Chapter 10

Responding to System Events

When the UPS system is running in Normal mode, it continually monitors itself and the incoming utility power. In Battery or Bypass modes, the UPS may issue alarms to let you know exactly what event caused the change from Normal mode. System events can be indicated by horns, lights on the UPS, or both.

Select Active from the Events menu on the LCD screen to look at the Active System Events screen. This screen shows any currently active alarms, notices, or commands.

10.1 System Event Horns

The system event horn beeps according to the type of event it is signifying:

￿When the UPS detects an alarm that requires your attention, the horn beeps at ½-second intervals.

￿When a notice occurs, the horn beeps at 2-second intervals.

10.2System Event Lights

The status indicators on the UPS Monitor Panel work in conjunction with the event horn to let you know when the UPS is operating in any mode other than Normal. Only the Normal indicator is visible during normal UPS operation. The others light to indicate alarms or events. When an alarm occurs, you should first check these indicators to see what type of event has taken place. (For descriptions of the status indicators, see “Reading the Status Indicators” on page 5-4.)

10.3 System Event Messages

When a system event occurs, a message is added to the Event History Log. A message may also appear on the Monitor Panel of the UPS. The Event History Log contains all system event messages, whether or not they were displayed on the Monitor Panel.

INVERTER MESSAGES - ALARMS

INVERTER MESSAGES - NOTICES

 

 

Inverter DC Over Voltage

Bypass AC Over Voltage

Clear Inverter DC Over Voltage

Clear Bypass AC Over Voltage

 

 

Inverter AC Over Voltage

Bypass AC Under Voltage

Clear Inverter AC Over Voltage

Clear Bypass AC Under Voltage

 

 

Inverter AC Under Voltage

Bypass Over Frequency

Clear Inverter AC Under Voltage

Clear Bypass Over Frequency

 

 

Inverter Over Frequency

Bypass Under Frequency

Clear Inverter Over Frequency

Clear Bypass Under Frequency

 

 

Inverter Under Frequency

Battery DC Under Voltage

Clear Inverter Under Frequency

Clear Battery DC Under Voltage

 

 

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

10-1

Page 75
Image 75
Eaton Electrical Powerware 9315 operation manual Responding to System Events, System Event Horns, System Event Lights