Heat & Glo LifeStyle 6000C manual IntelliFire Plus Ignition System, Shorts in the wiring

Page 69

B. IntelliFire Plus™ Ignition System

Symptom

Possible Cause

Corrective Action

 

 

 

1. Pilot won’t light.

A. Incorrect wiring.

Verify “S” wire (white) for sensor and “I” wire (orange) for ignitor are

The ignitor/module

 

connected to correct terminals on module and pilot assembly.

makes noise, but no

 

 

B. Loose connections or electrical

Verify no loose connections or electrical shorts in wiring from mod-

spark.

 

shorts in the wiring.

ule to pilot assembly. Verify connections underneath pilot assembly

 

 

are tight; also verify igniter and flame sense wires are not grounding

 

 

out to metal chassis, pilot burner, pilot enclosure, mesh screen if

 

 

present, or any other metal object.

 

 

 

 

C. Ignitor gap is too large.

Verify gap of igniter to right side of pilot hood. The gap should be

 

 

approximately .17 in. or 1/8 in. (3 mm).

 

 

 

2. Pilot won’t light,

A. No power, transformer installed

Verify that transformer is installed and plugged into module. Check

there is no noise or

incorrectly, or depleted batteries.

voltage of transformer at connection to module. Acceptable read-

spark.

 

ings of a good transformer are between 6.4 and 6.6 volts AC. Bat-

 

 

tery power supply voltage must be at least 4 volts. If below 4 volts,

 

 

replace batteries.

 

 

 

 

B. A shorted or loose connection in

Remove and reinstall the wiring harness that plugs into module.

 

wiring configuration or wiring har-

Verify there is a tight fit. Verify pilot assembly wiring to module. Re-

 

ness.

move and verify continuity of each wire in wiring harness. Replace

 

 

any damaged components.

 

 

 

 

C. Improper wall switch wiring.

Verify that 110/VAC power is “ON” to junction box.

 

 

 

 

D. Module not grounded.

Verify black ground wire from module wire harness is grounded to

 

 

metal chassis of appliance.

 

 

 

3. Pilot sparks, but

A. Gas supply.

Verify that incoming gas line ball valve is “open”. Verify that inlet

Pilot will not light.

 

pressure reading is within acceptable limits.

 

 

 

 

B. Ignitor gap is too large.

Verify gap of igniter to right side of pilot hood. The gap should be

 

 

approximately .17 in. or 1/8 in. (3 mm).

 

 

 

 

C. Module is not grounded.

Verify module is securely grounded to metal chassis of appliance.

 

 

 

 

D. Pilot valve solenoid

Verify that 1.5 to 1.8 VDC is supplied to pilot solenoid from module.

 

 

If below 1.5 volts, replace module. If 1.5 volts or greater, replace

 

 

valve.

 

 

 

4. Pilot lights but con-

A. A shorted or loose connection in

Verify all connections to wiring diagram in manual. Verify connec-

tinues to spark, and

flame sensing rod.

tions underneath pilot assembly are tight. Verify flame sense or ig-

main burner will not

 

niter wires are not grounding out to metal chassis, pilot burner, pilot

ignite. (If the pilot

 

enclosure or screen if present, or any other metal object.

continues to spark

 

 

B. Poor flame rectification or contami-

With fixed glass assembly in place, verify that flame is engulfing

after the pilot flame

nated flame sensing rod.

flame sensing rod on left side of pilot hood. Flame sensing rod

has been lit, flame

 

should glow shortly after ignition. With a multi-meter, verify that

rectification has not

 

 

current in series between module and sense lead is at least 0.14

occurred.)

 

 

microamps. Verify correct pilot orifice is installed and gas inlet is set

 

 

 

 

to pressure specifications. Polish flame sensing rod with fine steel

 

 

wool to remove any contaminants that may have accumulated on

 

 

flame sensing rod.

 

 

 

 

C. Module is not grounded.

Verify module is securely grounded to metal chassis of appliance.

 

 

Verify that wire harness is firmly connected to the module.

 

 

 

 

D. Damaged pilot assembly or con-

Verify that ceramic insulator around the flame sensing rod is not

 

taminated flame sensing rod.

cracked, damaged, or loose. Verify connection from flame sensing

 

 

rod to white sensor wire. Polish flame sensing rod with fine steel

 

 

wool to remove any contaminants that may have accumulated on

 

 

flame sensing rod. Verify continuity with a multi-meter with ohms set

 

 

at lowest range. Replace pilot if any damage is detected.

 

 

 

Heat & Glo • 6000C, 6000C-IPI, 8000C, 8000C-IPI2164-900 Rev. T • 9/12

69

Image 69
Contents What to do if you smell gas HOT SurfacesHot glass will cause burns Homeowner Reference Information CongratulationsUser Guide Table of ContentsTroubleshooting Appliance SetupFinishing Reference MaterialsLimited Lifetime Warranty Limited Lifetime Warranty Hearth & Home Technologies IncWarranty Conditions Limited Lifetime WarrantyBTU Specifications Tempered Glass SpecificationsHigh Altitude Installations Listing and Code ApprovalsCombustible Materials Specification Non-Combustible Materials SpecificationElectrical Codes C22.1Requirements for the Commonwealth of Massachusetts Gas Fireplace Safety Operating Instructions User GuideYour Fireplace Remote Controls, Wall Controls and Wall Switches Fixed Glass AssemblyFan Kit optional Clear SpaceModule Reset IPI Battery Tray/Battery InstallationNine Hour Safety Shutdown Feature Control Module OperationFinal inspection by Lighting Instructions IPIWhat to do if YOU Smell GAS GAS ValveLighting Instructions Standing Pilot For Your Safety Read Before Lighting Lighting InstructionsFrequently Asked Questions Issue SolutionsAfter Fireplace is Lit Maintenance Tasks-Homeowner Maintenance and ServiceGlass Cleaning Remote ControlGasket Seal and Glass Assembly Inspection Maintenance Tasks-Qualified Service TechnicianVenting LogsBase Refractory Refractory, Grate and Valve Assembly RemovalNotch Location Burner Identification/VerificationTypical Appliance System Getting StartedTools and Supplies Needed Design and Installation ConsiderationsInspect Appliance and Components Any such action may cause a fire hazardSelecting Appliance Location Framing and Clearances6000 8000Clearances Constructing the Appliance Chase6000 8000Mantel and Wall Projections Combustible MantelsCombustible Mantel Legs or Wall Projections Vent Termination Minimum Clearances Termination Locations= 9 inches U.S.A Covered Alcove ApplicationsApproved Pipe Vent Information and DiagramsVent Table Key Use of ElbowsOne Elbow Vent Diagrams Top Vent Horizontal TerminationVent pipe, if desired 6000C-IPI 8000C-IPI V1 Minimum H1 MaximumThree Elbows Top Vent Horizontal Termination Two Elbows6000C-IPI V1 Minimum H1 + H2 Maximum 8000C-IPI V1 Minimum H1 + H2 MaximumBreak Maximum + V 2 Min Top Vent Vertical TerminationH1 + H2 V1 + V2 Minimum H1 + H2 Maximum Top Vent Vertical Termination Three ElbowsPage Rear Vent Horizontal Termination Two Elbows H1 Maximum V1 Minimum H1 + H2 MaximumH1 Maximum V1 Minimum H2+ H3 H1+ H2+ H3 Max Rear Vent Vertical Termination One Elbow V1 Minimum H1 MaximumMinimum + H Maximum V1 Minimum H1 + H2 + H3 Maximum 10 ft Rear Vent Vertical Termination Three ElbowsCoaxial to Colinear Venting Prior to installing the gas applianceClearances to Combustibles Termination Cap Flue DamperConnecting the DV-46DVA-GCL Adapter to Appliance Top Vent Connecting the LINK-DV30B to the DV-46DVA-GCL adapterRear Vent Pipe Clearances to Combustibles Vent Clearances and FramingWall Penetration Framing Combustible Wall PenetrationPipe DVP SLP Install the Ceiling FirestopInstalling the Optional Heat-ZoneGas Kit Install Attic Insulation ShieldFlat Ceiling Installation Vaulted Ceiling InstallationTop Vent Appliance PreparationCut the metal retaining band and fold the sides out Rear VentInstalling the Non-combustible Board Securing and Leveling the ApplianceHeader Attach Vent to the Firebox Assembly Installing Vent Pipe DVP and SLP PipeAssemble Vent Sections DVP Pipe Only Assemble Pipe SectionsAssemble Slip Sections Assemble Vent Sections SLP Pipe OnlyDisassemble Vent Sections Secure the Vent SectionsInstall Decorative Ceiling Components SLP only Install Metal Roof Flashing Assemble and Install Storm CollarRoof Pitch Min. Ft Install Vertical Termination Cap Install Decorative Wall Components SLP onlyHeat Shield Requirements for Horizontal Termination DVP-HPC1 DVP-HPC2 Install Horizontal Termination Cap DVP and SLP PipeFuel Conversion Gas InformationGas Pressure Gas ConnectionIntelliFire Plus Ignition System Wiring Wiring RequirementsStanding Pilot Ignition System Wiring Optional Accessories RequirementsTo Junction Wall Switch Installation for Fan Optional Electrical Service and Repair Junction Box InstallationFacing Material FinishingDoors Finishing Material Inch Thick or LessDoor FIT Finish Material See Thickness Finishing Material Thickness 1-4 inches maximum Finishing Material Thickness 0-4 inches maximumModels Finishing Strips Removed Removal of Finishing StripsElevated Hearth Systems Appliance Setup Install the Log Assembly Log Assembly LOGS-6C 6000C, 6000C-IPIBottom view Logs # 2 LOG Contacts Grate Tines 8000C-IPILP, 8000CBV-IPI Install the Log Assembly Log Assembly LOGS-8CHorizontal Grate BAR Air Shutter Setting Install Trim and/or SurroundAir Shutter Settings 6000 8000Troubleshooting Symptom Possible Causes Corrective ActionStanding Pilot Ignition System Symptom Possible Cause Corrective Action TroubleshootingIntelliFire Plus Ignition System Shorts in the wiringAppliance Dimension Diagram Reference MaterialsLocation Inches Millimeters GAS Line Access R Left Side TOP View Front View Right View DVP-AS2 Vent Components DiagramsHorizontal Termination Cap DVP-TRAPBEK DVP-BEK2 RF6M RF12MDVP-TRAPFL COOL-ADDMDVP-FBHT DVP-TVHWPower Vent Inline Optional Wire HarnessPVI-SLP SLP-LPCLINK-DV30B DVP-HRC-SS DVP-HRC-ZC-SS Horizontal Termination CAPDV-46DVA-GCL DVP-2SL AdapterSLP90 SLP45SLP Pipe DVP-SLP24SLP-TRAP DVP-2SLSLP-WT-BK SLK-SNKD SLP-CCS-BKSLP-DCF-BK SLP-TVHWAt Depot Service PartsGas Fireplace DV Beginning Manufacturing Date Aug8000C, 8000C-IPI 8000C-IPI 6000C-IPIStocked 6000C8000C IPI Conversion Kits Standing Pilot Conversion KitsContact Information