5. HEATING OPERATION

Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Fig. 5 On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow

of [Heat] operation modes Quiet, Lo, Me, High, as shown in Table 6. ( Fig.5 : Airflow change - over ( Heating : Auto ) )

When the room

 

When the room

TR : Room temperature

temperature rises

 

 

temperature drops

Ts : Setting temperature

 

 

 

 

 

TR-Ts > -1°C (-2°F)

 

Lo mode

 

 

 

 

 

 

 

 

 

=

 

 

 

 

TR-Ts > -1.5°C (-3°F)

 

 

 

 

 

 

 

 

 

 

 

=

 

-1°C (-2°F)> TR-Ts > -2°C (-4°F)

 

 

 

 

 

 

 

 

 

 

 

=

 

 

 

Me mode

 

-1.5°C (3°F) > TR-Ts > -2.5°C (-5°F)

 

 

 

 

 

 

=

-2°C (-4°F)> TR-Ts

 

 

 

 

 

 

 

 

Me+ mode

 

-2.5°C (-5°F)> TR-Ts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6. COOL AIR PREVENTION CONTROL (Heating mode)

The maximum value of the indoor fan speed is set as shown in Fig.6 based on the detected temperature by the indoor heat-exchanger sensor on heating mode.

( Fig.6 : Cool air prevension control )

 

<Normal operation>

<Powerful operation>

When the Indoor heat

When the Indoor heat

When the Indoor heat

exchanger temp. rises

exchanger temp. drops

exchanger temp. rises

When the Indoor heat

exchanger temp. drops

42°C (108°F)

39°C (102°F)

37°C (99°F)

30°C (86°F)

*Hi or setting Fan mode

*Me+ or setting Fan mode

*Lo or setting Fan mode

Cool air prevention

S-Lo

 

42°C

 

 

 

 

 

37°C (99°F)

(108°F)

39°C

 

 

 

 

 

(102°F)

34°C (93°F)

37°C

 

 

 

 

(99°F)

 

30°C

 

 

 

32°C (90°F)

(86°F)

 

28°C (82°F)

 

Powerful

 

 

 

 

Hi

 

 

 

37°C

 

 

 

 

 

 

 

(99°F)

Lo

 

 

 

 

34°C

 

 

 

Cool air

 

 

 

 

(93°F)

 

 

 

 

32°C

 

 

 

prevention

 

 

 

(90°F)

 

 

 

 

 

S-Lo

 

 

 

28°C

 

 

 

 

 

 

 

 

(82°F)

* Lower speed is selected.

*Lower speed is selected.

7.MOISTURE RETURN PREVENTION CONTROL (Cooling mode& Dry mode)

Switch the airflow [Auto] at cooling mode, and the indoor fan motor will run as shown in Fig.7. ( Fig.7 : Indoor fan control )

Compressor

ON

OFF

Indoor fan

Setting air flow

Indoor fan

(as shown in Table 7)

S-Lo

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

10

30

60

180

60

180

60

10

30

(sec)

( Table 7 : Indoor fan speed )

 

 

Dry

 

Cooling

 

 

 

 

 

X zone

J zone

Y zone

 

 

 

 

 

 

 

ASU09/12RL2

700rpm

600rpm

0 480rpm

700rpm

 

 

 

 

 

01-05

Image 10
Contents Service Instruction Contents Appending Data Page Wall Mounted type Cooling Operation Heating Operation DRY OperationAuto Changeover Operation 01-03FAN Operation Indoor FAN ControlFan speed Cooling OperationMoisture Return Prevention Control Cooling mode& Dry mode Cool AIR Prevention Control Heating modeHeating Operation Outdoor FAN Control Outdoor Fan MotorVertical Louver Control Adjust the RIGHT-LEFT LouversLouver Control Function RangeOpeartion Frequency Range Limitation of Compressor Frequency by Outdoor TemperatureCompressor Control Opeartion Frequency Control AT Normal Start UPTimer Opeartion Control Program TimerCooling operation mode Sleep TimerHeating operation mode Auto Restart Prevent to Restart for 3 Minutes 3 Minutes STFOUR-WAY Valve Extension Select 24C 75FCompressor Preheating Powerful OperationForced Cooling Operation Test Operation Economy OperationCondition of the Defrost Operation Completion Defrost Operation ControlCondition of Starting the Defrost Operation Release ConditionNormal defrost Integrating defrost Defrost Flow Chart01-14 OFF Defrost Opeartion Control Defrost end 01-15Current Release Control Discharge GAS Temperature Overrise Prevension ControlVarious Protections 01-16High Temperature Release Control Heating Mode Antifreezing Control Cooling and Dry modeCooling Pressure Overrise Protection Trouble Shooting Troubleshooting Error DisplayCheck Point 4 Check Serial Signal Reverse Transfer Signal Trouble Shooting with Error CodeOutdoor unit Main PCB Indoor unit Controller PCB Indoor unit Fan motor Check Point Check external cause such as noise Indoor unit Controller PCBCheck Point Check Indoor unit electric components Check Point 3 Replace Controller PCBIndoor unit Controller PCB Indicator PCB Manual auto switch Check Point 2 Replace Controller PCBIndoor unit Controller PCB Room temperature thermistor Indoor unit Controller PCB Heat Ex. temperature thermistor Check Point 2 Check ambient temp. around motor Check Point 3 Check Indoor unit fan motorCheck Point 2 Replace Main PCB Check Point 1-2 Check external causeCheck Point 2 Check connection of Connector Check Point 3 Replace Main PCB02-11 Outdoor unit Main PCB Discharge pipe temperature thermistor CN71 CN70Outdoor unit Main PCB Heat exchanger temperature thermistor Resistance Value k 606 759 213 8531Outdoor unit Main PCB Outdoor temperature thermistor Check Point 4 Replace Main PCB Check Point 2 Check Heat exchanger Outdoor unit Main PCB CompressorCheck Point 3 Check Compressor Check Point 3 Replace Main PCB Check Point 3 Check Outdoor unit fan motor Outdoor unit Main PCB Outdoor unit Fan motorCheck Point 4 Check Output Voltage of Main PCB Check Point 2 Check each thermistor Check Point 3 Check the solenoid coil and 4-way valveForecast of Cause Indoor Unit No Power Trouble Shooting with no Error CodeCheck Point 3 Check Electrical Components Outdoor Unit No Power 02-23 Check Point 2 Check Outdoor unit operation Check Point Check Indoor/ Outdoor installation conditionNo Cooling / No Heating Check Point 3 Check Site conditionAbnormal Noise Water LeakingCompressor Service Parts InformationReplace Compressor Inverter Compressor Blue Red Outdoor unit Electronic Expansion Valve EEVCheck Point 5 Check Opening and Closing Operation of Valve Indoor unit fan motor Outdoor unit fan motorPage Appending Data Cooling Room Temperature Correction Function SettingSetting the Filter Sign Heating Room Temperature CorrectionRemote controller signal code Setting the Auto RestartYes Procedures to change the Function Setting for wireless RC Selecting the Function Number and Setting Value Remote Controller Signal Code Setting Room temperature thermistor Discharge thermistorPage 1116,Suenaga,Takatsu-ku,Kawasaki 213-8502,Japan