Communication

7.6.2 Entire Log – [Ctrl]+[P]

This key sequence prints the entire Event History Log of the UPS at the time the data is requested. The printout begins with the oldest alarm entry in the queue and ends with the most recent. Any alarms that occur while the Event History Log is printing are included in chronological order.

The Event History Log lists up to 400 system events in chronological order with the most recent event listed last. Figure 7-6 shows a sample Event History Log printout.

 

Uninterruptible Power System

 

 

 

UPS System Normal

 

03

NOV 1997

14:23:45

Alarm:

None

 

 

 

 

 

 

Notice:

None

 

 

 

 

 

 

 

Event History Log

 

 

 

 

 

 

Event Description

 

 

 

 

MAY 12

16:41:19.3

COMMAND: Keyswitch

On

0421

 

 

12

16:41:29.1

STATUS:

Auto Mode

 

1000

 

2030

12

16:41:42.4

COMMAND:

Rectifier

Commanded On

12

16:42:05.5

STATUS:

Inverter On

 

 

2202

12

16:42:46.8

STATUS:

Rectifier

On

 

 

 

12

16:43:15.8

STATUS:

Inverter Contactor (3) Closed

12

16:43:42.4

STATUS:

Bypass Contactor (K4) Open

12

16:44:29.1

STATUS:

Inverter Normal

4001

 

32

JUN 04 12:16:35.9 NOTICE: Room High Temperature

Figure 7-6. Event History Log

7-10

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

Page 56
Image 56
Eaton Electrical Powerware 9315 operation manual Entire Log Ctrl+P, Event History Log