Heat & Glo LifeStyle RED40ST Venting, B.Maintenance Tasks-QualifiedService Technician, Firebox

Page 14
Venting

Venting

Frequency: Seasonally

By: Homeowner

Tools needed: Protective gloves and safety glasses.

Inspect venting and termination cap for blockage or obstruction such plants, bird nests, leaves, snow, debris, etc.

Verify termination cap clearance to subsequent construc- tion (building additions, decks, fences, or sheds). See Section 6.

Inspect for corrosion or separation.

Verify weather stripping, sealing and flashing remains intact.

Inspect draft shield to verify it is not damaged or missing.

B.Maintenance Tasks-Qualified Service Technician

The following tasks must be performed by a qualified ser- vice technician.

Gasket Seal and Glass Assembly Inspection

Frequency: Annually

By: Qualified Service Technician

Tools needed: Protective gloves, drop cloth and a stable work surface.

Inspect gasket seal and its condition.

Inspect fixed glass assembly for scratches and nicks that can lead to breakage when exposed to heat.

Confirm there is no damage to glass or glass frame. Replace as necessary.

Verify that fixed glass assembly is properly retained and attachment components are intact and not damaged. Replace as necessary.

Firebox

Frequency: Annually

By: Qualified Service Technician

Tools needed: Protective gloves, sandpaper, steel wool, cloths, mineral spirits, primer and touch-up paint.

Inspect for paint condition, warped surfaces, corrosion or perforation. Sand and repaint as necessary.

Replace fireplace if firebox has been perforated.

Control Compartment and Firebox Top

Frequency: Annually

By: Qualified Service Technician

Tools needed: Protective gloves, vacuum cleaner, dust cloths

Vacuum and wipe out dust, cobwebs, debris or pet hair. Use caution when cleaning these areas. Screw tips that have penetrated the sheet metal are sharp and should be avoided.

Remove all foreign objects.

Verify unobstructed air circulation.

Burner Ignition and Operation

Frequency: Annually

By: Qualified Service Technician

Tools needed: Protective gloves, vacuum cleaner, whisk broom, flashlight, voltmeter, indexed drill bit set, and a manometer.

Verify burner is properly secured and aligned with pilot or igniter.

Clean off burner top, inspect for plugged ports, corrosion or deterioration. Replace burner if necessary.

Check for smooth lighting and ignition carryover to all ports. Verify that there is no ignition delay.

Inspect for lifting or other flame problems.

Verify air shutter setting is correct. See Section 14.J for required air shutter setting. Verify air shutter is clear of dust and debris.

Inspect orifice for soot, dirt and corrosion. Verify orifice size is correct. See Service Parts List for proper orifice sizing.

Verify manifold and inlet pressures. Adjust regulator as required.

Inspect pilot flame pattern and strength. See Figure 3.1 for proper pilot flame pattern. Clean or replace orifice spud as necessary.

Inspect IPI flame-sensing rod for soot, corrosion and deterioration. Polish with fine steel wool or replace as required.

Verify IPI millivolt output. Replace as necessary.

Verify that there is not a short in flame sense circuit by checking continuity between pilot hood and flame- sensing rod. Replace pilot as necessary.

Figure 3.1 IPI Pilot

14

Heat & Glo • RED40, RED40ST • 2155-900 Rev. o • 7/12

Image 14
Contents •What to do if you smell gas Models RED40 RED40STNOTICE Owner’s ManualA. Congratulations Homeowner Reference InformationInstaller Guide Table of ContentsSafety Alert Key 3 Maintenance and Service = Contains updated information 14 Appliance Setup15 Troubleshooting 13 FinishingWARRANTY COVERAGE B. Limited Lifetime WarrantyLIMITED LIFETIME WARRANTY WARRANTY PERIODWARRANTY EXCLUSIONS B. Limited Lifetime Warranty continuedWARRANTY CONDITIONS This warranty is void ifA. Appliance Certification D. High Altitude Installations1 Listing and Code Approvals B. Glass SpecificationsInstallation of Carbon Monoxide Detectors B. Your Fireplace A. Gas Fireplace Safety2 Operating Instructions User Guide C. Clear SpaceG. Before Lighting Fireplace E. Fixed Glass AssemblyD. Decorative Doors and Fronts erate fireplace with fixed glass assembly removedFOR YOUR SAFETY READ BEFORE LIGHTING H. Lighting Instructions IPIFinal inspection by LIGHTING INSTRUCTIONS IPIInitial Break-inProcedure J.Frequently Asked QuestionsI. After Fireplace is Lit •Some people may be sensitive to smoke and odorsGlass Cleaning 3 Maintenance and ServiceA. Maintenance Tasks-Homeowner Remote ControlVenting B.Maintenance Tasks-QualifiedService TechnicianGasket Seal and Glass Assembly Inspection FireboxInstaller Guide Getting StartedA. Typical Appliance System Figure 4.1 Typical SystemD. Inspect Appliance and Components B. Design and Installation ConsiderationsC.Tools and Supplies Needed 5 Framing and Clearances A. Selecting Appliance LocationFigure 5.2 Appliance Locations RED40ST 1/2 IN1/2 IN. C B. Constructing the Appliance Chase C. ClearancesMINIMUM FRAMING DIMENSIONS Combustible Mantels D. Mantel and Wall ProjectionsDimensions of Non-Combustibles Non-CombustibleMantelsRoof Pitch 6 Termination LocationsA. Vent Termination Minimum Clearances H Min. FtV= VENT TERMINAL X = AIR SUPPLY INLET = AREA WHERE TERMINAL IS NOT PERMITTEDCovered Alcove Applications A. Approved Pipe 7 Vent Information and DiagramsE. Vent Diagrams B. Vent Table KeyV1 Minimum Top Vent - Horizontal TerminationVenting with 1 elbow H1 MaximumINSTALLED HORIZONTALLY 1. Top Vent - Horizontal Termination - continuedVenting with 2 elbows H1 + H2 Maximumcontinued 1. Top Vent - Horizontal TerminationVenting with 3 elbows H2 V2 H1 V1Exhaust restrictor Instructions Top Vent - Vertical Termination No ElbowsV = 3 ft Min. 1m, 50 ft. Max. 15.2 m Top Vent - Vertical Termination V2 H1 V1V1 + V2 Minimum DIRECT VENT WITH 5 in. / 8 in. DIAMETER DVP PIPE B. Wall Penetration Framing 8 Vent Clearances and FramingA. Pipe Clearances to Combustibles Between ceiling firestopsC. Install the Ceiling Firestop Vaulted Ceiling Installation D. Install Attic Insulation ShieldFlat Ceiling Installation 9 Appliance Preparation A. Appliance PreparationWARNING! Risk of Fire! Prevent contact with B. Securing and Leveling the ApplianceSetting the Fireplace into the Framing •Sagging or loose insulationC. Active Convection Technology 10 Installing Vent Pipe DVP Pipe A. Assemble Vent SectionsPilot hole B. Assemble Slip SectionsC. Secure The Vent Sections E. Install Decorative Ceiling Components D. Disassemble Vent SectionsCAULK F. Install Metal Roof FlashingG. Assemble and Install Storm Collar CAUTION! Risk of Cuts, Abrasions or Flying DebrisH. Install Vertical Termination Cap J. Install Horizontal Termination Cap Figure 10.20 Venting Through the WallB. Gas Pressure 11 Gas InformationA. Fuel Conversion C. Gas Connection •Ensure adequate ventilationC. Optional Accessories Requirements A. Wiring RequirementsB. IntelliFire Ignition System Wiring 12 Electrical InformationOptional Remote Control Receiver Location REMOTE RECEIVERCOLOR PRODUCED D. Optional LED Lighting CircuitSWITCH TRIPPED G. Active Convection Blower Replacement E. Electrical Service and RepairF. Junction Box Installation KNOCKOUTSIDE BURNER SCREW FAN MOUNT FASTENERFigure 12.17. Remove Mounting Plate SLOT ON BLOWER HOUSINGBLOWER TAB ON MOUNTING PLATE Figure 12.18. Removed Mounting PlateB. Framing and Finishing Instructions 13 FinishingA. Splatter Guard Finishing InstructionsPainting Finish and Sealing JointsFinishing Around Opening with Gypsum Wallboard Figure 13.1 Finishing DetailsC. Mantel and Wall Projections Dimensions of CombustiblesFigure 13.6 Framing and Framing Materials-RED40ST D. Facing MaterialFigure 13.5 Framing and Framing Materials-RED40 Figure 13.7 Overlap Fit Method Non-CombustibleFinish Materials0 - 1 inch thickness-OverlapFit Method 42-3/4IN 0 Inches to 4 Inches Thick Inside Fit MethodFigure 13.9 Inside Fit Method 13-1/8INMESH FRAME ASSEMBLY E. Mesh FrontsASSEMBLY Figure 13.11. Mesh Front InstallationC. Clean the Appliance 14 Appliance SetupA. Remove Fixed Glass Assembly D. AccessoriesJ. Air Shutter Setting H. Fixed Glass AssemblyI. Install the Mesh Removing Fixed Glass AssemblySymptom 15 TroubleshootingA. IntelliFire Ignition System Possible CauseIntelliFire Ignition System - continued A. Appliance Dimension Diagram 16 Reference MaterialsT R Q S Figure 16.2 Appliance Dimensions RED40STM N O P A F GDVP-AS2 B. Vent Components DiagramsFigure 16.2 DVP vent components DVP-TRAP2 B. Vent Components Diagrams continuedDVP-TRAP1 DVP-TRAPK131 in 206 mm 8-1/8in13 in 330 mmPART NUMBER Optional Wire HarnessDESCRIPTION at Depot C. Service PartsRED40 StockedRED40ST 40 in Landscape See-ThruDV Fireplace#14 Valve Assembly #13 Control AssemblyService Parts List RED40,RED40STStocked Service PartsRED40, RED40ST   15.1 #15 Base Pan No Lights with Media15.3 15.215.3 15.215.1 15.416.3 #16 Base Pan With Lights and MediaStocked at Depot 16.116.1 16.216.3 16.4RED40-NNNNo lights, No Rock, No Refractory #17 Base Pan No Lights or Media withPorcelain or No refractory RED40-NNPNo lights, No Rock, PorcelainRED40ST-NNPNo lights, No Rock, Porcelain Stocked at DepotRED40ST-NNNNo lights, No Rock, No Refractory RED40ST-NNGNo lights, No Rock, Granite#21 Granite --With Media #19 Granite --No Media#20 Porcelain --No Media #22 Porcelain --With Media#19 Granite --No Media D. Contact Information NOTES