Trouble shooting 15 OUTDOOR UNIT Error Method:
Compressor rotor position detection error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB Compressor
Detective details:
If the detected rotor location is out of phase with actual rotor location more than 90°, the compressor stops.
After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again.
If and repeats 5 times, the compressor stops permanently.
Forecast of Cause :
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
Check Point 1 : Check Noise from Compressor |
Turn on Power and check operation noise. |
If an abnormal noise show, replace Compressor. |
OK |
Check Point 2 : Check connection of around the Compressor components
For Compressor Terminal, Main PCB
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
(Refer to PARTS INFORMATION 2)
>>Upon correcting the removed connector or
OK
Check Point 3: Replace Main PCB |
If Check Point 1,2 do not improve the symptom, change Main PCB. |
OK |
Check Point 4: Replace Compressor |
If Check Point 3 do not improve the symptom, change Compressor. |