The UPS systems are housed in freestanding, double-front cabinets with safety shields behind the doors. The UPS systems are available in 50/60 Hz with various output power ratings. Smaller models within a system may be upgraded in the field to larger models:

Table 9-1. Model Numbers

System

Models

Notes

 

 

 

Powerware 9315 300

225 and 300 kVA

60 Hz only

 

 

 

Powerware 9315 250

200 and 250 kVA

50/60 Hz (400V models only)

 

 

 

Powerware 9315 225

225 kVA

60 Hz only

 

 

 

Powerware 9315 200

200 kVA

50/60 Hz (400V models only)

 

 

 

The following sections detail the input, output, environmental, and battery specifications for the UPS.

Table 9-2. System Input

Operating Input

480 Vac for operation from 408 Vac to 528 Vac (60 Hz only)

Voltage

400 Vac for operation from 340 Vac to 440 Vac (50/60 Hz only)

(Nominal +10/–15%)

600 Vac for operation from 510 Vac to 660 Vac (60 Hz only)

Operating Input

3 Hz of nominal (50 Hz or 60 Hz)

Frequency Range

 

Operating Input

Battery Charge

Current

125% of full load for overload + battery charge

 

Actual load + 25% of full load for battery charge with 0.8 pF

 

output units

 

115% of full load for overload + battery charge

 

Actual load + 15% of full load for battery charge with 0.9 pF

 

output units

 

Reduced for Generator

 

Adjustable, set to 102%

Input Current

10% THD at full load (with input filter option installed)

Harmonic Content

 

Power Walk-In

Adjustable 3–60 second rectifier ramp-up to full utility load

Power Factor

Minimum 0.95

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4

 

 

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com