Eaton Electrical Powerware 9315 operation manual Using the LCD Screen

Models: Powerware 9315

1 84
Download 84 pages 23 Kb
Page 28
Image 28
5.1 Using the LCD Screen

Using the Monitor Panel

5.1 Using the LCD Screen

The LCD screen at the top of the Monitor Panel provides an operator interface with the UPS. Figure 5-2 identifies the display fields discussed in the following sections.

 

 

 

Uninterruptible Power System

 

 

 

 

 

A

System Normal

 

 

 

 

 

 

04 MAY 1997

14:23:45

F

Alarm:

None

 

 

 

 

 

 

 

 

 

 

 

 

Notice: None

 

 

 

 

 

 

 

 

 

 

 

B

Battery

 

Input

 

 

 

Output

 

G

 

 

 

 

 

 

 

Percent

 

 

 

 

 

 

 

 

 

 

 

 

100%

VAB

VBC

VCA

FREQ

VAB

VBC

VCA

FREQ

 

 

 

 

 

 

 

 

480

480

480

60.0

480

480

480

60.0

 

 

 

 

IA

IB

 

 

IC

IA

IB

IC

IN

 

 

 

 

480

480

 

480

361

361

361

000

 

 

 

 

KVA

KW

 

 

PF

 

KVA

KW

PF

 

 

C

 

 

399

379

0.95

 

300

240

0.80

 

Meters

 

 

 

 

 

 

 

 

 

 

 

D

System

 

Bypass

 

 

 

Battery

 

 

 

Load Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VAB

VBC

 

VCA

 

V

 

I

 

 

 

 

 

480

480

 

480

 

540

 

000

 

 

E

Meters

Events

Statistics Graphics

Setup

 

 

 

 

 

 

Figure 5-2. Parts of the LCD Screen (Typical for Powerware 9315 300 480/480V UPS)

AThe UPS status area contains three lines that display the current state of the UPS. The first line shows the present operational mode of the UPS. The second line shows the highest level of the current active alarms, and the third line shows any notices the UPS has posted. (For more information about alarms and notices, see Chapter 10, “Responding to System Events.”)

BThe battery charge box shows the percentage of battery capacity available.

CThe menu box shows the currently selected menu and lists the options available on that menu. The title at the top of the menu box is also shown below on the menu bar (E). Press the Manual background and Manual background buttons to scroll up and down through the options in the menu box.

DThe currently selected option is highlighted in the menu box. Press the Manual background and Manual background buttons to move the highlight up or down. The data in the information area (G) changes accordingly.

EThe menu bar lists the titles of the menus. The title of the menu currently displayed in the menu box is highlighted. When you press the Manual background and Manual background buttons to move the highlight left or right, the data in the menu box and the information area change accordingly.

FThe timestamp shows the current date and time. This date and time are recorded in the Event Log when a notice or alarm is activated.

GThe information area contains data about UPS status and operations. Select a menu option to display statistics or graphics.

5-2

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

Page 28
Image 28
Eaton Electrical Powerware 9315 operation manual Using the LCD Screen