Note: The lower cover panel must be pushed all the way down. The outer finishing flanges should line up. The fireplace opening must be between 15-3/4 in. (400 mm) and 16-1/8 in. (410 mm) for the decorative fronts to fit correctly. See Figure 13.4.

Finish and Sealing Joints

All joints between the finished wall sheating and the appliance must be sealed with non-combustible materials. Sealants, such as caulk or mastic used to seal the gap between the wall and the fireplace, should be rated at a minimum continuous exposure to 149 °C (300 °F). Wall board joints can be taped and sealed with combustible drywall tape.

Finishing Around Opening with Gypsum Wallboard

Gypsum wallboard (drywall) joints adjacent to the fireplace opening require special attention to minimize potential development of cracking. Hearth and Home Technologies recommends the following steps to minimize potential cracks in the finished drywall around the fireplace opening:

When installing gypsum wallboard around the fireplace, install the hole for the fireplace opening in a single wallboard sheet, if possible. This will minimize the joints adjacent to the fireplace opening.

The factory-supplied non-combustible board and the gypsum wallboard must join on the structural framing, where applicable. Wallboard and non-combustible board should be fastened to the framing with at least 1-1/4 in. (32 mm) long screw fasteners, located within 1-1/2 in. (38 mm) from each corner, and at no more than 12 in. (305 mm) intervals along the joint length.

The wall-board joints should be finished with a Taping Coat, followed by at least two subsequent Finish Coats of joint compound.

For the initial Taping Coat, it is critical that a general- purpose chemically hardening joint compound, such as SHEETROCK™ Brand Durabond™ Setting-Type Joint Compound, be used to fill the joint and embed the mesh tape. Fiberglass-mesh tape is recommended because it will provide a more crack-resistant joint than one finished with paper tape. Let the Taping Coat properly cure before applying subsequent Finish Coats.

For the second and third finishing coats, it is acceptable to use a light-weight joint compound and standard application, curing and sanding methods.

Do not operate the fireplace during the drywall finishing process. Allow the finish coat to cure for at least 24 hours prior to using the appliance.

Retain 12 mm clearance between plasterboard and vertical sides of unit. Butt join plasterboard and white insulation board at top of heater. USING ONLY FIBERGLASS TAPE finish insulation board to plasterboard as per normal plasterbaord procedures. Ensure that top coat finish extends down to top of heater, as indicated in diagram below. Insulation board will remain exposed as part of the finished plaster face.

V-JOINT TO PLATERBOARD & WHITE INSULATION BOARD, BUTT JOIN EACH AND BACK FILL WITH CORNICE CEMENT. OVERLAY JOIN WITH FIBERGLASS TAPE AND TROWEL TOP COAT OVER.

FIBERGLASS TAPE

ONLY ON JOINT

SIDE

 

WHITE INSULATION BOARD

 

ELEVATION

 

 

 

ENTIRE INSULATION

 

 

 

 

 

 

 

 

 

 

BOARD TO BE

 

 

 

TOP COATED

 

 

 

 

 

 

 

 

12 mm CLEARANCE TO COMBUSTIBLES

Plasterboard to be adhered to lower panel using silicone (no screws to be used).

Figure 13.5 White Insulation Board

Gas Pipe Requirements

1.If polyethylene composite gas pipe is to be used, a clearance of 150 mm must be maintained from all flues.

2.Polyethylene composite gas pipe must not be used as the final connection onto the heater.

3.Leave a 1 m. tail of 1/2 in. (13 mm) copper pipe.

Painting

If desired finishing includes a painted wall, 100% acrylic latex with compatible primer is recommend around the appliance. Oil-based or standard acrylic paints may discolor due to heat exposure.

Wallboard Joint-Crack Prevention and Repair

Wallboard joints around the fireplace will be affected by exposure to elevated temperatures, along with other en- vironmental and structural factors. The specific methods presented in the previous section will help prevent or minimize development of cracks.

If a crack does emerge adjacent the fireplace, it can be permanently repaired by filling it with spackling paste or paintable latex caulk, followed by repainting.

Heat & Glo • XLR-PLUS-N-AU, XLR-PLUS-PB-AU2264-900 Rev. M • 7/12

55

Image 55
Contents SAI Global Ref No GSCS20194 AS45532008What to do if you smell gas Models XLR-PLUS-N-AU XLR-PLUS-PB-AU Homeowner Reference Information CongratulationsUser Guide Table of ContentsFinishing Appliance SetupTroubleshooting Component AccessLimited Lifetime Warranty Australian Warranty InformationOther Rights Perth This warranty is void ifListing and Code Approvals Operating Instructions User Guide Gas Fireplace SafetyYour Fireplace Clear Space Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches IPI Battery Tray/Battery InstallationFinal inspection by Lighting Instructions IPIAGE 110/120 VAC or 220/240 Control Module Operation Nine Hour Safety Shutdown FeatureInitial Break-in Procedure Frequently Asked QuestionsAfter Fireplace is Lit Maintenance and Service Control Compartment and Firebox Top Maintenance Tasks-Qualified Service TechnicianGasket Seal and Glass Assembly Inspection FireboxTypical Appliance System Getting StartedTools and Supplies Needed Design and Installation ConsiderationsInspect Appliance and Components Selecting Appliance Location Framing and ClearancesClearances Constructing the Appliance ChaseFront Side Finishing Detail Mantel and Wall ProjectionsMantels Combustible/Non-Combustible Mantel Leg Combustible/Non-CombustibleVent Termination Minimum Clearances Termination LocationsMIN. Clearance in. mm Vent Information and Diagrams Minimum H1 Maximum Top Vent Horizontal Termination Venting with 1 elbowMinimum H1 + H2 Maximum Top Vent Horizontal Termination Venting with 2 elbowsExhaust Restrictor Instructions Top Vent Vertical Termination No Elbows V1 Max= 13.4 m 44 ftV1 Minimum Maximum V1 + V2 Minimum Top Vent Vertical Termination Venting with 2 elbowsV1 Minimum H1 + H2 Maximum V1 + V2 Minimum Top Vent Vertical Termination Venting with 3 elbowsTop Vent Vertical Termination Venting with 4 elbows Combustible Wall Penetration Vent Clearances and FramingPipe Clearances to Combustibles Wall Penetration FramingPipe SLP Install the Ceiling FirestopFlat Ceiling Installation Install Attic Insulation ShieldVaulted Ceiling Installation Top Vent Appliance PreparationSecuring and Leveling the Appliance Installing the Optional Heat-Zone-240V KitAssemble Vent Sections Installing Vent Pipe SLP PipeSecure The Vent Sections Assemble Slip SectionsDisassemble Vent Sections Install Decorative Ceiling ComponentsAssemble and Install Storm Collar Install Metal Roof FlashingInstall Decorative Wall Components Install Vertical Termination CapHeat Shield Requirements for Horizontal Termination 17 Venting through the Wall Install Horizontal Termination CapPropane Butane Gas InformationGas Connection Natural GasValve Pressure Taps Access Through the Valve AssemblyOptional Remote Control Receiver Location Wiring RequirementsIntelliFire Plus Ignition System Wiring Optional Accessories RequirementsJunction Cord Information Electrical Service and Repair BlowerFireplace Specific Information Kit ContentsIntroduction Determine Location Installation PrecautionsChanging Temperature Scale Installation of Remote Control HousingFan Installation AUX300CE Module InstallationProgramming the RC300AU to the Control Module Function Buttons Idle When Remote is in on ModeStandby mode Display ScreenAdjusting Fan Speed About on ModeAbout OFF Mode Adjusting Flame HeightPower Outage Adjusting ThermostatAdjusting Timer Setting the Child LockSymptom Possible Cause Corrective Action Frequently Asked Questions/TroubleshootingFinishing Instructions Non-Combustible Materials SpecificationFinishing Framing and Finishing InstructionsFinishing Details Painting Finish and Sealing JointsFinishing Around Opening with Gypsum Wallboard Gas Pipe RequirementsTOP View Unlimited Overlap Fit Method Tonic or Martini Decorative Front Facing MaterialInside and Overlap Method See .C Decorative FrontsSee Figures 13.15 Dimensions of Tonic Decorative FrontAppliance Setup Media Options Air Shutter SettingVerify Performance of Appliance Symptom Possible Cause Corrective Action TroubleshootingIntelliFire Plus Ignition System Ues to spark, and main Frequently Asked Questions/Troubleshooting Component Access Access Through the Valve Assembly Pilot Assembly Replacement Gas Valve ReplacementReference Materials Appliance Dimension DiagramInspect Maintenance Tasks Maintenance TasksDVP-HPC Cap Brick Extension Vent Components DiagramsSupport SLP-45 45 ElbowSLP90- 90 Elbow Ceiling FirestopSupport Box-Black SnorkelSLP-HRC-SS SLP-HRC-ZC-SS Horizontal Termination CAP XLR-PLUS-N-AU, XLR-PLUS-PB-AU Service Parts#15 Valve Assembly XLR-PLUS-N-AU, XLR-PLUS-PB-AU Service Parts ListContact Information

XLR-PLUS-N-AU, XLR-PLUS-PB-AU specifications

The Heat & Glo LifeStyle XLR-PLUS-PB-AU and XLR-PLUS-N-AU are modern gas fireplaces designed to provide both comfort and aesthetic appeal to your home. These models exemplify innovative design, advanced technology, and user-friendly features that make them ideal for any living space.

One of the standout features of the XLR-PLUS series is its elegant linear design, which offers a contemporary aesthetic suitable for various interior styles. The fireplaces are available in multiple sizes, ensuring they can fit into a wide range of spaces, whether in a cozy den or a spacious open-concept living area. The sleek appearance is complemented by a variety of front options, allowing homeowners to customize their fireplace to match personal tastes and home décor.

The heating technology in the XLR-PLUS fireplaces is another key highlight. Equipped with advanced gas burner systems, these units deliver efficient heating performance, making them an excellent choice for year-round use. The adjustable flame height feature not only enhances ambiance but also allows users to customize the heat output based on their needs. This flexibility contributes to energy savings, as users can efficiently manage their heating preferences.

Notably, the XLR-PLUS models incorporate the IntelliFire® Ignition System, a state-of-the-art technology that ensures reliable lighting and easy operation. This system simplifies the ignition process, allowing users to start their fireplace with the push of a button. Furthermore, the fireplaces come with a remote control that provides added convenience, enabling users to adjust settings from the comfort of their seat.

Safety is a top priority with the Heat & Glo LifeStyle series. These fireplaces feature a built-in safety shut-off mechanism that automatically turns off the unit if it detects any issues, offering peace of mind for users. Additionally, the glass front is designed to remain cool to the touch, reducing the risk of burns, making them a family-friendly option.

In terms of installation, both the XLR-PLUS-PB-AU and XLR-PLUS-N-AU models are designed with versatility in mind. They can be installed in various configurations, including built-in, wall-mounted, or as part of a custom cabinetry project. This adaptability allows homeowners to seamlessly integrate the fireplace into their space.

In summary, the Heat & Glo LifeStyle XLR-PLUS-PB-AU and XLR-PLUS-N-AU fireplaces combine cutting-edge technology, customizable design, and reliable performance. With features that prioritize both safety and user experience, these models are perfect for those looking to enhance their living spaces with warmth and style.