I. Install Vertical Termination Cap

Attach the vertical termination cap by sliding the inner collar of the cap into the inner flue of the pipe section while placing the outer collar of the cap over the outer flue of the pipe section.

Secure the cap by driving three self-tapping screws (supplied) through the pilot holes in the outer collar of the cap into the outer flue of the pipe (see Figure 10.18).

TERMINATION CAP

(1 of 3)

STORM

COLLAR

SCREWS

CAULK

Figure 10.18

J.Install Decorative Wall Components (SLP only)

A decorative wall thimble can be installed on wall through which the vent passes. The decorative wall thimble is used to cover the wall shield firestop.

Slide the decorative wall thimble over the last section of horizontal pipe before connecting the termination cap to the pipe.

Once the pipe section and the termination cap have been connected, slide the wall thimble up to the interior wall surface and attach with screws provided. See Figure 10.19.

K.Heat Shield Requirements for Horizontal Termination

WARNING! Risk of Fire! To prevent overheating and fire, heat shields must extend through the entire wall thick- ness.

DO NOT remove the heat shields attached to the wall shield firestop and the horizontal termination cap

(shown in Figure 10.20).

Heat shields must overlap 1-1/2 in. (38 mm) mini- mum.

There are two sections of the heat shield. One section is factory-attached to the wall shield firestop. The other section is factory-attached to the cap. See Figure 10.20.

If the wall thickness does not allow the required 1-1/2 in. (38 mm) heat shield overlap when installed, an extended heat shield must be used.

If the wall thickness is less than 4 in./102 mm (DVP) or 4-3/8 in./ 111 mm (SLP), the heat shields on the cap and wall shield firestop must be trimmed. A minimum 1-1/2 in. (38 mm) overlap MUST be maintained.

Use an extended heat shield if the finished wall thickness is greater than 7-1/4 in. (184 mm).

The extended heat shield may need to be cut to length maintaining sufficient length for a 1-1/2 in. (38 mm) overlap between heat shields.

Attach the extended heat shield to either of the existing heat shields using the screws supplied with the extended heat shield. Refer to vent components diagrams in the back of this manual.

Rest the small leg on the extended heat shield on top of the pipe section to properly space it from the pipe section.

Important Notice: Heat shields may not be field constructed.

Figure 10.19 Wall Thimble

50

Heat & Glo • 6000C, 6000C-IPI, 8000C, 8000C-IPI2164-900 Rev. T • 9/12

Image 50
Contents Hot glass will cause burns What to do if you smell gasHOT Surfaces Congratulations Homeowner Reference InformationTable of Contents User GuideFinishing Appliance SetupTroubleshooting Reference MaterialsLimited Lifetime Warranty Hearth & Home Technologies Inc Limited Lifetime WarrantyLimited Lifetime Warranty Warranty ConditionsHigh Altitude Installations Tempered Glass SpecificationsBTU Specifications Listing and Code ApprovalsElectrical Codes Non-Combustible Materials SpecificationCombustible Materials Specification C22.1Requirements for the Commonwealth of Massachusetts Your Fireplace Gas Fireplace SafetyOperating Instructions User Guide Fan Kit optional Fixed Glass AssemblyRemote Controls, Wall Controls and Wall Switches Clear SpaceNine Hour Safety Shutdown Feature IPI Battery Tray/Battery InstallationModule Reset Control Module OperationWhat to do if YOU Smell GAS Lighting Instructions IPIFinal inspection by GAS ValveFor Your Safety Read Before Lighting Lighting Instructions Lighting Instructions Standing PilotAfter Fireplace is Lit Frequently Asked QuestionsIssue Solutions Glass Cleaning Maintenance and ServiceMaintenance Tasks-Homeowner Remote ControlVenting Maintenance Tasks-Qualified Service TechnicianGasket Seal and Glass Assembly Inspection LogsRefractory, Grate and Valve Assembly Removal Base RefractoryBurner Identification/Verification Notch LocationGetting Started Typical Appliance SystemInspect Appliance and Components Design and Installation ConsiderationsTools and Supplies Needed Any such action may cause a fire hazard6000 Framing and ClearancesSelecting Appliance Location 80006000 Constructing the Appliance ChaseClearances 8000Combustible Mantel Legs or Wall Projections Mantel and Wall ProjectionsCombustible Mantels Termination Locations Vent Termination Minimum ClearancesCovered Alcove Applications = 9 inches U.S.AVent Table Key Vent Information and DiagramsApproved Pipe Use of ElbowsVent pipe, if desired Vent Diagrams Top Vent Horizontal TerminationOne Elbow 6000C-IPI 8000C-IPI V1 Minimum H1 Maximum6000C-IPI V1 Minimum H1 + H2 Maximum Top Vent Horizontal Termination Two ElbowsThree Elbows 8000C-IPI V1 Minimum H1 + H2 MaximumBreak Top Vent Vertical Termination Maximum + V 2 MinTop Vent Vertical Termination Three Elbows H1 + H2 V1 + V2 Minimum H1 + H2 MaximumPage H1 Maximum V1 Minimum H2+ H3 H1+ H2+ H3 Max Rear Vent Horizontal Termination Two ElbowsH1 Maximum V1 Minimum H1 + H2 Maximum Minimum + H Maximum Rear Vent Vertical Termination One ElbowV1 Minimum H1 Maximum Rear Vent Vertical Termination Three Elbows V1 Minimum H1 + H2 + H3 Maximum 10 ftClearances to Combustibles Prior to installing the gas applianceCoaxial to Colinear Venting Termination Cap Flue DamperRear Vent Connecting the DV-46DVA-GCL Adapter to Appliance Top VentConnecting the LINK-DV30B to the DV-46DVA-GCL adapter Wall Penetration Framing Vent Clearances and FramingPipe Clearances to Combustibles Combustible Wall PenetrationInstall the Ceiling Firestop Pipe DVP SLPFlat Ceiling Installation Install Attic Insulation ShieldInstalling the Optional Heat-ZoneGas Kit Vaulted Ceiling InstallationAppliance Preparation Top VentRear Vent Cut the metal retaining band and fold the sides outHeader Installing the Non-combustible BoardSecuring and Leveling the Appliance Assemble Vent Sections DVP Pipe Only Installing Vent Pipe DVP and SLP PipeAttach Vent to the Firebox Assembly Assemble Pipe SectionsAssemble Vent Sections SLP Pipe Only Assemble Slip SectionsSecure the Vent Sections Disassemble Vent SectionsInstall Decorative Ceiling Components SLP only Roof Pitch Min. Ft Install Metal Roof FlashingAssemble and Install Storm Collar Heat Shield Requirements for Horizontal Termination Install Vertical Termination CapInstall Decorative Wall Components SLP only Install Horizontal Termination Cap DVP and SLP Pipe DVP-HPC1 DVP-HPC2Gas Pressure Gas InformationFuel Conversion Gas ConnectionStanding Pilot Ignition System Wiring Wiring RequirementsIntelliFire Plus Ignition System Wiring Optional Accessories RequirementsTo Junction Electrical Service and Repair Junction Box Installation Wall Switch Installation for Fan OptionalFinishing Facing MaterialDoor FIT Finish Material See Thickness DoorsFinishing Material Inch Thick or Less Models Finishing Material Thickness 1-4 inches maximumFinishing Material Thickness 0-4 inches maximum Removal of Finishing Strips Finishing Strips RemovedElevated Hearth Systems Appliance Setup Bottom view Logs # 2 Install the Log Assembly Log Assembly LOGS-6C6000C, 6000C-IPI LOG Contacts Grate Tines Install the Log Assembly Log Assembly LOGS-8C 8000C-IPILP, 8000CBV-IPIHorizontal Grate BAR Air Shutter Settings Install Trim and/or SurroundAir Shutter Setting 6000 8000Standing Pilot Ignition System TroubleshootingSymptom Possible Causes Corrective Action Troubleshooting Symptom Possible Cause Corrective ActionShorts in the wiring IntelliFire Plus Ignition SystemLocation Inches Millimeters Appliance Dimension DiagramReference Materials GAS Line Access R Left Side TOP View Front View Right View Vent Components Diagrams DVP-AS2DVP-TRAP Horizontal Termination CapDVP-TRAPFL RF6M RF12MBEK DVP-BEK2 COOL-ADDMDVP-TVHW DVP-FBHTPVI-SLP Optional Wire HarnessPower Vent Inline SLP-LPCDV-46DVA-GCL DVP-HRC-SS DVP-HRC-ZC-SS Horizontal Termination CAPLINK-DV30B DVP-2SL AdapterSLP Pipe SLP45SLP90 DVP-SLP24SLP-WT-BK SLP-TRAPDVP-2SL SLP-DCF-BK SLP-CCS-BKSLK-SNKD SLP-TVHWGas Fireplace DV Service PartsAt Depot Beginning Manufacturing Date Aug8000C, 8000C-IPI 6000C-IPI 8000C-IPI8000C Stocked6000C Standing Pilot Conversion Kits IPI Conversion KitsContact Information