C. Gas Connection

2.Remove the base pan. It is attached with 10 screws to the interior firebox bottom and with 12 screws to the burner assembly. If your appliance is a model that has the glass rock media, you must also remove the pilot shield cover at this time. See Figure 11.2 and Figure 11.3.

3.Remove the two screws securing the burner to the firebox sides and disengage burner from over orifice. Remove burner. See Figure 11.3.

4.Remove access panel covers or glass windows, along with gaskets. Gaskets may be fragile. Handle with care. See Figure 11.2.

INNER ACCESS WINDOWS

(FOR USE AFTER FINISHING)

ACCESS PANEL

(For use prior to finishing)

OUTER ACCESS PANEL TRAY

(For use after finishing)

Figure 11.2 Gas and Electrical Access

PILOT SHIELD

(INSTALLED ON MODELS WITH LIGHT MEDIA OPTION)

INNER BASE PAN TRAY

BURNER ASSEMBLY

C. Gas Connection

Refer to Reference Section 16 for location of gas line access in appliance.

Gas line may be run through either side of appliance.

The gap between supply piping and gas access hole may be caulked with caulk with a minimum of 300ºF continuous exposure rating or stuffed with non- combustible, unfaced insulation to prevent cold air infiltration.

Ensure that gas line does not come in contact with outer wrap of the appliance. Follow local codes.

Pipe incoming gas line into valve compartment.

Connect incoming gas line to the 1/2 in. (13 mm) connection on manual shutoff valve.

WARNING! Risk of Fire or Explosion! Support control when attaching pipe to prevent bending gas line.

• A small amount of air will be in the gas supply lines.

WARNING! Risk of Fire or Explosion! Gas build-up dur- ing line purge could ignite.

Purge should be performed by qualified service technician.

Ensure adequate ventilation.

Ensure there are no ignition sources such as sparks or open flames.

Light the appliance. It will take a short time for air to purge from lines. When purging is complete the appliance will light and operate normally.

WARNING! Risk of Fire, Explosion or Asphyxiation! Check all fittings and connections with a non-corrosive commercially available leak-check solution. DO NOT use open flame. Fittings and connections could have loos- ened during shipping and handling.

WARNING! Risk of Fire! DO NOT change valve settings. This valve has been preset at the factory.

Figure 11.3. Base Pan with Burner and Pilot Cover

D. High Altitude Installations

GAS SHUT OFF VALVE

Figure 11.4 Gas Fitting Access

NOTICE: If the heating value of the gas has been reduced, these rules do not apply. Check with your local gas utility or authorities having jurisdiction.

When installing above 2000 feet elevation:

In the USA: Reduce burner orifice 4% for each 1000 feet above 2000 feet.

In CANADA: Reduce burner orifice 10% for elevations between 2000 feet and 4500 feet. Above 4500 feet, consult local gas utility.

Heat & Glo • RED40, RED40ST • 2155-900 Rev. o • 7/12

45

 

Image 45
Contents NOTICE Models RED40 RED40ST•What to do if you smell gas Owner’s ManualHomeowner Reference Information A. CongratulationsSafety Alert Key Table of ContentsInstaller Guide 3 Maintenance and Service15 Troubleshooting 14 Appliance Setup = Contains updated information 13 FinishingLIMITED LIFETIME WARRANTY B. Limited Lifetime WarrantyWARRANTY COVERAGE WARRANTY PERIODWARRANTY CONDITIONS B. Limited Lifetime Warranty continuedWARRANTY EXCLUSIONS This warranty is void if1 Listing and Code Approvals D. High Altitude InstallationsA. Appliance Certification B. Glass SpecificationsInstallation of Carbon Monoxide Detectors 2 Operating Instructions User Guide A. Gas Fireplace SafetyB. Your Fireplace C. Clear SpaceD. Decorative Doors and Fronts E. Fixed Glass AssemblyG. Before Lighting Fireplace erate fireplace with fixed glass assembly removedFinal inspection by H. Lighting Instructions IPIFOR YOUR SAFETY READ BEFORE LIGHTING LIGHTING INSTRUCTIONS IPII. After Fireplace is Lit J.Frequently Asked QuestionsInitial Break-inProcedure •Some people may be sensitive to smoke and odorsA. Maintenance Tasks-Homeowner 3 Maintenance and ServiceGlass Cleaning Remote ControlGasket Seal and Glass Assembly Inspection B.Maintenance Tasks-QualifiedService TechnicianVenting FireboxA. Typical Appliance System Getting StartedInstaller Guide Figure 4.1 Typical SystemB. Design and Installation Considerations C.Tools and Supplies NeededD. Inspect Appliance and Components A. Selecting Appliance Location 5 Framing and Clearances1/2 IN 1/2 IN. CFigure 5.2 Appliance Locations RED40ST C. Clearances B. Constructing the Appliance ChaseMINIMUM FRAMING DIMENSIONS Dimensions of Non-Combustibles D. Mantel and Wall ProjectionsCombustible Mantels Non-CombustibleMantelsA. Vent Termination Minimum Clearances 6 Termination LocationsRoof Pitch H Min. Ft= AREA WHERE TERMINAL IS NOT PERMITTED Covered Alcove ApplicationsV= VENT TERMINAL X = AIR SUPPLY INLET E. Vent Diagrams 7 Vent Information and DiagramsA. Approved Pipe B. Vent Table KeyVenting with 1 elbow Top Vent - Horizontal TerminationV1 Minimum H1 MaximumVenting with 2 elbows 1. Top Vent - Horizontal Termination - continuedINSTALLED HORIZONTALLY H1 + H2 MaximumVenting with 3 elbows 1. Top Vent - Horizontal Terminationcontinued H2 V2 H1 V1Top Vent - Vertical Termination No Elbows V = 3 ft Min. 1m, 50 ft. Max. 15.2 mExhaust restrictor Instructions V2 H1 V1 Top Vent - Vertical TerminationVenting with 3 elbows DIRECT VENT WITH 5 in. / 8 in. DIAMETER DVP PIPE A. Pipe Clearances to Combustibles 8 Vent Clearances and FramingB. Wall Penetration Framing Between ceiling firestopsC. Install the Ceiling Firestop D. Install Attic Insulation Shield Flat Ceiling InstallationVaulted Ceiling Installation A. Appliance Preparation 9 Appliance PreparationSetting the Fireplace into the Framing B. Securing and Leveling the ApplianceWARNING! Risk of Fire! Prevent contact with •Sagging or loose insulationC. Active Convection Technology A. Assemble Vent Sections 10 Installing Vent Pipe DVP PipeB. Assemble Slip Sections C. Secure The Vent SectionsPilot hole D. Disassemble Vent Sections E. Install Decorative Ceiling ComponentsG. Assemble and Install Storm Collar F. Install Metal Roof FlashingCAULK CAUTION! Risk of Cuts, Abrasions or Flying DebrisH. Install Vertical Termination Cap Figure 10.20 Venting Through the Wall J. Install Horizontal Termination Cap11 Gas Information A. Fuel ConversionB. Gas Pressure •Ensure adequate ventilation C. Gas ConnectionB. IntelliFire Ignition System Wiring A. Wiring RequirementsC. Optional Accessories Requirements 12 Electrical InformationREMOTE RECEIVER Optional Remote Control Receiver LocationD. Optional LED Lighting Circuit SWITCH TRIPPEDCOLOR PRODUCED F. Junction Box Installation E. Electrical Service and RepairG. Active Convection Blower Replacement KNOCKOUTFAN MOUNT FASTENER SIDE BURNER SCREWBLOWER TAB ON MOUNTING PLATE SLOT ON BLOWER HOUSINGFigure 12.17. Remove Mounting Plate Figure 12.18. Removed Mounting PlateA. Splatter Guard 13 FinishingB. Framing and Finishing Instructions Finishing InstructionsFinishing Around Opening with Gypsum Wallboard Finish and Sealing JointsPainting Figure 13.1 Finishing DetailsDimensions of Combustibles C. Mantel and Wall ProjectionsD. Facing Material Figure 13.5 Framing and Framing Materials-RED40Figure 13.6 Framing and Framing Materials-RED40ST Non-CombustibleFinish Materials 0 - 1 inch thickness-OverlapFit MethodFigure 13.7 Overlap Fit Method Figure 13.9 Inside Fit Method 0 Inches to 4 Inches Thick Inside Fit Method42-3/4IN 13-1/8INASSEMBLY E. Mesh FrontsMESH FRAME ASSEMBLY Figure 13.11. Mesh Front InstallationA. Remove Fixed Glass Assembly 14 Appliance SetupC. Clean the Appliance D. AccessoriesI. Install the Mesh H. Fixed Glass AssemblyJ. Air Shutter Setting Removing Fixed Glass AssemblyA. IntelliFire Ignition System 15 TroubleshootingSymptom Possible CauseIntelliFire Ignition System - continued 16 Reference Materials A. Appliance Dimension DiagramM N O P Figure 16.2 Appliance Dimensions RED40STT R Q S A F GB. Vent Components Diagrams Figure 16.2 DVP vent componentsDVP-AS2 DVP-TRAP1 B. Vent Components Diagrams continuedDVP-TRAP2 DVP-TRAPK131 in 13 in 8-1/8in206 mm 330 mmOptional Wire Harness DESCRIPTIONPART NUMBER RED40 C. Service Partsat Depot Stocked40 in Landscape See-ThruDV Fireplace RED40STService Parts List #13 Control Assembly#14 Valve Assembly RED40,RED40STRED40, RED40ST Service PartsStocked   15.3 #15 Base Pan No Lights with Media15.1 15.215.1 15.215.3 15.4Stocked at Depot #16 Base Pan With Lights and Media16.3 16.116.3 16.216.1 16.4Porcelain or No refractory #17 Base Pan No Lights or Media withRED40-NNNNo lights, No Rock, No Refractory RED40-NNPNo lights, No Rock, PorcelainRED40ST-NNNNo lights, No Rock, No Refractory Stocked at DepotRED40ST-NNPNo lights, No Rock, Porcelain RED40ST-NNGNo lights, No Rock, Granite#20 Porcelain --No Media #19 Granite --No Media#21 Granite --With Media #22 Porcelain --With MediaRED40ST NOTES D. Contact Information