Bryant 340MAV Electrical Data, Direct Venting, II. COMBUSTION-AIR and Vent Piping, General

Page 22

TABLE 4—ELECTRICAL DATA

UNIT

VOLTS—

OPERATING

MAX

UNIT

MIN

MAX WIRE

MAX FUSE

HERTZ—

VOLTAGE RANGE

UNIT

WIRE

LENGTH

OR CKT BKR

SIZE

AMPACITY†

PHASE

Max*

Min*

AMPS

GAGE

(FT)‡

AMPS**

 

 

 

 

 

 

 

 

 

 

 

024040

115—60—1

127

104

6.1

8.4

14

44

15

036040

115—60—1

127

104

7.3

10.0

14

37

15

024060

115—60—1

127

104

6.1

8.4

14

44

15

036060

115—60—1

127

104

7.1

9.8

14

38

15

048060

115—60—1

127

104

9.5

12.8

14

29

15

036080

115—60—1

127

104

7.6

10.4

14

36

15

048080

115—60—1

127

104

10.0

13.4

14

28

15

060080

115—60—1

127

104

14.1

18.4

12

31

20

048100

115—60—1

127

104

10.2

13.5

14

27

15

060100

115—60—1

127

104

14.8

19.3

12

30

20

060120

115—60—1

127

104

14.6

19.1

12

30

20

060140

115—60—1

127

104

14.3

18.8

12

30

20

 

 

 

 

 

 

 

 

 

* Permissible limits of voltage range at which unit will operate satisfactorily.

Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humi difier, etc.) full load amps.

Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. ** Time-delay type is recommended.

NOTE: DO NOT connect furnace control HUM terminal to HUM (humidifier) terminal on Thermidistat™, Zone Controller or simi- lar device. See Thermidistat™, Zone Controller, thermostat, or controller manufacturer’s instructions for proper connection.

2. Humidifier (HUM)

A quick-connect terminal (HUM) and screw terminal (COM 24-v) are provided for 24-v humidifier connection. (See Fig. 30.) HUM terminal is energized with 24v (0.5-amp maxi- mum) when gas valve is energized.

NOTE: A field-supplied, 115-v controlled relay connected to EAC terminals may be added if humidifier operation is desired during blower operation.

DIRECT VENTING

The 340MAV Furnaces require a dedicated (one 340MAV furnace only) direct-vent system. In a direct-vent system, all air for combustion is taken directly from outdoor atmosphere, and all flue gases are discharged to outdoor atmosphere.

I.REMOVAL OF EXISTING FURNACES FROM COMMON VENT SYSTEMS

When an existing Category I furnace is removed or replaced, the original venting system may no longer be sized to properly vent the remaining attached appliances. An improperly sized Category I venting system could cause the formation of condensate in the furnace and vent, leakage of condensate and combustion products, spillage of combustion products into the living space, etc.

WARNING: CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.

The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:

1.Seal any unused openings in venting system.

2.Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1-2002/NFPA54-2002 or the CSA B149.1, Natural Gas and Propane Installation Code and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies, which could cause an unsafe condition.

3.As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.

4.Close fireplace dampers.

5.Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.

6.Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.

7.Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.

8.If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1-2002/NFPA54-2002 and/or CSA B149.1, Natural Gas and Propane Installation Code.

9.After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-fired appliance to their previous conditions of use.

Vent system or vent connectors may need to be resized. For any other appliances when resizing vent systems or vent connectors, system or connector must be sized to approach minimum size as determined using appropriate table found in the NFGC or NSC-

NGPIC.

II. COMBUSTION-AIR AND VENT PIPING

A.General

Combustion-air and vent pipe, fittings, primers, and solvents must conform to American National Standards Institute (ANSI) stan- dards and American Society for Testing and Materials (ASTM) standards. See Table 6 for approved materials for use in the U.S.A.

—22—

Image 22
Contents Electrostatic Discharge ESD Precautions Safety ConsiderationsMultipoise Orientations Dimensions Unit SizeVI. GAS Piping and GAS Pipe Pressure Testing SafetyII. General Installation Codes and StandardsElectrostatic Discharge ESD Precautions VII. Electrical ConnectionsGeneral IntroductionApplications II. Upflow ApplicationsCondensate Trap Location Alternate Upflow Orientation Pressure Switch TubingCondensate Trap Tubing Factory-Shipped Orientation Condensate Trap Tubing Alternate Upflow OrientationCondensate Trap Location III. Downflow ApplicationsCondensate Trap Tubing Horizontal Left Tube Configuration Construct a Working Platform IV. Horizontal Left SUPPLY-AIR Discharge ApplicationsHorizontal Right SUPPLY-AIR Discharge Applications Attic Location and Working Platform Location Furnace Location for Proper Condensate Drainage II. Furnace Location Relative to Cooling EquipmentIII. Installation in Horizontal Applications II. Installation in Upflow or Downflow ApplicationsInstallation Leveling Legs if Desired III. Hazardous LocationsFurnace Plenum Opening Floor Opening Casing Opening DimensionsWidth Duct Flanges II. Ductwork Acoustical TreatmentFilter Arrangement III. Supply AIR ConnectionsIV. Return AIR Connections Filter InformationMaximum Capacity of Pipe VI. Bottom Closure PanelVII. GAS Piping Casings onlyFire or Explosion Hazard Electrical ConnectionsWiring III AccessoriesPCB Removal of Existing Furnaces from Common Vent Systems Electrical DataDirect Venting II. COMBUSTION-AIR and Vent PipingControl Center COMBUSTION-AIR and Vent Pipe Termination Clearances Clearance FTExample Combustion-Air and Vent Pipe DiameterCombustion-Air and Vent Pipe Attachment COMBUSTION-AIR Intake Housing Plug Fitting Short Vent 5 to 8 Ft SystemMaximum Allowable Pipe Length FT Altitude FT6001 to 7000‡ Air Intake Housing Plug Fitting Drain Extended Exposed Sidewall Pipes Vent Extension PipeTwo-Pipe Termination Kit Concentric Vent/Air Termination Kit IV. Multiventing and Vent TerminationsRoof Termination Preferred Sidewall Termination of 12 in. or Less II. Application Condensate Drain GeneralIII. Condensate Drain Protection III. Continuous Blower Mode Heating ModeII. Cooling Mode IV. Heat Pump ModeComponent Test START-UP Procedures GeneralIV. Adjustments II. Prime Condensate Trap with WaterInducer Housing Drain Cap BTU/CU FT Orifice Manifold 625 650 Only 7001 675 725 8000 775 750 15% 825 2001to 725 750 Only 4001 775 800 825 5000 875 850 900 925 United States Example 100,000 Btuh Input Furnace Installed AT 4300 FTAltitude Derate Multiplier CanadaGAS Rate CU FT/HR Blower OFF Delay Setup PositionCheck Safety Controls Speed SelectorChecklist II. Check Pressure SwitchCheck Primary Limit Control Load Calculation CHECKLIST-INSTALLATIONCHECKLIST-START-UP Combustion AIR Vent Piping
Related manuals
Manual 12 pages 2.16 Kb Manual 44 pages 12.97 Kb

340MAV specifications

The Bryant 340MAV is a standout model in the Bryant lineup, designed to provide exceptional comfort, efficiency, and performance for residential heating and cooling needs. This unit offers a perfect blend of innovative technology and user-friendly features, making it an ideal choice for homeowners seeking reliability and quality.

One of the defining characteristics of the Bryant 340MAV is its impressive efficiency rating. With a SEER (Seasonal Energy Efficiency Ratio) of up to 18, this model ensures that homeowners can enjoy effective cooling during the summer months while minimizing energy consumption. Similarly, the heating efficiency is notable, with a high AFUE (Annual Fuel Utilization Efficiency) rating. This makes the 340MAV an environmentally friendly option that also promotes cost savings on energy bills.

The 340MAV incorporates advanced technologies that enhance its performance. One such technology is the variable-speed compressor, which allows the system to adjust its output based on the demands of the home. This means that the unit operates more quietly and reduces energy usage by matching the cooling or heating output required. Additionally, the two-stage heating capability provides more consistent temperatures and improved comfort throughout the space.

Operating noise is a crucial factor in residential HVAC systems, and the Bryant 340MAV is designed with this in mind. Engineered for quiet operation, the unit features a sound-dampening design, including an insulated cabinet and a specially designed compressor that minimizes noise levels. Homeowners can enjoy a comfortable indoor climate without the disruptive racket often associated with traditional systems.

Furthermore, the Bryant 340MAV is equipped with a durable all-aluminum coil, which improves heat transfer efficiency while also being resistant to corrosion. This characteristic contributes to the longevity of the unit, ensuring that it can withstand various environmental factors without compromising performance.

Another key feature is the advanced control options that the Bryant 340MAV offers. Integration with smart thermostats allows homeowners to monitor and adjust their HVAC system remotely, ensuring optimal comfort at all times. Additionally, the system is compatible with Bryant's Perfect Airâ„¢ filtration system, enhancing indoor air quality by reducing pollutants and allergens.

In summary, the Bryant 340MAV is a high-efficiency heating and cooling solution that brings together cutting-edge technology, quiet operation, and user-friendly features. With its focus on comfort and energy savings, it stands out as a prime choice for homeowners looking to invest in a reliable HVAC system.