8.COMPRESSOR CONTROL
1.OPEARTION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as shown in the Table 11.
(Table 11 : Compressor frequency range)
| Cooling / Dry | Heating | |||
|
|
|
|
| |
| Minimum | Maximum | Minimum | Maximum | |
|
|
|
|
| |
AOU09RL2 | 18rps | 80rps | 18rps | 120rps | |
AOU12RL2 | 96rps | ||||
|
|
|
2.OPEARTION FREQUENCY CONTROL AT NORMAL START UP
The compressor frequency soon after the
Frequency |
|
|
|
|
|
Frequency |
|
|
|
|
|
Frequency |
|
|
|
|
|
Frequency |
|
|
|
|
|
Frequency |
|
|
|
|
|
Frequency |
|
|
|
|
|
Time | Time | Time | Time | Time | Time 6 |
(Frequency) |
|
|
|
|
|
Frequency Frequency Frequency Frequency Frequency Frequency
AOU09RL2 | 56rps | 67rps | 75rps | 78rps | 78rps | 78rps |
AOU12RL2 | 56rps | 74rps | 87rps | 97rps | 108rps | 119rps |
(Time) |
|
|
|
|
|
|
| Time | Time | Time | Time | Time | Time 6 |
|
|
|
|
|
|
|
AOU09RL2 | 80sec | 140sec | 200sec | 380sec | 440sec | 440sec |
AOU12RL2 | 60sec | 100sec | 140sec | 200sec | 350sec | 410sec |
3.LIMITATION OF COMPRESSOR FREQUENCY BY OUTDOOR TEMPERATURE
The minimum compressor frequency is limited by outdoor temperature as shown in the Table12.
(Table12 : Limitation of Compressor Frequency)
[ Cooling/ Dry ]
| 10°C (50°F) | 14°C (59°F) | 40°C (104°F) |
|
| ||||
| Under | Over | Under | Over | Under | Over |
|
| |
AOU09RL2 | 35rps | 23rps | 30rps |
|
| ||||
AOU12RL2 | 45rps | 27rps |
|
| |||||
|
|
|
|
| |||||
[ Heating ] |
|
|
|
|
|
|
|
| |
| - 3°C (26°F) | 7°C (45°F) | 14°C (59°F) | 40°C (104°F) | |||||
| Under | Over | Under | Over | Under | Over | Under | Over | |
AOU09RL2 | 34rps | 22rps | 27rps | 30rps | |||||
AOU12RL2 | 36rps | 27rps | 27rps | ||||||
|
|
|