Heat & Glo LifeStyle RED40ST owner manual H. Install Vertical Termination Cap

Page 42
H. Install Vertical Termination Cap

H. Install Vertical Termination Cap

Attach the vertical termination cap by sliding the inner collar of the cap into the inner flue of the pipe section while placing the outer collar of the cap over the outer flue of the pipe section.

Secure the cap by driving three self-tapping screws (supplied) through the pilot holes in the outer collar of the cap into the outer flue of the pipe (see Figure 10.19).

TERMINATION CAP

(1 of 3)

STORM

COLLAR

SCREWS

CAULK Manual background

Figure 10.19

I.Heat Shield Requirements for Horizontal Termination

WARNING! Risk of Fire! To prevent overheating and fire, heat shields must extend through the entire wall thick- ness.

DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap (shown in Figure 10.20).

Heat shields must overlap 1-1/2 in. (38 mm) mini- mum.

There are two sections of the heat shield. One section is factory-attached to the wall shield firestop. The other section is factory-attached to the cap. See Figure 10.20.

If the wall thickness does not allow the required 1-1/2 in. (38 mm) heat shield overlap when installed, an extended heat shield must be used.

If the wall thickness is less than 4 in./102 mm, the heat shields on the cap and wall shield firestop must be trimmed. A minimum 1-1/2 in. (38 mm) overlap MUST be maintained.

Use an extended heat shield if the finished wall thickness is greater than 7-1/4 in. (184 mm).

The extended heat shield may need to be cut to length maintaining sufficient length for a 1-1/2 in. (38 mm) overlap between heat shields.

Attach the extended heat shield to either of the existing heat shields using the screws supplied with the extended heat shield. Refer to vent components diagrams in the back of this manual.

Rest the small leg on the extended heat shield on top of the pipe section to properly space it from the pipe section.

Important Notice: Heat shields may not be field constructed.

42

Heat & Glo • RED40, RED40ST • 2155-900 Rev. o • 7/12

Image 42
Contents •What to do if you smell gas Models RED40 RED40STNOTICE Owner’s ManualA. Congratulations Homeowner Reference InformationInstaller Guide Table of ContentsSafety Alert Key 3 Maintenance and Service = Contains updated information 14 Appliance Setup15 Troubleshooting 13 FinishingWARRANTY COVERAGE B. Limited Lifetime WarrantyLIMITED LIFETIME WARRANTY WARRANTY PERIODWARRANTY EXCLUSIONS B. Limited Lifetime Warranty continuedWARRANTY CONDITIONS This warranty is void ifA. Appliance Certification D. High Altitude Installations1 Listing and Code Approvals B. Glass SpecificationsInstallation of Carbon Monoxide Detectors B. Your Fireplace A. Gas Fireplace Safety2 Operating Instructions User Guide C. Clear SpaceG. Before Lighting Fireplace E. Fixed Glass AssemblyD. Decorative Doors and Fronts erate fireplace with fixed glass assembly removedFOR YOUR SAFETY READ BEFORE LIGHTING H. Lighting Instructions IPIFinal inspection by LIGHTING INSTRUCTIONS IPIInitial Break-inProcedure J.Frequently Asked QuestionsI. After Fireplace is Lit •Some people may be sensitive to smoke and odorsGlass Cleaning 3 Maintenance and ServiceA. Maintenance Tasks-Homeowner Remote ControlVenting B.Maintenance Tasks-QualifiedService TechnicianGasket Seal and Glass Assembly Inspection FireboxInstaller Guide Getting StartedA. Typical Appliance System Figure 4.1 Typical SystemB. Design and Installation Considerations C.Tools and Supplies NeededD. Inspect Appliance and Components 5 Framing and Clearances A. Selecting Appliance Location1/2 IN 1/2 IN. CFigure 5.2 Appliance Locations RED40ST B. Constructing the Appliance Chase C. ClearancesMINIMUM FRAMING DIMENSIONS Combustible Mantels D. Mantel and Wall ProjectionsDimensions of Non-Combustibles Non-CombustibleMantelsRoof Pitch 6 Termination LocationsA. Vent Termination Minimum Clearances H Min. Ft= AREA WHERE TERMINAL IS NOT PERMITTED Covered Alcove ApplicationsV= VENT TERMINAL X = AIR SUPPLY INLET A. Approved Pipe 7 Vent Information and DiagramsE. Vent Diagrams B. Vent Table KeyV1 Minimum Top Vent - Horizontal TerminationVenting with 1 elbow H1 MaximumINSTALLED HORIZONTALLY 1. Top Vent - Horizontal Termination - continuedVenting with 2 elbows H1 + H2 Maximumcontinued 1. Top Vent - Horizontal TerminationVenting with 3 elbows H2 V2 H1 V1Top Vent - Vertical Termination No Elbows V = 3 ft Min. 1m, 50 ft. Max. 15.2 mExhaust restrictor Instructions Top Vent - Vertical Termination V2 H1 V1V1 + V2 Minimum DIRECT VENT WITH 5 in. / 8 in. DIAMETER DVP PIPE B. Wall Penetration Framing 8 Vent Clearances and FramingA. Pipe Clearances to Combustibles Between ceiling firestopsC. Install the Ceiling Firestop D. Install Attic Insulation Shield Flat Ceiling InstallationVaulted Ceiling Installation 9 Appliance Preparation A. Appliance PreparationWARNING! Risk of Fire! Prevent contact with B. Securing and Leveling the ApplianceSetting the Fireplace into the Framing •Sagging or loose insulationC. Active Convection Technology 10 Installing Vent Pipe DVP Pipe A. Assemble Vent SectionsB. Assemble Slip Sections C. Secure The Vent SectionsPilot hole E. Install Decorative Ceiling Components D. Disassemble Vent SectionsCAULK F. Install Metal Roof FlashingG. Assemble and Install Storm Collar CAUTION! Risk of Cuts, Abrasions or Flying DebrisH. Install Vertical Termination Cap J. Install Horizontal Termination Cap Figure 10.20 Venting Through the Wall11 Gas Information A. Fuel ConversionB. Gas Pressure C. Gas Connection •Ensure adequate ventilationC. Optional Accessories Requirements A. Wiring RequirementsB. IntelliFire Ignition System Wiring 12 Electrical InformationOptional Remote Control Receiver Location REMOTE RECEIVERD. Optional LED Lighting Circuit SWITCH TRIPPEDCOLOR PRODUCED G. Active Convection Blower Replacement E. Electrical Service and RepairF. Junction Box Installation KNOCKOUTSIDE BURNER SCREW FAN MOUNT FASTENERFigure 12.17. Remove Mounting Plate SLOT ON BLOWER HOUSINGBLOWER TAB ON MOUNTING PLATE Figure 12.18. Removed Mounting PlateB. Framing and Finishing Instructions 13 FinishingA. Splatter Guard Finishing InstructionsPainting Finish and Sealing JointsFinishing Around Opening with Gypsum Wallboard Figure 13.1 Finishing DetailsC. Mantel and Wall Projections Dimensions of CombustiblesD. Facing Material Figure 13.5 Framing and Framing Materials-RED40Figure 13.6 Framing and Framing Materials-RED40ST Non-CombustibleFinish Materials 0 - 1 inch thickness-OverlapFit MethodFigure 13.7 Overlap Fit Method 42-3/4IN 0 Inches to 4 Inches Thick Inside Fit MethodFigure 13.9 Inside Fit Method 13-1/8INMESH FRAME ASSEMBLY E. Mesh FrontsASSEMBLY Figure 13.11. Mesh Front InstallationC. Clean the Appliance 14 Appliance SetupA. Remove Fixed Glass Assembly D. AccessoriesJ. Air Shutter Setting H. Fixed Glass AssemblyI. Install the Mesh Removing Fixed Glass AssemblySymptom 15 TroubleshootingA. IntelliFire Ignition System Possible CauseIntelliFire Ignition System - continued A. Appliance Dimension Diagram 16 Reference MaterialsT R Q S Figure 16.2 Appliance Dimensions RED40STM N O P A F GB. Vent Components Diagrams Figure 16.2 DVP vent componentsDVP-AS2 DVP-TRAP2 B. Vent Components Diagrams continuedDVP-TRAP1 DVP-TRAPK131 in 206 mm 8-1/8in13 in 330 mmOptional Wire Harness DESCRIPTIONPART NUMBER at Depot C. Service PartsRED40 StockedRED40ST 40 in Landscape See-ThruDV Fireplace#14 Valve Assembly #13 Control AssemblyService Parts List RED40,RED40STStocked Service PartsRED40, RED40ST   15.1 #15 Base Pan No Lights with Media15.3 15.215.3 15.215.1 15.416.3 #16 Base Pan With Lights and MediaStocked at Depot 16.116.1 16.216.3 16.4RED40-NNNNo lights, No Rock, No Refractory #17 Base Pan No Lights or Media withPorcelain or No refractory RED40-NNPNo lights, No Rock, PorcelainRED40ST-NNPNo lights, No Rock, Porcelain Stocked at DepotRED40ST-NNNNo lights, No Rock, No Refractory RED40ST-NNGNo lights, No Rock, Granite#21 Granite --With Media #19 Granite --No Media#20 Porcelain --No Media #22 Porcelain --With Media#19 Granite --No Media D. Contact Information NOTES