BECKETT GENISYS
MODEL 7505
PRIMARY OPERATIONAL GUIDE
BECKETT GENISYS 7505
Sequence of Operation
BURNER STATES
1.Standby: The burner is idle, waiting for a call for heat.
2.
3.Trial for Ignition: The fuel valve is opened. A flame should be established within the factory set trial for ignition time (“lockout time”).
4.Lockout: The control has shut the burner down for one of the following safety reasons:
•The trial for ignition (lockout) time expires without flame being established.
•The cad cell detects flame during
•The Recycle mode
If the control locks out three times without completing a successful call for heat, the control enters Restricted (Hard) Lockout, and must be reset by a technician. Hold the reset button for 15 seconds until the red light shuts off to reset from Restricted Lockout.
5.Ignition Carryover: Once flame is established, the igniter remains on for 10 additional seconds to ensure flame stability.
6.Run: The flame is sustained until the call for heat is satisfied. The burner is then sent to
7.Recycle: If the flame is lost while the burner is firing, the control shuts down the burner, enters a
8.
9.Pump Prime: The igniter and motor are on with the oil valve open for up to 4 minutes. During Pump Prime mode, the cad cell is disregarded, allowing the technician to prime the pump without having to jumper the cad cell.
RESET BUTTON OPERATION
•Table A explains what action the control will take when the reset button is pressed for different lengths of time during the various burner operating states.
Manual | |