Eaton Electrical Powerware 9315 Performing Preventive Maintenance, A V E R T I S S E M E N T

Models: Powerware 9315

1 84
Download 84 pages 23 Kb
Page 68
Image 68
A V E R T I S S E M E N T !

Maintaining the UPS System

W A R N I N G

￿Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal of batteries is required. Refer to your local codes for disposal requirements.

￿Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.

C A U T I O N

Do not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead-acid batteries and must be disposed of properly. For more information, contact your local recycling or hazardous waste center.

A V E R T I S S E M E N T !

Une batterie peut prêsenter un risque de choc êlectrique, de brulure, ou d’incendie. Suivre les précautions qui s’imposent.

￿Pour le remplacement, utiliser le même nombre et modéle des batteries.

￿L’élimination des batteries est règlementée. Consulter les codes locaux à cet effet.

8.2Performing Preventive Maintenance

The UPS requires very little preventive maintenance. However, the UPS should be inspected periodically to verify that it is operating normally and that the batteries are in good condition.

Perform the following checks DAILY:

￿Check the area surrounding the UPS. Ensure the area is not cluttered, allowing free access to the UPS.

￿Ensure the air intakes (vents on the front doors) and exhaust opening (on top of the UPS cabinet) are not blocked.

￿Ensure the operating environment is within the parameters specified in Chapter 9, “Product Specifications.”

￿Ensure the UPS is in Normal mode (Normal status indicator is lit). If an alarm lamp is lit or the Normal status indicator is not lit, contact your Eaton service representative.

Perform the following checks MONTHLY:

￿Ensure all status indicator lamps are operative. (Press the 8.2Performing Preventive Maintenance and Manual background buttons simultaneously to test the lamps.)

￿Monitor system parameters as described in Chapter 5, “Using the Monitor Panel.”

￿Check the air filters (located behind the front doors) and replace them as necessary (the filter size is 16″×20″×1″).

￿Record the results of your checks and any corrective actions in a suitable log.

8-2

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

Page 68
Image 68
Eaton Electrical Powerware 9315 Performing Preventive Maintenance, A V E R T I S S E M E N T, W A R N I N G, C A U T I O N