Bryant 340MAV Concentric Vent/Air Termination Kit, IV. Multiventing and Vent Terminations

Page 31

TABLE 8—MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT) WITH AND WITHOUT INSULATION IN WINTER

DESIGN TEMPERATURE AMBIENT*

FURNACE

WINTER DESIGN

MAX PIPE

WITHOUT

WITH 3/8–IN. OR

TEMPERATURE

DIAMETER

SIZE

INSULATION

THICKER INSULATION†

(°F)

(IN.)

 

 

 

 

20

1.5

51

70

 

0

1.5

28

70

040

-20

1.5

16

70

20

2

45

70

 

 

0

2

22

70

 

-20

2

10

58

 

20

2

65

70

060

0

2

35

70

 

-20

2

20

70

 

20

2

55

55

 

0

2

48

55

080

-20

2

30

55

20

2.5

70

70

 

 

0

2.5

47

70

 

-20

2.5

28

70

 

20

2.5

40

40

 

 

 

 

 

 

0

2.5

40

40

 

 

 

 

 

100

-20

2.5

38

40

 

 

 

 

20

3

70

70

 

 

 

 

 

 

 

0

3

50

70

 

 

 

 

 

 

-20

3

28

70

 

 

 

 

 

 

20

3

70

70

 

 

 

 

 

 

0

3

61

70

 

 

 

 

 

120

-20

3

37

70

 

 

 

 

20

4

70

70

 

 

 

 

 

 

 

0

4

48

70

 

 

 

 

 

 

-20

4

23

70

 

 

 

 

 

 

20

3

60

60

 

0

3

60

60

140

-20

3

44

60

20

4

70

70

 

 

0

4

57

70

 

-20

4

30

70

 

 

 

 

 

*Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length as specified in Table 7.

† Insulation thickness based on R value of 3.5 per in.

5.Check required dimensions as shown in Fig. 36, 39, or 40.

C.Concentric Vent/Air Termination Kit

1.Determine location for termination.

Consideration of the following should be made when determining an appropriate location for termination kit.

a.Comply with all clearance requirements as stated in Table 5.

b.Termination kit should be positioned where vent vapors will not damage plants/shrubs or air conditioning equip- ment.

c.Termination kit should be positioned so it will not be affected by wind eddy (such as inside building corners) or that may allow recirculation of flue gases, airborne leaves, or light snow.

d.Termination kit should be positioned where it will not be damaged by or subjected to foreign objects, such as stones, balls, etc.

e.Termination kit should be positioned where vent vapors are not objectionable.

2.Cut one 4-in. diameter hole for 2-in. kit, or one 5-in. diameter hole for 3-in. kit.

—31—

3.Loosely assemble concentric vent/air termination compo- nents together using instructions in kit.

4.Slide assembled kit with rain shield REMOVED through hole.

NOTE: Do not allow insulation or other materials to accumulate inside of pipe assembly when installing it through hole.

Roof terminations—Locate assembly through roof to ap- propriate height as shown in Fig. 37.

Sidewall terminations—Locate assembly through sidewall with rain shield positioned no more than 1-in. from wall as shown in Fig. 38.

5.Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.

6.Check required dimensions as shown in Fig. 37 or 38.

IV. MULTIVENTING AND VENT TERMINATIONS

When 2 or more 340MAV Furnaces are vented near each other, each furnace must be individually vented. NEVER common vent or breach vent 340MAV furnaces. When 2 or more 340MAV furnaces are vented near each other, 2 vent terminations may be installed as shown in Fig. 41, 42, 43, 44, and 45, but next vent termination must be at least 36 in. away from first 2 terminations.

Image 31
Contents Safety Considerations Electrostatic Discharge ESD PrecautionsMultipoise Orientations Unit Size DimensionsCodes and Standards SafetyII. General Installation VI. GAS Piping and GAS Pipe Pressure TestingVII. Electrical Connections Electrostatic Discharge ESD PrecautionsII. Upflow Applications IntroductionApplications GeneralCondensate Trap Tubing Alternate Upflow Orientation Pressure Switch TubingCondensate Trap Tubing Factory-Shipped Orientation Condensate Trap Location Alternate Upflow OrientationCondensate Trap Location III. Downflow ApplicationsCondensate Trap Tubing Horizontal Left Tube Configuration Construct a Working Platform IV. Horizontal Left SUPPLY-AIR Discharge ApplicationsHorizontal Right SUPPLY-AIR Discharge Applications Attic Location and Working Platform Location II. Furnace Location Relative to Cooling Equipment Furnace Location for Proper Condensate DrainageIII. Hazardous Locations II. Installation in Upflow or Downflow ApplicationsInstallation Leveling Legs if Desired III. Installation in Horizontal ApplicationsFurnace Plenum Opening Floor Opening Casing Opening DimensionsWidth II. Ductwork Acoustical Treatment Duct FlangesFilter Information III. Supply AIR ConnectionsIV. Return AIR Connections Filter ArrangementCasings only VI. Bottom Closure PanelVII. GAS Piping Maximum Capacity of PipeElectrical Connections Fire or Explosion HazardIII Accessories WiringPCB II. COMBUSTION-AIR and Vent Piping Electrical DataDirect Venting Removal of Existing Furnaces from Common Vent SystemsControl Center Clearance FT COMBUSTION-AIR and Vent Pipe Termination ClearancesExample Combustion-Air and Vent Pipe DiameterCombustion-Air and Vent Pipe Attachment Short Vent 5 to 8 Ft System COMBUSTION-AIR Intake Housing Plug FittingAltitude FT Maximum Allowable Pipe Length FT6001 to 7000‡ Air Intake Housing Plug Fitting Drain Extended Exposed Sidewall Pipes Vent Extension PipeTwo-Pipe Termination Kit IV. Multiventing and Vent Terminations Concentric Vent/Air Termination KitRoof Termination Preferred Sidewall Termination of 12 in. or Less II. Application Condensate Drain GeneralIII. Condensate Drain Protection IV. Heat Pump Mode Heating ModeII. Cooling Mode III. Continuous Blower ModeII. Prime Condensate Trap with Water START-UP Procedures GeneralIV. Adjustments Component TestInducer Housing Drain Cap BTU/CU FT Orifice Manifold 625 650 Only 7001 675 725 8000 775 750 15% 825 2001to 725 750 Only 4001 775 800 825 5000 875 850 900 925 Canada Example 100,000 Btuh Input Furnace Installed AT 4300 FTAltitude Derate Multiplier United StatesSpeed Selector Blower OFF Delay Setup PositionCheck Safety Controls GAS Rate CU FT/HRChecklist II. Check Pressure SwitchCheck Primary Limit Control Combustion AIR Vent Piping CHECKLIST-INSTALLATIONCHECKLIST-START-UP Load Calculation
Related manuals
Manual 12 pages 2.16 Kb Manual 44 pages 12.97 Kb

340MAV specifications

The Bryant 340MAV is a standout model in the Bryant lineup, designed to provide exceptional comfort, efficiency, and performance for residential heating and cooling needs. This unit offers a perfect blend of innovative technology and user-friendly features, making it an ideal choice for homeowners seeking reliability and quality.

One of the defining characteristics of the Bryant 340MAV is its impressive efficiency rating. With a SEER (Seasonal Energy Efficiency Ratio) of up to 18, this model ensures that homeowners can enjoy effective cooling during the summer months while minimizing energy consumption. Similarly, the heating efficiency is notable, with a high AFUE (Annual Fuel Utilization Efficiency) rating. This makes the 340MAV an environmentally friendly option that also promotes cost savings on energy bills.

The 340MAV incorporates advanced technologies that enhance its performance. One such technology is the variable-speed compressor, which allows the system to adjust its output based on the demands of the home. This means that the unit operates more quietly and reduces energy usage by matching the cooling or heating output required. Additionally, the two-stage heating capability provides more consistent temperatures and improved comfort throughout the space.

Operating noise is a crucial factor in residential HVAC systems, and the Bryant 340MAV is designed with this in mind. Engineered for quiet operation, the unit features a sound-dampening design, including an insulated cabinet and a specially designed compressor that minimizes noise levels. Homeowners can enjoy a comfortable indoor climate without the disruptive racket often associated with traditional systems.

Furthermore, the Bryant 340MAV is equipped with a durable all-aluminum coil, which improves heat transfer efficiency while also being resistant to corrosion. This characteristic contributes to the longevity of the unit, ensuring that it can withstand various environmental factors without compromising performance.

Another key feature is the advanced control options that the Bryant 340MAV offers. Integration with smart thermostats allows homeowners to monitor and adjust their HVAC system remotely, ensuring optimal comfort at all times. Additionally, the system is compatible with Bryant's Perfect Airâ„¢ filtration system, enhancing indoor air quality by reducing pollutants and allergens.

In summary, the Bryant 340MAV is a high-efficiency heating and cooling solution that brings together cutting-edge technology, quiet operation, and user-friendly features. With its focus on comfort and energy savings, it stands out as a prime choice for homeowners looking to invest in a reliable HVAC system.