Trouble shooting 17 INDOOR UNIT Error Method:
Indicate or Display:
Refer to error code table.
Detective Actuators:
Indoor unit Controller PCB Heat Ex. temperature thermistor Room temperature thermistor
Detective details:
When the indoor heat exchanger temperature is compared with the room temperature, and either following condition is detected continuously two times, the compressor stops.
Cooling or Dry operation
[Indoor heat exchanger temp.] - [Room temp.] > 10degC (20°F) Heating operation
[Indoor heat exchanger temp.] - [room temp.] < - 10degC
If the same operation is repeated 5 times, the compressor stops permanently.
Forecast of Cause :
1. | Connector connection failure 2. Thermistor failure 3. Coil failure 4. |
5. | Controller PCB failure |
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or
OK
Check Point 2 : Check each thermistor
Isn’t it fallen off the holder?
Is there a cable pinched?
>>Check characteristics of thermistor (Refer to Trouble shooting 5, 6), If defective, replace the thermistor
OK
Check Point 3 : Check the solenoid coil and 4-way valve
[ Solenoid coil ]
Remove CN30 from PCB and check the resistance value of coil. Resistance value is 1.88k 2.29k(at 20°C (68°F)).
>> If it is Open or abnormal resistance value, replace Solenoid Coil.
[
Check each piping temperature,
and the location of the valve by the temperature difference.
>>If the value location is not proper, replace
OK
Check Point 4 : Replace Controller PCB |
If Check Point 1- 3 do not improve the symptom, replace Controller PCB. |