2. HEATING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor.
*If the room temperature is lower by 3°C (6°F) than a set temperature, the compressor operation frequency will attain to maximum performance.
*If the room temperature is some degrees higher than a set temperature,
the compressor will be stopped.
*When the room temperature is between +2.5°C (+5°F) to
However, the maximum frequency is limited shown in Table 4 based on the fan mode.
( Table 3 : Compressor frequency range )
| Minimum | Maximum | |
| frequency | frequency | |
|
|
| |
AOU09RL2 | 18rps | 80rps | |
AOU12RL2 | 120rps | ||
|
( Table 4 : Limit of maximum speed based on outdoor temperature )
|
| Indoor fan mode |
|
|
| |
|
|
|
|
|
|
|
|
| Hi | Me | Lo | Quiet | Auto |
AOU09RL2 |
|
| 80rps |
|
| |
AOU12RL2 |
|
| 120rps |
|
|
3. DRY OPERATION
The compressor frequency shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table 5.
However, after the compressor is driven, the indoor unit shall run at operation frequency of (09 : 52 rps, 12 : 61 rps) for 60 seconds.
( Table 5 : Compressor frequency in Dry mode)
|
| Operating |
|
| frequency |
AO09RL2 | X zone | 30rps |
| J zone | 28rps |
| Y zone | 0rps |
|
| Operating |
|
| frequency |
AO12RL2 | X zone | 33rps |
| J zone | 25rps |
| Y zone | 0rps |
( Fig.2 : Compressor control based on room temperature )
|
| When the room | |
When the room | temperature rises | ||
temperature drops |
| Ts+1.5°C (Ts+3°F) | |
| |||
|
|
| |
Ts+0.5°C (Ts+1°F) | X zone |
|
|
|
| Ts | |
|
|
| |
Ts | J zone |
|
|
|
|
| |
| Y zone |
|
|
|
|
| |
|
|
|
|