Bryant 340MAV instruction manual Orifice Manifold

Page 39

 

 

TABLE 9—MODEL 340MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT

(Continued)

 

 

 

 

FOR USE WITH 040 THROUGH 120 SIZE FURNACES ONLY

 

 

 

 

 

 

 

(TABULATED DATA BASED ON 20,000 BTUH PER BURNER, DERATED 2% FOR EACH 1000 FT ABOVE SEA LEVEL)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

 

HEAT VALUE

 

0.58

 

0.60

 

0.62

 

0.64

 

 

0.66

 

 

RANGE

 

 

 

 

 

 

 

 

(FT)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

Orifice

 

Manifold

 

 

(BTU/CU FT)

 

 

 

 

 

 

 

 

 

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

 

No.

 

Pressure

 

 

 

725

43

 

3.7

43

 

3.8

42

 

3.2

42

 

3.3

 

42

 

3.4

 

 

 

750

43

 

3.4

43

 

3.5

43

 

3.7

43

 

3.8

 

42

 

3.2

Only

 

4001

775

44

 

3.7

44

 

3.8

43

 

3.4

43

 

3.5

 

43

 

3.7

 

 

800

44

 

3.5

44

 

3.6

44

 

3.7

44

 

3.8

 

43

 

3.4

 

 

 

 

 

 

 

 

 

U.S.A.

 

to

825

44

 

3.2

44

 

3.4

44

 

3.5

44

 

3.6

 

44

 

3.7

 

5000

875

45

 

3.5

45

 

3.6

45

 

3.7

44

 

3.2

 

44

 

3.3

 

 

 

850

45

 

3.7

45

 

3.8

44

 

3.3

44

 

3.4

 

44

 

3.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

900

45

 

3.3

45

 

3.4

45

 

3.5

45

 

3.6

 

45

 

3.8

 

 

0%

925

45

 

3.1

45

 

3.2

45

 

3.3

45

 

3.4

 

45

 

3.6

 

 

derate

950

45

 

3.0

45

 

3.1

45

 

3.2

45

 

3.3

 

45

 

3.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

 

HEAT VALUE

 

0.58

 

0.60

 

0.62

 

0.64

 

 

0.66

 

 

RANGE

 

 

 

 

 

 

 

 

(FT)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

Orifice

 

Manifold

 

 

(BTU/CU FT)

 

 

 

 

 

 

 

 

 

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

 

No.

 

Pressure

 

 

 

700

43

 

3.6

43

 

3.7

42

 

3.2

42

 

3.3

 

42

 

3.4

 

 

 

725

43

 

3.4

43

 

3.5

43

 

3.6

43

 

3.7

 

43

 

3.8

 

 

 

750

44

 

3.6

44

 

3.7

43

 

3.4

43

 

3.5

 

43

 

3.6

 

 

 

775

44

 

3.4

44

 

3.5

44

 

3.6

44

 

3.7

 

43

 

3.4

Only

 

5001

800

44

 

3.2

44

 

3.3

44

 

3.4

44

 

3.5

 

44

 

3.6

 

 

825

45

 

3.6

45

 

3.7

44

 

3.2

44

 

3.3

 

44

 

3.4

 

 

 

 

 

 

 

 

 

U.S.A.

 

to

850

45

 

3.4

45

 

3.5

45

 

3.6

45

 

3.8

 

44

 

3.2

 

 

875

45

 

3.2

45

 

3.3

45

 

3.4

45

 

3.6

 

45

 

3.7

 

 

 

 

 

 

 

 

 

 

 

6000

900

45

 

3.0

45

 

3.1

45

 

3.3

45

 

3.4

 

45

 

3.5

 

 

 

925

45

 

2.9

45

 

3.0

45

 

3.1

45

 

3.2

 

45

 

3.3

 

 

 

950

45

 

2.7

45

 

2.8

45

 

2.9

45

 

3.0

 

45

 

3.1

 

 

11%

975

45

 

2.6

45

 

2.7

45

 

2.8

45

 

2.9

 

45

 

2.9

 

 

derate

1000

45

 

2.5

45

 

2.5

45

 

2.6

45

 

2.7

 

45

 

2.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALTITUDE

AVG GAS

 

 

 

 

 

SPECIFIC GRAVITY OF NATURAL GAS

 

 

 

 

 

HEAT VALUE

 

0.58

 

0.60

 

0.62

 

0.64

 

 

0.66

 

 

RANGE

 

 

 

 

 

 

 

 

(FT)

AT ALTITUDE

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

Orifice

 

Manifold

 

Orifice

 

Manifold

 

 

(BTU/CU FT)

 

 

 

 

 

 

 

 

 

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

No.

 

Pressure

 

No.

 

Pressure

 

 

 

650

42

 

3.2

42

 

3.3

42

 

3.4

42

 

3.5

 

42

 

3.6

 

 

 

675

43

 

3.6

43

 

3.7

43

 

3.8

42

 

3.2

 

42

 

3.3

Only

 

6001

700

44

 

3.8

43

 

3.4

43

 

3.6

43

 

3.7

 

43

 

3.8

 

 

725

44

 

3.6

44

 

3.7

44

 

3.8

43

 

3.4

 

43

 

3.5

 

 

 

 

 

 

 

 

 

U.S.A.

 

to

750

44

 

3.3

44

 

3.4

44

 

3.6

44

 

3.7

 

44

 

3.8

 

7000

800

45

 

3.5

45

 

3.7

45

 

3.8

44

 

3.2

 

44

 

3.3

 

 

 

775

45

 

3.8

44

 

3.2

44

 

3.3

44

 

3.4

 

44

 

3.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

825

45

 

3.3

45

 

3.4

45

 

3.6

45

 

3.7

 

45

 

3.8

 

 

13%

850

45

 

3.1

45

 

3.2

45

 

3.4

45

 

3.5

 

45

 

3.6

 

 

derate

875

45

 

3.0

45

 

3.1

45

 

3.2

45

 

3.3

 

45

 

3.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Orifice numbers shown in BOLD are factory installed.

Percents of derate are based on midpoints of U.S. altitude ranges.

—39—

Image 39
Contents Safety Considerations Electrostatic Discharge ESD PrecautionsMultipoise Orientations Unit Size DimensionsCodes and Standards SafetyII. General Installation VI. GAS Piping and GAS Pipe Pressure TestingVII. Electrical Connections Electrostatic Discharge ESD PrecautionsII. Upflow Applications IntroductionApplications GeneralCondensate Trap Tubing Alternate Upflow Orientation Pressure Switch TubingCondensate Trap Tubing Factory-Shipped Orientation Condensate Trap Location Alternate Upflow OrientationIII. Downflow Applications Condensate Trap LocationCondensate Trap Tubing Horizontal Left Tube Configuration IV. Horizontal Left SUPPLY-AIR Discharge Applications Construct a Working PlatformHorizontal Right SUPPLY-AIR Discharge Applications Attic Location and Working Platform Location II. Furnace Location Relative to Cooling Equipment Furnace Location for Proper Condensate DrainageIII. Hazardous Locations II. Installation in Upflow or Downflow ApplicationsInstallation Leveling Legs if Desired III. Installation in Horizontal ApplicationsOpening Dimensions Furnace Plenum Opening Floor Opening CasingWidth II. Ductwork Acoustical Treatment Duct FlangesFilter Information III. Supply AIR ConnectionsIV. Return AIR Connections Filter ArrangementCasings only VI. Bottom Closure PanelVII. GAS Piping Maximum Capacity of PipeElectrical Connections Fire or Explosion HazardIII Accessories WiringPCB II. COMBUSTION-AIR and Vent Piping Electrical DataDirect Venting Removal of Existing Furnaces from Common Vent SystemsControl Center Clearance FT COMBUSTION-AIR and Vent Pipe Termination ClearancesCombustion-Air and Vent Pipe Diameter ExampleCombustion-Air and Vent Pipe Attachment Short Vent 5 to 8 Ft System COMBUSTION-AIR Intake Housing Plug FittingAltitude FT Maximum Allowable Pipe Length FT6001 to 7000‡ Air Intake Housing Plug Fitting Drain Vent Extension Pipe Extended Exposed Sidewall PipesTwo-Pipe Termination Kit IV. Multiventing and Vent Terminations Concentric Vent/Air Termination KitRoof Termination Preferred Sidewall Termination of 12 in. or Less Condensate Drain General II. ApplicationIII. Condensate Drain Protection IV. Heat Pump Mode Heating ModeII. Cooling Mode III. Continuous Blower ModeII. Prime Condensate Trap with Water START-UP Procedures GeneralIV. Adjustments Component TestInducer Housing Drain Cap BTU/CU FT Orifice Manifold 625 650 Only 7001 675 725 8000 775 750 15% 825 2001to 725 750 Only 4001 775 800 825 5000 875 850 900 925 Canada Example 100,000 Btuh Input Furnace Installed AT 4300 FTAltitude Derate Multiplier United StatesSpeed Selector Blower OFF Delay Setup PositionCheck Safety Controls GAS Rate CU FT/HRII. Check Pressure Switch ChecklistCheck Primary Limit Control Combustion AIR Vent Piping CHECKLIST-INSTALLATIONCHECKLIST-START-UP Load Calculation
Related manuals
Manual 12 pages 2.16 Kb Manual 44 pages 12.97 Kb

340MAV specifications

The Bryant 340MAV is a standout model in the Bryant lineup, designed to provide exceptional comfort, efficiency, and performance for residential heating and cooling needs. This unit offers a perfect blend of innovative technology and user-friendly features, making it an ideal choice for homeowners seeking reliability and quality.

One of the defining characteristics of the Bryant 340MAV is its impressive efficiency rating. With a SEER (Seasonal Energy Efficiency Ratio) of up to 18, this model ensures that homeowners can enjoy effective cooling during the summer months while minimizing energy consumption. Similarly, the heating efficiency is notable, with a high AFUE (Annual Fuel Utilization Efficiency) rating. This makes the 340MAV an environmentally friendly option that also promotes cost savings on energy bills.

The 340MAV incorporates advanced technologies that enhance its performance. One such technology is the variable-speed compressor, which allows the system to adjust its output based on the demands of the home. This means that the unit operates more quietly and reduces energy usage by matching the cooling or heating output required. Additionally, the two-stage heating capability provides more consistent temperatures and improved comfort throughout the space.

Operating noise is a crucial factor in residential HVAC systems, and the Bryant 340MAV is designed with this in mind. Engineered for quiet operation, the unit features a sound-dampening design, including an insulated cabinet and a specially designed compressor that minimizes noise levels. Homeowners can enjoy a comfortable indoor climate without the disruptive racket often associated with traditional systems.

Furthermore, the Bryant 340MAV is equipped with a durable all-aluminum coil, which improves heat transfer efficiency while also being resistant to corrosion. This characteristic contributes to the longevity of the unit, ensuring that it can withstand various environmental factors without compromising performance.

Another key feature is the advanced control options that the Bryant 340MAV offers. Integration with smart thermostats allows homeowners to monitor and adjust their HVAC system remotely, ensuring optimal comfort at all times. Additionally, the system is compatible with Bryant's Perfect Airâ„¢ filtration system, enhancing indoor air quality by reducing pollutants and allergens.

In summary, the Bryant 340MAV is a high-efficiency heating and cooling solution that brings together cutting-edge technology, quiet operation, and user-friendly features. With its focus on comfort and energy savings, it stands out as a prime choice for homeowners looking to invest in a reliable HVAC system.