Bryant 340MAV III. Downflow Applications, Condensate Trap Location, Condensate Trap Tubing

Page 8

COLLECTOR BOX

DRAIN TUBE (BLUE)

CAP

PLUG

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

EXTENSION TUBE

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED)

COLLECTOR BOX

EXTENSION TUBE

CONDENSATE

TRAP

INDUCER HOUSING

DRAIN TUBE (VIOLET)

A00262

Fig. 8—Downflow Tube Configuration

(Left-Hand Trap Installation)

H. Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommenda- tions and procedures.

III. DOWNFLOW APPLICATIONS

A downflow furnace application is where furnace blower is located above combustion and controls section of furnace, and conditioned air is discharged downwards.

A. Condensate Trap Location

The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2, 8, or 9.

To relocate condensate trap from the blower shelf to desired location, perform the following:

1.Remove 3 tubes connected to condensate trap.

2.Remove trap from blower shelf by gently pushing tabs inward and rotating trap.

3.Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed.

WARNING: Casing hole filler cap must be installed in blower shelf when condensate trap is relocated. Failure to follow this warning could result in electrical shock, fire, personal injury or death.

4.Install condensate trap into left-hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.

5.Fill unused condensate trap casing holes with plastic filler caps (factory-supplied in loose parts bag).

B.Condensate Trap Tubing

NOTE: See Fig. 8 or 9 or tube routing label on main furnace door to check for proper connections.

—8—

PLUG

CAP

COLLECTOR BOX

DRAIN TUBE (BLUE)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

EXTENSION TUBE

COLLECTOR BOX

DRAIN TUBE (BLUE

& WHITE STRIPED)

COLLECTOR BOX EXTENSION TUBE

INDUCER HOUSING

DRAIN TUBE (VIOLET)

CONDENSATE

TRAP

COLLECTOR BOX

EXTENSION

DRAIN TUBE

DRAIN TUBE

COUPLING

A00296

Fig. 9—Downflow Tube Configuration

(Right-Hand Trap Installation)

1.Collector Box Drain Tube

a.Remove factory-installed plug from LOWER collector box drain tube (blue and white striped label).

b.Install removed clamp and plug into UPPER collector box drain tube (blue label) which was connected to condensate trap.

c.Connect LOWER collector box drain connection to condensate trap.

(1.) Condensate Trap Located on Left Side of Casing

(a.) Connect LOWER collector box drain tube (blue and white striped label) to condensate trap. Tube does not need to be cut.

(b.) Clamp tube to prevent any condensate leakage.

(2.) Condensate Trap Located on Right Side of Casing

(a.) Install drain tube coupling (factory-supplied in loose parts bag) into collector box drain tube (blue and white striped label) which was pre- viously plugged.

(b.) Connect larger diameter drain tube (factory- supplied in loose parts bag) to drain tube coupling, extending collector box drain tube for connection to condensate trap.

(c.) Route extended collector box drain tube di- rectly from collector box drain to condensate trap as shown in Fig. 9.

(d.) Determine appropriate length and cut.

(e.) Connect to condensate trap.

(f.) Clamp tube to prevent any condensate leakage.

2. Inducer Housing Drain Tube

Image 8
Contents Electrostatic Discharge ESD Precautions Safety ConsiderationsMultipoise Orientations Dimensions Unit SizeSafety II. General InstallationVI. GAS Piping and GAS Pipe Pressure Testing Codes and StandardsElectrostatic Discharge ESD Precautions VII. Electrical ConnectionsIntroduction ApplicationsGeneral II. Upflow ApplicationsPressure Switch Tubing Condensate Trap Tubing Factory-Shipped OrientationCondensate Trap Location Alternate Upflow Orientation Condensate Trap Tubing Alternate Upflow OrientationCondensate Trap Tubing III. Downflow ApplicationsCondensate Trap Location Horizontal Left Tube Configuration Horizontal Right SUPPLY-AIR Discharge Applications IV. Horizontal Left SUPPLY-AIR Discharge ApplicationsConstruct a Working Platform Attic Location and Working Platform Location Furnace Location for Proper Condensate Drainage II. Furnace Location Relative to Cooling EquipmentII. Installation in Upflow or Downflow Applications Installation Leveling Legs if DesiredIII. Installation in Horizontal Applications III. Hazardous LocationsWidth Opening DimensionsFurnace Plenum Opening Floor Opening Casing Duct Flanges II. Ductwork Acoustical TreatmentIII. Supply AIR Connections IV. Return AIR ConnectionsFilter Arrangement Filter InformationVI. Bottom Closure Panel VII. GAS PipingMaximum Capacity of Pipe Casings onlyFire or Explosion Hazard Electrical ConnectionsWiring III AccessoriesPCB Electrical Data Direct VentingRemoval of Existing Furnaces from Common Vent Systems II. COMBUSTION-AIR and Vent PipingControl Center COMBUSTION-AIR and Vent Pipe Termination Clearances Clearance FTCombustion-Air and Vent Pipe Attachment Combustion-Air and Vent Pipe DiameterExample COMBUSTION-AIR Intake Housing Plug Fitting Short Vent 5 to 8 Ft SystemMaximum Allowable Pipe Length FT Altitude FT6001 to 7000‡ Air Intake Housing Plug Fitting Drain Two-Pipe Termination Kit Vent Extension PipeExtended Exposed Sidewall Pipes Concentric Vent/Air Termination Kit IV. Multiventing and Vent TerminationsRoof Termination Preferred Sidewall Termination of 12 in. or Less III. Condensate Drain Protection Condensate Drain GeneralII. Application Heating Mode II. Cooling ModeIII. Continuous Blower Mode IV. Heat Pump ModeSTART-UP Procedures General IV. AdjustmentsComponent Test II. Prime Condensate Trap with WaterInducer Housing Drain Cap BTU/CU FT Orifice Manifold 625 650 Only 7001 675 725 8000 775 750 15% 825 2001to 725 750 Only 4001 775 800 825 5000 875 850 900 925 Example 100,000 Btuh Input Furnace Installed AT 4300 FT Altitude Derate MultiplierUnited States CanadaBlower OFF Delay Setup Position Check Safety ControlsGAS Rate CU FT/HR Speed SelectorCheck Primary Limit Control II. Check Pressure SwitchChecklist CHECKLIST-INSTALLATION CHECKLIST-START-UPLoad Calculation Combustion AIR Vent Piping
Related manuals
Manual 12 pages 2.16 Kb Manual 44 pages 12.97 Kb

340MAV specifications

The Bryant 340MAV is a standout model in the Bryant lineup, designed to provide exceptional comfort, efficiency, and performance for residential heating and cooling needs. This unit offers a perfect blend of innovative technology and user-friendly features, making it an ideal choice for homeowners seeking reliability and quality.

One of the defining characteristics of the Bryant 340MAV is its impressive efficiency rating. With a SEER (Seasonal Energy Efficiency Ratio) of up to 18, this model ensures that homeowners can enjoy effective cooling during the summer months while minimizing energy consumption. Similarly, the heating efficiency is notable, with a high AFUE (Annual Fuel Utilization Efficiency) rating. This makes the 340MAV an environmentally friendly option that also promotes cost savings on energy bills.

The 340MAV incorporates advanced technologies that enhance its performance. One such technology is the variable-speed compressor, which allows the system to adjust its output based on the demands of the home. This means that the unit operates more quietly and reduces energy usage by matching the cooling or heating output required. Additionally, the two-stage heating capability provides more consistent temperatures and improved comfort throughout the space.

Operating noise is a crucial factor in residential HVAC systems, and the Bryant 340MAV is designed with this in mind. Engineered for quiet operation, the unit features a sound-dampening design, including an insulated cabinet and a specially designed compressor that minimizes noise levels. Homeowners can enjoy a comfortable indoor climate without the disruptive racket often associated with traditional systems.

Furthermore, the Bryant 340MAV is equipped with a durable all-aluminum coil, which improves heat transfer efficiency while also being resistant to corrosion. This characteristic contributes to the longevity of the unit, ensuring that it can withstand various environmental factors without compromising performance.

Another key feature is the advanced control options that the Bryant 340MAV offers. Integration with smart thermostats allows homeowners to monitor and adjust their HVAC system remotely, ensuring optimal comfort at all times. Additionally, the system is compatible with Bryant's Perfect Airâ„¢ filtration system, enhancing indoor air quality by reducing pollutants and allergens.

In summary, the Bryant 340MAV is a high-efficiency heating and cooling solution that brings together cutting-edge technology, quiet operation, and user-friendly features. With its focus on comfort and energy savings, it stands out as a prime choice for homeowners looking to invest in a reliable HVAC system.