Heat & Glo LifeStyle XLR-PLUS-N-AU, XLR-PLUS-PB-AU manual MIN. Clearance in. mm

Page 23

 

 

 

 

 

 

a

 

 

j

 

T

 

 

 

 

 

h

 

c

 

 

 

 

 

 

 

 

j

j

e

e

d

 

 

openable

 

h

 

 

 

 

window

 

P

 

 

 

 

 

h

 

 

 

n

door

 

g

 

 

 

 

 

f

 

k

 

T

 

M

 

 

 

 

 

 

 

 

 

 

I

 

 

 

d

 

c

 

 

 

 

 

 

 

 

b

 

 

 

 

g

 

 

 

 

k

 

 

 

 

 

 

 

 

 

 

See note 2

See note 3

T

T = Flue terminal

M = Gas meter

Shading indicates prohibited

I = Mechanical air inlet

P = Electricity meter or fuse box

areas for flue terminals

a

- Below eaves, balconies or other projections:

MIN. CLEARANCE - in. (mm)

 

Appliances up to 50 MJ/h input

12

(300)

 

Appliances over 50 MJ/h input

20-1/2

(500)

b

- From the ground or above a balcony

12

(300)

c

- From a return wall or external corner

20-1/2

(500)

d

- From a gas meter (M)

39

(1000)

e

- From an electricity meter or fuse box (P)

20-1/2

(500)

f

- From a drain or soil pipe

6

(150)

g- Horizontally from any building structure (unless appliance approved

for closer installation) or obstruction facing a terminal

20-1/2

(500)

h - From any other flue terminal, cowl, or combustion air intake

20-1/2

(500)

j- Horizontally from an openable window, door, non-mechanical air

 

inlet, or any other opening into a building, with the exception of

 

 

 

sub-floor ventilation:

 

 

 

 

 

Appliances up to 150 MJ/h input

 

20-1/2

(500)

 

Appliances over 150 MJ/h input

 

60

(1500)

k

- From a mechanical air inlet, including a spa blower

60

(1500)

n

- Vertically below an openable window, non-mechanical air

 

 

 

inlet or any other opening into a building, with the exception of

See table

 

sub-floor ventilation

 

 

 

below

 

 

 

 

 

 

 

 

CLEARANCE

 

 

 

 

 

 

 

 

 

Space Heaters

 

All other appliances

 

 

 

 

 

 

 

 

 

Up to 50 MJ/h input

Up to 50 MJ/h input

Over 50 MJ/h input and

Over 50 MJ/h input

 

Up to 150 MJ/h input

 

 

 

 

 

 

6 in. (150 mm)

20 in. (500 mm)

39 in. (1000 mm)

59 in. (1500 mm)

NOTES: 1. All distances are measured vertically or horizontally along the wall to a point in line with the nearest part of the terminal.

2.Prohibited area below electricity meter or fuse box extends to ground level.

3.See clause 5.13.6.6 for restrictions on a flue terminal under a roofed area.

4.See Appendix J, Figure J1(a) and J2(a) for clearances required from a flue

terminal to a LP Gas cylinder. A flue terminal is considered to be a source of ignition.

MINIMUM CLEARANCES REQUIRED FOR BALANCED FLUE TERMINALS

OR THE FLUE TERMINALS OF OUTDOOR APPLIANCES

Figure 6.3 Minimum Clearances for Termination

Heat & Glo • XLR-PLUS-N-AU, XLR-PLUS-PB-AU2264-900 Rev. M • 7/12

23

Image 23
Contents What to do if you smell gas Ref No GSCS20194 AS45532008SAI Global Models XLR-PLUS-N-AU XLR-PLUS-PB-AU Homeowner Reference Information CongratulationsUser Guide Table of ContentsFinishing Appliance SetupTroubleshooting Component AccessLimited Lifetime Warranty Australian Warranty InformationOther Rights Perth This warranty is void ifListing and Code Approvals Your Fireplace Gas Fireplace SafetyOperating Instructions User Guide Clear Space Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches IPI Battery Tray/Battery InstallationAGE 110/120 VAC or 220/240 Lighting Instructions IPIFinal inspection by Control Module Operation Nine Hour Safety Shutdown FeatureAfter Fireplace is Lit Frequently Asked QuestionsInitial Break-in Procedure Maintenance and Service Control Compartment and Firebox Top Maintenance Tasks-Qualified Service TechnicianGasket Seal and Glass Assembly Inspection FireboxTypical Appliance System Getting StartedInspect Appliance and Components Design and Installation ConsiderationsTools and Supplies Needed Selecting Appliance Location Framing and ClearancesClearances Constructing the Appliance ChaseFront Side Finishing Detail Mantel and Wall ProjectionsMantels Combustible/Non-Combustible Mantel Leg Combustible/Non-CombustibleVent Termination Minimum Clearances Termination LocationsMIN. Clearance in. mm Vent Information and Diagrams Minimum H1 Maximum Top Vent Horizontal Termination Venting with 1 elbowMinimum H1 + H2 Maximum Top Vent Horizontal Termination Venting with 2 elbowsExhaust Restrictor Instructions Top Vent Vertical Termination No Elbows V1 Max= 13.4 m 44 ftV1 Minimum Maximum V1 + V2 Minimum Top Vent Vertical Termination Venting with 2 elbowsV1 Minimum H1 + H2 Maximum V1 + V2 Minimum Top Vent Vertical Termination Venting with 3 elbowsTop Vent Vertical Termination Venting with 4 elbows Combustible Wall Penetration Vent Clearances and FramingPipe Clearances to Combustibles Wall Penetration FramingPipe SLP Install the Ceiling FirestopVaulted Ceiling Installation Install Attic Insulation ShieldFlat Ceiling Installation Top Vent Appliance PreparationSecuring and Leveling the Appliance Installing the Optional Heat-Zone-240V KitAssemble Vent Sections Installing Vent Pipe SLP PipeSecure The Vent Sections Assemble Slip SectionsDisassemble Vent Sections Install Decorative Ceiling ComponentsAssemble and Install Storm Collar Install Metal Roof FlashingHeat Shield Requirements for Horizontal Termination Install Vertical Termination CapInstall Decorative Wall Components 17 Venting through the Wall Install Horizontal Termination CapPropane Butane Gas InformationGas Connection Natural GasValve Pressure Taps Access Through the Valve AssemblyOptional Remote Control Receiver Location Wiring RequirementsIntelliFire Plus Ignition System Wiring Optional Accessories RequirementsJunction Cord Information Electrical Service and Repair BlowerIntroduction Kit ContentsFireplace Specific Information Determine Location Installation PrecautionsChanging Temperature Scale Installation of Remote Control HousingProgramming the RC300AU to the Control Module AUX300CE Module InstallationFan Installation Function Buttons Idle When Remote is in on ModeStandby mode Display ScreenAdjusting Fan Speed About on ModeAbout OFF Mode Adjusting Flame HeightPower Outage Adjusting ThermostatAdjusting Timer Setting the Child LockSymptom Possible Cause Corrective Action Frequently Asked Questions/TroubleshootingFinishing Instructions Non-Combustible Materials SpecificationFinishing Framing and Finishing InstructionsFinishing Details Painting Finish and Sealing JointsFinishing Around Opening with Gypsum Wallboard Gas Pipe RequirementsTOP View Unlimited Overlap Fit Method Tonic or Martini Decorative Front Facing MaterialInside and Overlap Method See .C Decorative FrontsSee Figures 13.15 Dimensions of Tonic Decorative FrontAppliance Setup Verify Performance of Appliance Air Shutter SettingMedia Options IntelliFire Plus Ignition System TroubleshootingSymptom Possible Cause Corrective Action Ues to spark, and main Frequently Asked Questions/Troubleshooting Component Access Access Through the Valve Assembly Pilot Assembly Replacement Gas Valve ReplacementReference Materials Appliance Dimension DiagramInspect Maintenance Tasks Maintenance TasksDVP-HPC Cap Brick Extension Vent Components DiagramsSupport SLP-45 45 ElbowSLP90- 90 Elbow Ceiling FirestopSupport Box-Black SnorkelSLP-HRC-SS SLP-HRC-ZC-SS Horizontal Termination CAP XLR-PLUS-N-AU, XLR-PLUS-PB-AU Service Parts#15 Valve Assembly XLR-PLUS-N-AU, XLR-PLUS-PB-AU Service Parts ListContact Information

XLR-PLUS-N-AU, XLR-PLUS-PB-AU specifications

The Heat & Glo LifeStyle XLR-PLUS-PB-AU and XLR-PLUS-N-AU are modern gas fireplaces designed to provide both comfort and aesthetic appeal to your home. These models exemplify innovative design, advanced technology, and user-friendly features that make them ideal for any living space.

One of the standout features of the XLR-PLUS series is its elegant linear design, which offers a contemporary aesthetic suitable for various interior styles. The fireplaces are available in multiple sizes, ensuring they can fit into a wide range of spaces, whether in a cozy den or a spacious open-concept living area. The sleek appearance is complemented by a variety of front options, allowing homeowners to customize their fireplace to match personal tastes and home décor.

The heating technology in the XLR-PLUS fireplaces is another key highlight. Equipped with advanced gas burner systems, these units deliver efficient heating performance, making them an excellent choice for year-round use. The adjustable flame height feature not only enhances ambiance but also allows users to customize the heat output based on their needs. This flexibility contributes to energy savings, as users can efficiently manage their heating preferences.

Notably, the XLR-PLUS models incorporate the IntelliFire® Ignition System, a state-of-the-art technology that ensures reliable lighting and easy operation. This system simplifies the ignition process, allowing users to start their fireplace with the push of a button. Furthermore, the fireplaces come with a remote control that provides added convenience, enabling users to adjust settings from the comfort of their seat.

Safety is a top priority with the Heat & Glo LifeStyle series. These fireplaces feature a built-in safety shut-off mechanism that automatically turns off the unit if it detects any issues, offering peace of mind for users. Additionally, the glass front is designed to remain cool to the touch, reducing the risk of burns, making them a family-friendly option.

In terms of installation, both the XLR-PLUS-PB-AU and XLR-PLUS-N-AU models are designed with versatility in mind. They can be installed in various configurations, including built-in, wall-mounted, or as part of a custom cabinetry project. This adaptability allows homeowners to seamlessly integrate the fireplace into their space.

In summary, the Heat & Glo LifeStyle XLR-PLUS-PB-AU and XLR-PLUS-N-AU fireplaces combine cutting-edge technology, customizable design, and reliable performance. With features that prioritize both safety and user experience, these models are perfect for those looking to enhance their living spaces with warmth and style.