5. INDOOR FAN CONTROL
1. Fan speed
( Table 6 : Indoor fan speed )
Operation mode | Air flow mode | Speed (rpm) | ||
ASU09RL2 | ASU12RL2 | |||
|
| |||
|
|
|
| |
Heating | Powerful | 1420 | 1420 | |
| Hi | 1360 | 1360 | |
| Me+ | 1290 | 1290 | |
| Me | 1120 | 1120 | |
| Lo | 900 | 900 | |
| Quiet | 700 | 700 | |
| Cool air prevention | 600 | 600 | |
| 480 | 480 | ||
Cooling/ Fan | Powerful | 1400 | 1400 | |
| Hi | 1320 | 1320 | |
| Me | 1120 | 1120 | |
| Lo | 840 | 860 | |
| Quiet | 700 | 700 | |
| * Soft Quiet | 600 | 600 | |
Dry |
| X zone: 700 | X zone: 700 | |
|
| J zone: 600 | J zone: 600 | |
|
|
|
|
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs. (Hi > Me, Me > Lo, Lo > Quiet, Quiet > Soft Quiet)
2. FAN OPERATION
The airflow can be switched in 5 steps such as Auto, Quiet, Lo, Me, Hi, while the indoor fan only runs. When fan mode is set at [Auto], it operates on [Me] fan Speed.
3. COOLING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature, as shown in Fig4. On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow of [Cool] operation modes Quiet, Lo, Me, Hi, as shown in Table 6.
( Fig.4 : Airflow change - over ( Cooling : Auto ) )
|
|
|
| When the room |
| ||
When the room |
| temperature rises |
| ||||
|
|
|
|
| |||
temperature drops |
|
| TR : Room temperature | ||||
| Hi mode |
|
| = | Ts : Setting temperature | ||
|
|
| 2.5°C (5°F) > | ||||
|
|
|
|
| |||
|
|
|
| ||||
2°C (4°F) > |
| Me mode |
|
|
| = | |
|
|
|
|
| |||
= |
|
|
|
|
|
|
|
|
| Lo mode |
| 1.5°C (3°F) > |
| ||
|
|
|
|
| |||
1°C (2°F) > |
|
| |||||
|
|
|
|
|
4.DRY OPERATION
Refer to the Table 6.
During the dry mode operation, the fan speed setting can not be changed.