When a furnace is installed so that the supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used. Seal supply- and
Flexible connections should be used between ductwork and furnace to prevent transmission of vibration. Ductwork passing through unconditioned space should be insulated to enhance system performance. When air conditioning is used, a vapor barrier is recommended.
Maintain a
Fig. 21—Duct Flanges
A93029
For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel. This opening shall be accessible when the furnace is installed and shall be of such a size that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air
Air Conditioning Contractors National Association (SMACNA) or American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) or consult The Air Systems Design Guide- lines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design static pressure.
stream. The cover attachment shall prevent leaks.
II. DUCTWORK ACOUSTICAL TREATMENT
Metal duct systems that do not have a 90 degree elbow and 10 ft of main duct to the first branch
ANGLE
IRON OR
EQUIVALENT
| (B) |
|
| (A) |
|
(B) |
|
|
(A) ROD LOCATION |
|
|
USING DIMPLE |
|
|
LOCATORS | (A) | |
(SEE DIMENSIONAL | ||
DWG FOR | & WASHER (4) |
|
LOCATIONS) | REQD PER ROD |
|
53⁄4″
ALTERNATE SUPPORT LOCATION
DRAIN
(A)
(B)
(B)ALTERNATE SUPPORT LOCATION FROM BACK
(A)PREFERRED ROD LOCATION
(B)ALTERNATE ROD LOCATION
NOTES: 1. A 1 In. clearance minimum between top of furnace and combustible material.
2.The entire length of furnace must be supported when furnace is used in horizontal position to ensure proper drainage.
A93304