Trouble shooting 18 OUTDOOR UNIT Error Method:
Discharge temperature error
Indicate or Display:
Refer to error code table.
Detective Actuators:
Outdoor unit Main PCB Discharge temperature thermistor
Detective details:
"Protection stop by "discharge temperature 110degC during compressor operation"" generated 2 times within 24 hours.
Forecast of Cause : 1. | 2/ | 2. Capillary tube, strainer clogged |
3. | Outdoor unit operation failure, foreign matter on heat exchanger | |
4. | Discharge temperature thermistor failure | 5. Insufficient refrigerant |
6. | Main PCB failure |
|
|
|
|
<Cooling operation>
Check Point 1 : Check if
If the
<Heating operation>
Check Point 1 : Check if
If the
OK
Check Point 2 : Check the capillary tube, strainer
Capillary tube, Strainer(after Capillary) clogging check. Refer to "Service Parts Information 3".
OK
Check Point 2 : Check the capillary tube, strainer
Capillary tube, Strainer(before Capillary) clogging check. Refer to "Service Parts Information 3".
OK
Check Point 3 : Check the outdoor unit fan,heat exchanger
Check for foreign object at heat exchanger
Check if fan can be rotated by hand.
Motor check (PARTS INFORMATION 5)
OK
Check Point 4 : Check the discharge thermistor
Discharger thermistor characteristics check. (Check by disconnecting thermistor from PCB.)
OK
* For the characteristics of the thermistor, refer to the "Trouble shooting 10".
OK
Check Point 5 : Check the refrigerant amount
Leak check