Bryant 340MAV IV. Horizontal Left SUPPLY-AIR Discharge Applications, Construct a Working Platform

Page 10

IV. HORIZONTAL LEFT (SUPPLY-AIR DISCHARGE) APPLICATIONS

A horizontal left furnace application is where furnace blower is located to the right of combustion and controls section of furnace, and conditioned air is discharged to the left.

NOTE: The auxiliary junction box (J-Box) MUST be relocated to opposite side of furnace casing. (See Fig. 10.) See Electrical Connection section for J-Box relocation.

A. Condensate Trap Location

The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 10.

To relocate condensate trap from the blower shelf to desired location, perform the following:

1.Remove 3 tubes connected to condensate trap.

2.Remove trap from blower shelf by gently pushing tabs inward and rotating trap.

3.Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.

WARNING: Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated. Failure to follow this warning could result in electrical shock, fire, personal injury or death.

4.Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.

5.Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).

B.Condensate Trap Tubing

NOTE: See Fig. 10 or tube routing label on main furnace door to check for proper connections.

1.Collector Box Drain Tube

a.Install drain tube coupling (factory-supplied in loose parts bag) into collector box drain tube (blue label) which was previously connected to condensate trap.

b.Connect large diameter drain tube and clamp (factory- supplied in loose parts bag) to drain tube coupling, extending collector box drain tube.

c.Route extended tube (blue label) to condensate trap and cut to appropriate length.

d.Clamp tube to prevent any condensate leakage.

2.Inducer Housing Drain Tube

a.Remove and discard LOWER (molded) inducer housing drain tube which was previously connected to conden- sate trap.

b.Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to the con- densate trap.

c.Determine appropriate length, cut, and connect tube.

d.Clamp tube to prevent any condensate leakage.

3.Relief Port Tube

a.Extend collector box tube (green label) which was previously connected to the condensate trap by splicing to small diameter tube (factory-supplied in loose parts bag).

b.Route extended collector box pressure tube to relief port connection on the condensate trap.

c.Determine appropriate length, cut, and connect tube.

d.Clamp tube to prevent any condensate leakage.

C. Condensate Trap Field Drain Attachment

Refer to Condensate Drain section for recommendations and procedures.

D. Pressure Switch Tubing

The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected, extended, rerouted, and then reconnected to the pressure switch in HORIZONTAL LEFT applications.

NOTE: See Fig. 10 or tube routing label on main furnace door to check for proper connections.

Modify tube as described below.

1.Disconnect collector box pressure tube (pink label) attached to pressure switch.

2.Use smaller diameter tube (factory-supplied in loose parts bag) to extend tube disconnected in item 1.

3.Route extended tube:

a.Behind inducer housing.

b.Between blower shelf and inducer housing.

c.Behind inducer motor bracket.

d.Between inducer motor and pressure switch.

4.Determine appropriate length, cut, and reconnect tube to pressure switch connection labeled COLLECTOR BOX.

E.Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommenda- tions and procedures.

F. Construct a Working Platform

Construct working platform where all required furnace clearances are met. (See Fig. 3 and 11.)

CAUTION: The condensate trap MUST be installed

below furnace. See Fig. 5 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain. Failure to follow this caution will result in intermittent unit operation.

NOTE: Combustion-air and vent pipes are restricted to a mini- mum length of 5 ft. (See Table 7.)

NOTE: A 12-in. minimum offset pipe section is recommended with short (5 to 8 ft) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 11 or 34.)

V.HORIZONTAL RIGHT (SUPPLY-AIR DISCHARGE) APPLICATIONS

A horizontal right furnace application is where furnace blower is located to the left of combustion and controls section of furnace, and conditioned air is discharged to the right.

CAUTION: Local codes may require a drain pan under entire furnace and condensate trap when a condensing

furnace is used in attic application or over a finished ceiling. Failure to follow this caution will result in minor property damage.

NOTE: In Canada, installations shall be in accordance with current NSCNGPIC Installation Codes and/or local codes. NOTE: The auxiliary junction box (J-Box) MUST be relocated to opposite side of furnace casing. (See Fig. 12.) See Electrical Connection section for J-Box relocation.

—10—

Image 10
Contents Electrostatic Discharge ESD Precautions Safety ConsiderationsMultipoise Orientations Dimensions Unit SizeVI. GAS Piping and GAS Pipe Pressure Testing SafetyII. General Installation Codes and StandardsElectrostatic Discharge ESD Precautions VII. Electrical ConnectionsGeneral IntroductionApplications II. Upflow ApplicationsCondensate Trap Location Alternate Upflow Orientation Pressure Switch TubingCondensate Trap Tubing Factory-Shipped Orientation Condensate Trap Tubing Alternate Upflow OrientationCondensate Trap Location III. Downflow ApplicationsCondensate Trap Tubing Horizontal Left Tube Configuration Construct a Working Platform IV. Horizontal Left SUPPLY-AIR Discharge ApplicationsHorizontal Right SUPPLY-AIR Discharge Applications Attic Location and Working Platform Location Furnace Location for Proper Condensate Drainage II. Furnace Location Relative to Cooling EquipmentIII. Installation in Horizontal Applications II. Installation in Upflow or Downflow ApplicationsInstallation Leveling Legs if Desired III. Hazardous LocationsFurnace Plenum Opening Floor Opening Casing Opening DimensionsWidth Duct Flanges II. Ductwork Acoustical TreatmentFilter Arrangement III. Supply AIR ConnectionsIV. Return AIR Connections Filter InformationMaximum Capacity of Pipe VI. Bottom Closure PanelVII. GAS Piping Casings onlyFire or Explosion Hazard Electrical ConnectionsWiring III AccessoriesPCB Removal of Existing Furnaces from Common Vent Systems Electrical DataDirect Venting II. COMBUSTION-AIR and Vent PipingControl Center COMBUSTION-AIR and Vent Pipe Termination Clearances Clearance FTExample Combustion-Air and Vent Pipe DiameterCombustion-Air and Vent Pipe Attachment COMBUSTION-AIR Intake Housing Plug Fitting Short Vent 5 to 8 Ft SystemMaximum Allowable Pipe Length FT Altitude FT6001 to 7000‡ Air Intake Housing Plug Fitting Drain Extended Exposed Sidewall Pipes Vent Extension PipeTwo-Pipe Termination Kit Concentric Vent/Air Termination Kit IV. Multiventing and Vent TerminationsRoof Termination Preferred Sidewall Termination of 12 in. or Less II. Application Condensate Drain GeneralIII. Condensate Drain Protection III. Continuous Blower Mode Heating ModeII. Cooling Mode IV. Heat Pump ModeComponent Test START-UP Procedures GeneralIV. Adjustments II. Prime Condensate Trap with WaterInducer Housing Drain Cap BTU/CU FT Orifice Manifold 625 650 Only 7001 675 725 8000 775 750 15% 825 2001to 725 750 Only 4001 775 800 825 5000 875 850 900 925 United States Example 100,000 Btuh Input Furnace Installed AT 4300 FTAltitude Derate Multiplier CanadaGAS Rate CU FT/HR Blower OFF Delay Setup PositionCheck Safety Controls Speed SelectorChecklist II. Check Pressure SwitchCheck Primary Limit Control Load Calculation CHECKLIST-INSTALLATIONCHECKLIST-START-UP Combustion AIR Vent Piping
Related manuals
Manual 12 pages 2.16 Kb Manual 44 pages 12.97 Kb

340MAV specifications

The Bryant 340MAV is a standout model in the Bryant lineup, designed to provide exceptional comfort, efficiency, and performance for residential heating and cooling needs. This unit offers a perfect blend of innovative technology and user-friendly features, making it an ideal choice for homeowners seeking reliability and quality.

One of the defining characteristics of the Bryant 340MAV is its impressive efficiency rating. With a SEER (Seasonal Energy Efficiency Ratio) of up to 18, this model ensures that homeowners can enjoy effective cooling during the summer months while minimizing energy consumption. Similarly, the heating efficiency is notable, with a high AFUE (Annual Fuel Utilization Efficiency) rating. This makes the 340MAV an environmentally friendly option that also promotes cost savings on energy bills.

The 340MAV incorporates advanced technologies that enhance its performance. One such technology is the variable-speed compressor, which allows the system to adjust its output based on the demands of the home. This means that the unit operates more quietly and reduces energy usage by matching the cooling or heating output required. Additionally, the two-stage heating capability provides more consistent temperatures and improved comfort throughout the space.

Operating noise is a crucial factor in residential HVAC systems, and the Bryant 340MAV is designed with this in mind. Engineered for quiet operation, the unit features a sound-dampening design, including an insulated cabinet and a specially designed compressor that minimizes noise levels. Homeowners can enjoy a comfortable indoor climate without the disruptive racket often associated with traditional systems.

Furthermore, the Bryant 340MAV is equipped with a durable all-aluminum coil, which improves heat transfer efficiency while also being resistant to corrosion. This characteristic contributes to the longevity of the unit, ensuring that it can withstand various environmental factors without compromising performance.

Another key feature is the advanced control options that the Bryant 340MAV offers. Integration with smart thermostats allows homeowners to monitor and adjust their HVAC system remotely, ensuring optimal comfort at all times. Additionally, the system is compatible with Bryant's Perfect Airâ„¢ filtration system, enhancing indoor air quality by reducing pollutants and allergens.

In summary, the Bryant 340MAV is a high-efficiency heating and cooling solution that brings together cutting-edge technology, quiet operation, and user-friendly features. With its focus on comfort and energy savings, it stands out as a prime choice for homeowners looking to invest in a reliable HVAC system.