Fujitsu AOU12RL2, ASU12RL2, AOU09RL2 manual Function Setting, Setting the Filter Sign, No indication

Page 55

3-1. FUNCTION SETTING

3-1-1 INDOOR UNIT

Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed condition.

After the power is turned on, perform the Function Setting on the remote control.

The settings may be selected between the following two: Function Number or Setting Value. Settings will not be changed if invalid numbers or setting values are selected.

1-1. Setting the Filter Sign

The indoor unit has a sign to inform the user that it is time to clean the filter. Select the time setting for the filter sign display interval in the table

below according to the amount of dust or debris in the room.

If you do not wish the filter sign to be displayed, select the setting value for "No indication".

 

(

Factory setting)

Setting Description

Function Number

Setting Value

Standard (400 hours)

 

00

 

 

 

Long interval (1000 hours)

11

01

 

 

Short interval ( 200 hours)

02

 

 

 

 

No indication

 

03

 

 

 

1-2. Cooling Room Temperature Correction

Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below.

 

(

Factory setting)

 

 

 

Setting Description

Function Number

Setting Value

 

 

 

Standard

 

00

Slightly lower control

30

01

 

 

Lower control

02

 

Warmer control

 

03

 

 

 

1-3. Heating Room Temperature Correction

Depending on the installed environment, the room temperature sensor may require a correction. The settings may be selected as shown in the table below.

 

(

Factory setting)

 

 

 

Setting Description

Function Number

Setting Value

 

 

 

Standard

 

00

Lower control

31

01

 

 

Slightly warmer control

02

 

 

 

 

Warmer control

 

03

 

 

 

03-01

Image 55
Contents Service Instruction Contents Appending Data Page Wall Mounted type Cooling Operation DRY Operation Heating Operation01-03 Auto Changeover OperationCooling Operation Indoor FAN ControlFan speed FAN OperationMoisture Return Prevention Control Cooling mode& Dry mode Cool AIR Prevention Control Heating modeHeating Operation Outdoor Fan Motor Outdoor FAN ControlFunction Range Adjust the RIGHT-LEFT LouversLouver Control Vertical Louver ControlOpeartion Frequency Control AT Normal Start UP Limitation of Compressor Frequency by Outdoor TemperatureCompressor Control Opeartion Frequency RangeProgram Timer Timer Opeartion ControlCooling operation mode Sleep TimerHeating operation mode 24C 75F Prevent to Restart for 3 Minutes 3 Minutes STFOUR-WAY Valve Extension Select Auto RestartEconomy Operation Powerful OperationForced Cooling Operation Test Operation Compressor PreheatingRelease Condition Defrost Operation ControlCondition of Starting the Defrost Operation Condition of the Defrost Operation CompletionNormal defrost Integrating defrost Defrost Flow Chart01-14 Defrost end 01-15 OFF Defrost Opeartion Control01-16 Discharge GAS Temperature Overrise Prevension ControlVarious Protections Current Release ControlHigh Temperature Release Control Heating Mode Antifreezing Control Cooling and Dry modeCooling Pressure Overrise Protection Trouble Shooting Error Display TroubleshootingCheck Point 4 Check Serial Signal Reverse Transfer Signal Trouble Shooting with Error CodeOutdoor unit Main PCB Indoor unit Controller PCB Indoor unit Fan motor Check Point 3 Replace Controller PCB Indoor unit Controller PCBCheck Point Check Indoor unit electric components Check Point Check external cause such as noiseCheck Point 2 Replace Controller PCB Indoor unit Controller PCB Indicator PCB Manual auto switchIndoor unit Controller PCB Room temperature thermistor Indoor unit Controller PCB Heat Ex. temperature thermistor Check Point 3 Check Indoor unit fan motor Check Point 2 Check ambient temp. around motorCheck Point 1-2 Check external cause Check Point 2 Replace Main PCBCheck Point 3 Replace Main PCB Check Point 2 Check connection of Connector02-11 CN71 CN70 Outdoor unit Main PCB Discharge pipe temperature thermistorResistance Value k 606 759 213 8531 Outdoor unit Main PCB Heat exchanger temperature thermistorOutdoor unit Main PCB Outdoor temperature thermistor Check Point 4 Replace Main PCB Check Point 2 Check Heat exchanger Outdoor unit Main PCB CompressorCheck Point 3 Check Compressor Check Point 3 Replace Main PCB Check Point 3 Check Outdoor unit fan motor Outdoor unit Main PCB Outdoor unit Fan motorCheck Point 4 Check Output Voltage of Main PCB Check Point 3 Check the solenoid coil and 4-way valve Check Point 2 Check each thermistorForecast of Cause Indoor Unit No Power Trouble Shooting with no Error CodeCheck Point 3 Check Electrical Components Outdoor Unit No Power 02-23 Check Point 3 Check Site condition Check Point Check Indoor/ Outdoor installation conditionNo Cooling / No Heating Check Point 2 Check Outdoor unit operationWater Leaking Abnormal NoiseCompressor Service Parts InformationReplace Compressor Inverter Compressor Blue Red Outdoor unit Electronic Expansion Valve EEVCheck Point 5 Check Opening and Closing Operation of Valve Outdoor unit fan motor Indoor unit fan motorPage Appending Data Heating Room Temperature Correction Function SettingSetting the Filter Sign Cooling Room Temperature CorrectionRemote controller signal code Setting the Auto RestartYes Procedures to change the Function Setting for wireless RC Selecting the Function Number and Setting Value Remote Controller Signal Code Setting Discharge thermistor Room temperature thermistorPage 1116,Suenaga,Takatsu-ku,Kawasaki 213-8502,Japan