TABLE A
RESET BUTTON OPERATION
If the burner is in the |
| Pushing the Reset button will: | ||
|
|
| ||
Button Click | Button Hold | Button Hold | ||
below state: | ||||
| (press < 1 second) | (press > 1 second) | (press 15+ seconds) | |
Lockout | Reset from Soft Lockout |
| Reset from Restricted (Hard) Lockout | |
|
|
|
| |
Go to Pump Prime |
|
| ||
Trial for Ignition, | Disable the Burner: |
| ||
(see Below) | Enables Pump Priming: | |||
Ignition Carryover | ||||
| Any time the burner is running, | |||
|
| After the reset button has been held for | ||
| Yellow LED flashes to | press and hold the reset button | ||
| 15 seconds, the button can then be | |||
| indicate cad cell resistance. | to disable the burner. | tapped during the next ignition sequence | |
| The burner will remain off as | |||
Run (igniter is shut off) | See "Cad Cell Resistance | to enter Pump Prime mode. | ||
long as the button is held. | ||||
| Indicator" for table of |
| ||
|
|
| ||
| resistance values. |
|
| |
|
|
|
| |
No action |
|
| ||
|
|
|
| |
Pump Prime | No action | Exit Pump Prime mode and return to Standby | ||
|
|
|
|
TABLE B
STATUS LIGHTS
LED | On Continuously | Flashing | |
Color | |||
|
| ||
|
|
| |
Red | Restricted (hard) Lockout | Soft Lockout | |
Green | Flame Detected (Could be flame or stray light) | Recycle | |
Yellow | Control is in Pump Prime mode or | Cad Cell resistance. See "Cad Cell Resistance Indicator" | |
Reset button currently held for 15+ seconds | section for table of resistance values. | ||
| |||
|
|
|