Trouble shooting 11 OUTDOOR UNIT Error Method:
Outdoor unit Heat Ex. liquid temp. sensor error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB
Heat exchanger temperature thermistor
Detective details:
When Heat exchanger temperature thermistor open or
Forecast of Cause :
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or
OK
Check Pointi t 2 :: Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature |
| 0°C | 5°C | 10°C | 20°C | 30°C | ||||
| (14°F) | (23°F) | (32°F) | (41°F) | (50°F) | (68°F) | (86°F) | |||
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
Resistance Value (k | ) | 27.21 | 20.80 |
| 16.05 |
| 12.47 | 9.775 | 6.129 | 3.947 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Temperature |
| 40°C | 50°C |
| 60°C |
| 70°C | 80°C |
|
|
| (104°F) | (122°F) | (140°F) | (158°F) | (176°F) |
|
| |||
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
Resistance Value (k | ) | 2.606 | 1.759 |
| 1.213 |
| 0.8531 | 0.6115 |
|
|
|
|
|
|
|
|
|
|
|
|
|
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Poiintt 3 :: Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
THERMISTOR |
|
(PIPE) | BLACK |
| |
| BLACK |
| BLACK |
THERMISTOR | BLACK |
| |
(DISCHARGE) |
|
THERMISTOR |
(OUTDOOR) |
BLACK |
BLACK |
11
22 CN71
33
44
11
22 CN70
33
If the voltage does not appear, replace Main PCB.