WIRING
FACTORY WIRING
All units are fully factory wired. Multispeed blowers are factory wired on high speed for cooling/manual fan operation. Heating speeds are wired for the largest input and may need lower speed for field installed low input nozzle. If replacement wire is necessary, use 105 degrees C minimum. See electrical data, Table 3.
FIELD WIRING
All wiring must conform to the National Electrical Code and all local codes. A separate fuse or breaker should be used for the furnace.
TABLE 3
ELECTRICAL DATA
|
|
|
|
|
|
|
| Max. Time | |
|
|
| Blower Motor | Burner Motor | Minimum | Delay Fuse | |||
|
|
|
|
|
|
| |||
|
| Total | HP | FLA | HP | FLA | Circuit | or HACR | |
Model | Amps | Ampacity | Circuit Breaker | ||||||
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| |
FH085D36F | 7.3 | 1/3 | 5.6 | 1/7 | 1.7 | 9 | 15 | ||
|
|
|
|
|
|
|
|
| |
FH110D48F | 12.2 | 1/2 | 10.5 | 1/7 | 1.7 | 15 | 20 | ||
|
|
|
|
|
|
|
|
| |
FH110D60F | 14.2 | 3/4 | 12.5 | 1/7 | 1.7 | 18 | 20 | ||
|
|
|
|
|
|
|
|
| |
FLF085D36F | 7.3 | 1/3 | 5.6 | 1/7 | 1.7 | 9 | 15 | ||
|
|
|
|
|
|
|
|
| |
FLR085D36F | 7.3 | 1/3 | 5.6 | 1/7 | 1.7 | 9 | 15 | ||
|
|
|
|
|
|
|
|
| |
FLF110D48F | 12.2 | 1/2 | 10.5 | 1/7 | 1.7 | 15 | 20 | ||
|
|
|
|
|
|
|
|
| |
FLR110D48F | 12.2 | 1/2 | 10.5 | 1/7 | 1.7 | 15 | 20 | ||
|
|
|
|
|
|
|
|
| |
FLF110D60F | 14.2 | 3/4 | 12.5 | 1/7 | 1.7 | 18 | 20 | ||
|
|
|
|
|
|
|
|
| |
FLR110D60F | 14.2 | 3/4 | 12.5 | 1/7 | 1.7 | 18 | 20 | ||
|
|
|
|
|
|
|
|
| |
FLR140D60F | 14.2 | 3/4 | 12.5 | 1/7 | 1.7 | 18 | 20 | ||
|
|
|
|
|
|
|
|
| |
FC085D36F | 7.3 | 1/3 | 5.6 | 1/7 | 1.7 | 9 | 15 | ||
|
|
|
|
|
|
|
|
|