Heat & Glo LifeStyle RED40ST owner manual Installation of Carbon Monoxide Detectors

Page 8
Installation of Carbon Monoxide Detectors

Note: The following requirements reference various Massachusetts and national codes not contained in this document.

H.Requirements for the Commonwealth of Massachusetts

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, in- cluding but not limited to decks and porches, the following requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addi- tion, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detec- tor with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fu- eled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that dur- ing said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accor- dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanent- ly mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fu- eled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) in. in size, “GAS

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB- STRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizon- tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector ob- serves carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

Product Approved side wall horizontally vented gas fu- eled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

Detailed instructions for the installation of the venting system design or the venting system components; and

A complete parts list for the venting system design or venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not pro- vide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:

The referenced “special venting system” instructions shall be included with the appliance or equipment in- stallation instructions; and

The “special venting systems” shall be Product Ap- proved by the Board, and the instructions for that sys- tem shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Ap- proved side wall horizontally vented gas fueled equip- ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

See Gas Connection section for additional Common- wealth of Massachusetts requirements.

8

Heat & Glo • RED40, RED40ST • 2155-900 Rev. o • 7/12

Image 8
Contents Models RED40 RED40ST NOTICE•What to do if you smell gas Owner’s ManualA. Congratulations Homeowner Reference InformationTable of Contents Safety Alert KeyInstaller Guide 3 Maintenance and Service14 Appliance Setup 15 Troubleshooting = Contains updated information 13 FinishingB. Limited Lifetime Warranty LIMITED LIFETIME WARRANTYWARRANTY COVERAGE WARRANTY PERIODB. Limited Lifetime Warranty continued WARRANTY CONDITIONSWARRANTY EXCLUSIONS This warranty is void ifD. High Altitude Installations 1 Listing and Code ApprovalsA. Appliance Certification B. Glass SpecificationsInstallation of Carbon Monoxide Detectors A. Gas Fireplace Safety 2 Operating Instructions User GuideB. Your Fireplace C. Clear SpaceE. Fixed Glass Assembly D. Decorative Doors and FrontsG. Before Lighting Fireplace erate fireplace with fixed glass assembly removedH. Lighting Instructions IPI Final inspection byFOR YOUR SAFETY READ BEFORE LIGHTING LIGHTING INSTRUCTIONS IPIJ.Frequently Asked Questions I. After Fireplace is LitInitial Break-inProcedure •Some people may be sensitive to smoke and odors3 Maintenance and Service A. Maintenance Tasks-HomeownerGlass Cleaning Remote ControlB.Maintenance Tasks-QualifiedService Technician Gasket Seal and Glass Assembly InspectionVenting FireboxGetting Started A. Typical Appliance SystemInstaller Guide Figure 4.1 Typical SystemD. Inspect Appliance and Components B. Design and Installation ConsiderationsC.Tools and Supplies Needed 5 Framing and Clearances A. Selecting Appliance LocationFigure 5.2 Appliance Locations RED40ST 1/2 IN1/2 IN. C B. Constructing the Appliance Chase C. ClearancesMINIMUM FRAMING DIMENSIONS D. Mantel and Wall Projections Dimensions of Non-CombustiblesCombustible Mantels Non-CombustibleMantels6 Termination Locations A. Vent Termination Minimum ClearancesRoof Pitch H Min. FtV= VENT TERMINAL X = AIR SUPPLY INLET = AREA WHERE TERMINAL IS NOT PERMITTEDCovered Alcove Applications 7 Vent Information and Diagrams E. Vent DiagramsA. Approved Pipe B. Vent Table KeyTop Vent - Horizontal Termination Venting with 1 elbowV1 Minimum H1 Maximum1. Top Vent - Horizontal Termination - continued Venting with 2 elbowsINSTALLED HORIZONTALLY H1 + H2 Maximum1. Top Vent - Horizontal Termination Venting with 3 elbowscontinued H2 V2 H1 V1Exhaust restrictor Instructions Top Vent - Vertical Termination No ElbowsV = 3 ft Min. 1m, 50 ft. Max. 15.2 m Top Vent - Vertical Termination V2 H1 V1Top Vent - Vertical Termination DIRECT VENT WITH 5 in. / 8 in. DIAMETER DVP PIPE 8 Vent Clearances and Framing A. Pipe Clearances to CombustiblesB. Wall Penetration Framing Between ceiling firestopsC. Install the Ceiling Firestop Vaulted Ceiling Installation D. Install Attic Insulation ShieldFlat Ceiling Installation 9 Appliance Preparation A. Appliance PreparationB. Securing and Leveling the Appliance Setting the Fireplace into the FramingWARNING! Risk of Fire! Prevent contact with •Sagging or loose insulationC. Active Convection Technology 10 Installing Vent Pipe DVP Pipe A. Assemble Vent SectionsPilot hole B. Assemble Slip SectionsC. Secure The Vent Sections E. Install Decorative Ceiling Components D. Disassemble Vent SectionsF. Install Metal Roof Flashing G. Assemble and Install Storm CollarCAULK CAUTION! Risk of Cuts, Abrasions or Flying DebrisH. Install Vertical Termination Cap J. Install Horizontal Termination Cap Figure 10.20 Venting Through the WallB. Gas Pressure 11 Gas InformationA. Fuel Conversion C. Gas Connection •Ensure adequate ventilationA. Wiring Requirements B. IntelliFire Ignition System WiringC. Optional Accessories Requirements 12 Electrical InformationOptional Remote Control Receiver Location REMOTE RECEIVERCOLOR PRODUCED D. Optional LED Lighting CircuitSWITCH TRIPPED E. Electrical Service and Repair F. Junction Box InstallationG. Active Convection Blower Replacement KNOCKOUTSIDE BURNER SCREW FAN MOUNT FASTENERSLOT ON BLOWER HOUSING BLOWER TAB ON MOUNTING PLATEFigure 12.17. Remove Mounting Plate Figure 12.18. Removed Mounting Plate13 Finishing A. Splatter GuardB. Framing and Finishing Instructions Finishing InstructionsFinish and Sealing Joints Finishing Around Opening with Gypsum WallboardPainting Figure 13.1 Finishing DetailsC. Mantel and Wall Projections Dimensions of CombustiblesFigure 13.6 Framing and Framing Materials-RED40ST D. Facing MaterialFigure 13.5 Framing and Framing Materials-RED40 Figure 13.7 Overlap Fit Method Non-CombustibleFinish Materials0 - 1 inch thickness-OverlapFit Method 0 Inches to 4 Inches Thick Inside Fit Method Figure 13.9 Inside Fit Method42-3/4IN 13-1/8INE. Mesh Fronts ASSEMBLYMESH FRAME ASSEMBLY Figure 13.11. Mesh Front Installation14 Appliance Setup A. Remove Fixed Glass AssemblyC. Clean the Appliance D. AccessoriesH. Fixed Glass Assembly I. Install the MeshJ. Air Shutter Setting Removing Fixed Glass Assembly15 Troubleshooting A. IntelliFire Ignition SystemSymptom Possible CauseIntelliFire Ignition System - continued A. Appliance Dimension Diagram 16 Reference MaterialsFigure 16.2 Appliance Dimensions RED40ST M N O PT R Q S A F GDVP-AS2 B. Vent Components DiagramsFigure 16.2 DVP vent components B. Vent Components Diagrams continued DVP-TRAP1DVP-TRAP2 DVP-TRAPK131 in 8-1/8in 13 in206 mm 330 mmPART NUMBER Optional Wire HarnessDESCRIPTION C. Service Parts RED40at Depot StockedRED40ST 40 in Landscape See-ThruDV Fireplace#13 Control Assembly Service Parts List#14 Valve Assembly RED40,RED40STService Parts RED40, RED40STStocked   #15 Base Pan No Lights with Media 15.315.1 15.215.2 15.115.3 15.4#16 Base Pan With Lights and Media Stocked at Depot16.3 16.116.2 16.316.1 16.4#17 Base Pan No Lights or Media with Porcelain or No refractoryRED40-NNNNo lights, No Rock, No Refractory RED40-NNPNo lights, No Rock, PorcelainStocked at Depot RED40ST-NNNNo lights, No Rock, No RefractoryRED40ST-NNPNo lights, No Rock, Porcelain RED40ST-NNGNo lights, No Rock, Granite#19 Granite --No Media #20 Porcelain --No Media#21 Granite --With Media #22 Porcelain --With MediaService Parts D. Contact Information NOTES