Bard FLF085D36F, FLR140D60F, FLR110D48F Table a Reset Button Operation, Table B Status Lights

Page 15

TABLE A

RESET BUTTON OPERATION

If the burner is in the

 

Pushing the Reset button will:

 

 

 

Button Click

Button Hold

Button Hold

below state:

 

(press < 1 second)

(press > 1 second)

(press 15+ seconds)

Lockout

Reset from Soft Lockout

 

Reset from Restricted (Hard) Lockout

 

 

 

 

Valve-on Delay,

Go to Pump Prime

 

 

Trial for Ignition,

Disable the Burner:

 

(see Below)

Enables Pump Priming:

Ignition Carryover

 

Any time the burner is running,

 

 

After the reset button has been held for

 

Yellow LED flashes to

press and hold the reset button

 

15 seconds, the button can then be

 

indicate cad cell resistance.

to disable the burner.

tapped during the next ignition sequence

 

The burner will remain off as

Run (igniter is shut off)

See "Cad Cell Resistance

to enter Pump Prime mode.

long as the button is held.

 

Indicator" for table of

 

 

 

 

 

resistance values.

 

 

 

 

 

 

Motor-Off Delay, Standby

No action

 

 

 

 

 

 

Pump Prime

No action

Exit Pump Prime mode and return to Standby

 

 

 

 

TABLE B

STATUS LIGHTS

LED

On Continuously

Flashing

Color

 

 

 

 

 

Red

Restricted (hard) Lockout

Soft Lockout

Green

Flame Detected (Could be flame or stray light)

Recycle

Yellow

Control is in Pump Prime mode or

Cad Cell resistance. See "Cad Cell Resistance Indicator"

Reset button currently held for 15+ seconds

section for table of resistance values.

 

 

 

 

Manual

2100-422M

Page

15 of 42

Image 15
Contents OIL Furnace Installation Instructions Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsEquipment Selection Locating the FurnaceMinimum Clearances FLF/FLR 085, 110 and 140 Specification Sheet Supply Specification Sheet FC085 Model Dimensions Counterflow Specification SheetInstallation Installing the FurnaceInstalling a Cooling Unit Instruments Required for Proper Setup of the FurnaceElectrical Data WiringFactory Wiring Field WiringTypical Unit Setup FLF Unit Shown Typical Unit Setup FLF Unit ShownI m n e y Typical Single Inside Tank Installation OIL Line PipingBeckett AFG or NX OIL Burner Beckett Cleancut OIL Pump Beckett Solid State IgniterGenisys 7505 Primary Control Reset Button Operation Beckett GenisysBurner States Table B Status Lights Table a Reset Button OperationPriming the Pump CAD Cell Resistance IndicatorDisable Function Resetting from Restricted LockoutElectronic Blower Control Cleaner ConnectionFurnace Data Burner Setup and Adjustment ProceduresCombustion Adjustment Steps Preparation StepsCombustion Diagnosis Short Form Adjustment Procedure Typical Smoke CO2 Chart with Adjustment Range High Air Settings Low Bacharach Smoke NumberPressure Gauge Connection to Bleed Port No Fuel OIL Efficiency Chart NET Stack TEMP. Degrees F Recommended START-UP SettingsCorrelation of Percent of CO2, O2 and Reserve AIR Spacing of Electrodes GUN Assembly AdjustmentRemoving GUN Assembly Combustion AIR RequirementsCombustion AIR Boot Assembly AFG Burner Combustion AIR Boot AssemblyALL AIR from Inside Building Appliances Located in Confined SpacesMinimum Ventilation Openings ALL Ventilation AIR from OutdoorsAppliances Located in Confined Spaces ALL AIR from Outdoors Manual 2100-422M Vertical Venting Louvers and GrillesVenting Options ThermostatAFG AIR Filters Typical Installation of FR25 Filter KITLO-BOY Models Filter Locations Filter Installation LO-BOY ModelsFinal Inspection and Test Service HintsLubrication Inspect AIR FilterRemoval of Burner only Combination Combustion CHAMBER/BURNER Mounting SystemTo Remove Burner only To Remove the Entire Combustion Chamber Mounting SystemRemoval of Entire Combustion Chamber Mounting System Cleaning of the Heat Exchanger Common Causes of TroubleCare of Finish Chart FLF/FLR085D36F Data Chart FH085D36F DataChart FH110D48F Data Chart FH110D60F DataChart FC085D36F Data Chart FLR140D60F DataExchanger FH Series Wiring Diagram4047-119 E 4047-120 D