDo Discardnot Manufactured Date Table of Contents 1Listing and Code Approvals BELOW. Keep Clear of ALL Obstructions Requirements for the Commonwealth of MassachusettsManufacturer Requirements Getting Started Design & Installation ConsiderationsInspect Appliance & Components Tools and Supplies NeededSelecting Appliance Location Appliance Location and ClearancesClearances Design Purposes onlyVent Termination Minimum Clearances 4Termination LocationsAlcove Applications Venting Components Vent InformationUse of Elbows Measuring StandardsExceptions for Horizontal Installations How to Use the Vent GraphVenting Guidelines Vertical Distance from Appliance to 90 ElbowType B Rear Installations for Use with Rear Vent Kit Up & Out Installations for Top Vent ConfigurationsHorizontal Termination Type aRear Vent 203mm Direct Vent Pipe Vertical TerminationStep Wood Screws Twist-lock the vent cap and seal Cathedral Ceiling Class a Metal Chimney Existing Masonry Chimney Type a Up & Out Installations for Top Vent ConfigurationsCap Retro Connector Fuel Conversions Gas InformationConverting to LP Gas Propane Natural GAS Valve Regulator ReplacementPressure Gas PressuresCheck for GAS Leaks Gas ConnectionConnecting to the Appliance Recommendation for WireStanding Pilot Ignition System Wiring Wire Size Max. LengthON/OFF Remove Shipping Materials Appliance SetupTop to Rear Vent Conversion Leg Leveling System AccessoriesBrick Installation Front Installation Fronts shipped attached to faceFor Both Quartet and Solitaire Fronts Qty Description Positioning the LogsMineral Wool Blower Installation Glass Door Assembly Replacement31 Blower Wiring Diagram Shutter Adjustment Damper AdjustmentFor TOP or Rear Vent Installations Make adjustmentBefore Lighting Appliance Operating InstructionsControls Lighting Appliance For Your Safety Read Before LightingInitial Break-in Procedure Frequently Asked QuestionsAfter Appliance is Lit Symptom Possible Cause Corrective Action TroubleshootingBe Placed in this Opening After servicing Maintaining and Servicing Your ApplianceNecessary. USE Caution When CLEANING/HANDLING Ceramic Burner Maintenance Tasks InspectReference Materials Appliance Dimension DiagramVent Components Diagram Miscellaneous Vent Components ListItem # Description TopazBRNR-TOPAZ RD. Service Parts List cont’dRV-TPZ-CLG RV-TPZ-CCRRV-TPZ-CSB RV-TPZ-CWLCast Parts Individual Pieces RE. Accessories Warranty Policy This page Intentionally Left Blank Quadra-Fire · Topaz · 7009-113E January 3 This page Intentionally Left Blank Contact Information TopazDealer Telephone