Bryant 340MAV VI. Bottom Closure Panel, VII. GAS Piping, Maximum Capacity of Pipe, Casings only

Page 18

1712-IN. WIDE

CASINGS ONLY:

INSTALL FIELD-SUPPLIED FILTER FILLER STRIP UNDER FILTER.

3

24 1/2

1

21-IN. WIDE CASINGS ONLY: SUPPORT RODS (3) EXTEND 1/4" ON EACH SIDE OF FILTER AND REST ON CASING FLANGE

BOTTOM

CLOSURE

PANEL

FRONT FILLER

PANEL

WASHABLE FILTER

A93047

Fig. 25—Removing Bottom Closure Panel

CAUTION: Connect gas pipe to furnace using a backup wrench to avoid damaging gas controls. Failure to follow this caution will result in intermittent unit operation or performance satisfaction.

WARNING: Gas valve shutoff switch MUST be facing forward or tilted upward. Failure to follow this warning could result in property damage or death.

FILTER

FILTER RETAINER

SUPPORT

Fig. 24—Bottom Filter Arrangement

VI. BOTTOM CLOSURE PANEL

A00290

WARNING: Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A failure to follow this warning could result in fire, explo- sion, personal injury, or death.

WARNING: Use proper length of pipe to avoid stress on gas control manifold. Failure to follow this warning could result in a gas leak resulting in fire, explosion, personal

These furnaces are shipped with bottom enclosure panel installed in bottom return-air opening. This panel MUST be in place when side return air is used.

To remove bottom closure panel, perform following:

1.Tilt or raise furnace and remove 2 screws holding front filler panel. (See Fig. 25.)

2.Rotate front filler panel downward to release holding tabs.

3.Remove bottom closure panel.

4.Reinstall front filler panel and screws.

VII. GAS PIPING

Gas piping must be installed in accordance with national and local codes. Refer to current edition of NFGC in the United States. Canadian installations must be made in accordance with NSCNG- PIC and all authorities having jurisdiction. Gas supply line should be a separate line running directly from meter to furnace, if possible. Refer to Table 3 for recommended gas pipe sizing. Risers must be used to connect to furnace and to meter. Support all gas piping with appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft. Joint compound (pipe dope) should be applied sparingly and only to male threads of joints. Pipe dope must be resistant to propane gas.

injury, or death.

TABLE 3—MAXIMUM CAPACITY OF PIPE*

NOMINAL

 

 

LENGTH OF PIPE (FT)

 

IRON

INTERNAL

 

 

 

 

 

 

 

 

PIPE

DIAMETER

 

 

 

 

 

 

 

 

 

 

 

 

SIZE

(IN.)

10

 

20

30

40

50

(IN.)

 

 

 

 

 

 

 

 

 

1/2

0.622

175

 

120

97

82

73

3/4

0.824

360

 

250

200

170

151

1

1.049

680

 

465

375

320

285

1-1/4

1.380

1400

 

950

770

660

580

1-1/2

1.610

2100

 

1460

1180

990

900

*Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. wc) or less, and a pressure drop of 0.5-in. wc (based on a 0.60 specific gravity gas). Ref: Table 12.2 NFPA 54-2002.

Install a sediment trap in riser leading to furnace. Trap can be installed by connecting a tee to riser leading to furnace so straight-through section of tee is vertical. Then connect a capped nipple into lower end of tee. Capped nipple should extend below level of gas controls. Place a ground joint union between gas control manifold and manual gas shutoff valve. (See Fig. 26.)

—18—

Image 18
Contents Electrostatic Discharge ESD Precautions Safety ConsiderationsMultipoise Orientations Dimensions Unit SizeVI. GAS Piping and GAS Pipe Pressure Testing SafetyII. General Installation Codes and StandardsElectrostatic Discharge ESD Precautions VII. Electrical ConnectionsGeneral IntroductionApplications II. Upflow ApplicationsCondensate Trap Location Alternate Upflow Orientation Pressure Switch TubingCondensate Trap Tubing Factory-Shipped Orientation Condensate Trap Tubing Alternate Upflow OrientationIII. Downflow Applications Condensate Trap LocationCondensate Trap Tubing Horizontal Left Tube Configuration IV. Horizontal Left SUPPLY-AIR Discharge Applications Construct a Working PlatformHorizontal Right SUPPLY-AIR Discharge Applications Attic Location and Working Platform Location Furnace Location for Proper Condensate Drainage II. Furnace Location Relative to Cooling EquipmentIII. Installation in Horizontal Applications II. Installation in Upflow or Downflow ApplicationsInstallation Leveling Legs if Desired III. Hazardous Locations Opening Dimensions Furnace Plenum Opening Floor Opening Casing Width Duct Flanges II. Ductwork Acoustical TreatmentFilter Arrangement III. Supply AIR ConnectionsIV. Return AIR Connections Filter InformationMaximum Capacity of Pipe VI. Bottom Closure PanelVII. GAS Piping Casings onlyFire or Explosion Hazard Electrical ConnectionsWiring III AccessoriesPCB Removal of Existing Furnaces from Common Vent Systems Electrical DataDirect Venting II. COMBUSTION-AIR and Vent PipingControl Center COMBUSTION-AIR and Vent Pipe Termination Clearances Clearance FTCombustion-Air and Vent Pipe Diameter ExampleCombustion-Air and Vent Pipe Attachment COMBUSTION-AIR Intake Housing Plug Fitting Short Vent 5 to 8 Ft SystemMaximum Allowable Pipe Length FT Altitude FT6001 to 7000‡ Air Intake Housing Plug Fitting Drain Vent Extension Pipe Extended Exposed Sidewall PipesTwo-Pipe Termination Kit Concentric Vent/Air Termination Kit IV. Multiventing and Vent TerminationsRoof Termination Preferred Sidewall Termination of 12 in. or Less Condensate Drain General II. ApplicationIII. Condensate Drain Protection III. Continuous Blower Mode Heating ModeII. Cooling Mode IV. Heat Pump ModeComponent Test START-UP Procedures GeneralIV. Adjustments II. Prime Condensate Trap with WaterInducer Housing Drain Cap BTU/CU FT Orifice Manifold 625 650 Only 7001 675 725 8000 775 750 15% 825 2001to 725 750 Only 4001 775 800 825 5000 875 850 900 925 United States Example 100,000 Btuh Input Furnace Installed AT 4300 FTAltitude Derate Multiplier CanadaGAS Rate CU FT/HR Blower OFF Delay Setup PositionCheck Safety Controls Speed SelectorII. Check Pressure Switch ChecklistCheck Primary Limit Control Load Calculation CHECKLIST-INSTALLATIONCHECKLIST-START-UP Combustion AIR Vent Piping
Related manuals
Manual 12 pages 2.16 Kb Manual 44 pages 12.97 Kb