Majestic Appliances RDV4136 Vertical Sidewall Applications, Install baffle to the deflector

Page 14

RDV4136 Series Direct Vent Gas Fireplace

Be sure to install the baffle as shown in Figure 16. Close half the opening when used on extended vent runs. Be sure there is no lifting or ghosting of the flame.

Flue Pipe

Flue Box

Baffle

Screws

FP1863

Fig. 15 Install baffle to the deflector.

 

Slot

 

Be sure this

 

portion is

Baffle

towards the

 

front of the

 

fireplace

FP1864

Fig. 16 Baffle in position, top view.

Vertical Sidewall Applications

Since it is very important that the vent- ing system maintain its balance between the combustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.

The vent graph showing the relationship between verti- cal and horizontal side wall venting will help to deter- mine the various dimensions allowable.

Minimum clearance between vent pipes and combustible materials is one 1” (25mm) on top, bottom and sides unless otherwise noted.

When the vent termination exits through foundations less than 20” (508 mm) below siding outcrop, the vent pipe must flush up with the siding.

It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length of vent pipe from the flue collar of the fireplace to the face of the outer wall.

20' (6m)

(2.3m)

Pipe

Straps Every

 

3’ (914mm)

7.5'

Pipe Straps

Every 3’ (914mm)

 

Firestop/Zero

 

Clearance Sleeve

 

FP1012

Fig. 17 Support straps for horizontal runs.

Horizontal plane means no vertical rise exists on this portion of the vent assembly.

The maximum number of 90° elbows per side wall installations is three (3).

If a 90° elbow is used in the horizontal vent run (level height maintained) the maximum horizontal vent length is reduced by 36” (914 mm). This does

not apply if the 90° elbows are used to increase or redirect a vertical rise.

Example: According to the chart the maximum vertical vent length in a system with a 7.5’ (2.3 m) horizontal rise is 20’ (6 m) and if a 90° is required in the horizontal vent it must be reduced to 17’ (5.2 m). In Figure 19, Dimension A plus B must not be greater than 17’ (5.2 m).

The maximum number of 45° elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run.

2'

(610 mm)

5' (1.5 m)

2'

(610 mm)

Minimum Horizontal

Vent Run

 

Maximum Horizontal

FP1821

Vent Run

Fig. 18

Horizontal vent run.

14

10010618

Image 14
Contents Builder Top Vent Direct Vent Models RDV4136 Table of Contents Ansi Z21.88-2005 / CSA Vented Gas Fireplace Heaters Installation & Operating InstructionsRDV4136 Certified To Requirements for the Commonwealth of Massachusetts Gas Equipment Venting System not ProvidedFireplace Dimensions Clearance to Combustibles Mantel ChartLocating Your Fireplace MantelsFraming and Finishing Gas Line InstallationHearth Final FinishingInstallation IN/IP Models Remote ON/OFF SwitchInstallation RN/RP Models EB-1 Electrical Box EB-1 receptacleGeneral Venting Location of Vent TerminationCanadian Installations1 US Installations2 General Venting Information Termination LocationGeneral Information on Assembling Vent Pipes Canadian InstallationsUSA Installations Flex Vent PipesExample a How to Use the Vent GraphTwist Lock Pipes Example BInstall baffle to the deflector Vertical Sidewall ApplicationsVertical Sidewall Installation Twist Lock Pipe Zero clearance sleeve is only required for combustible wallsAlways install horizontal venting on a level plane Vertical height requirementStep Vertical Sidewall Installation Flex Vent PipeBelow Grade Installations Vertical Through-the-Roof Installation Vertical Through-the-Roof ApplicationsMin 610 mm Venting Components Operating Instructions Window Frame Assembly RemovalGlass Cleaning Glass InformationLog Identification Chart Installation of Logs, Lava Rock & Ember MaterialLog Installation LogsEmber Material Left Cross Log Right Cross Log Rear Log Front Flame Characteristics Correct pilot flame appearanceTo Turn Off Gas To Heater Lighting and Operating InstructionsFor Fireplaces Equipped with the SIT 820 Valve Lighting Instructions Lighting & Operating InstructionsFor Fireplaces equipped with AF4000 Gas Valve Turning Off the Gas to the ApplianceTroubleshooting AF4000 ValveTroubleshooting AF4000 Valve Igniter operationAF4000 Valve Face Troubleshooting Honeywell VS8421 Remove Window Frame Assembly Before Service WorkNova SIT820 Valve Burner Orifice ConversionSkyTech Valve Pilot Orifice Conversion Injector Orifice Size MatrixLogs May Be HOT MaintenanceCleaning the Standing Pilot Control System Burner and Burner CompartmentRDV4136 Units GFSJ5J1RP RDV4136 Description RDV4136Fuel Conversion Kits Hard direct Wire Hook Up Optional AccessoriesFan Assembly Wiring InstructionsCeramic Refractory Panels Remote ControlsBack-up Battery Kit Porcelain Steel BackLimited Lifetime Warranty Efficiency Ratings