AIR FOR COMBUSTION

AND VENTILATION

Continued

1.Determine the volume of the space (length x width x height).

Length x Width x Height =________ cu. ft. (volume of space)

Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

_______(volume of space) x 20 = (Maximum Btu/Hr the space can support)

Example: 3168 cu. ft. (volume of space) x 20 = 63,360 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

__________ Btu/Hr

Gas water heater*

__________ Btu/Hr

Gas furnace

__________ Btu/Hr

Vented gas heater

__________

Btu/Hr

Gas fireplace logs

__________

Btu/Hr

Other gas appliances* +

________

Btu/Hr

Total

=

________

Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

40,000

 

Gas water heater

 

__________ Btu/Hr

Vent-free heater

39,000

Btu/Hr

+ ________

Total

79,000

Btu/Hr

= ________

4. Compare the maximum Btu/Hr the space can

support with the actual amount of Btu/Hr used.

__________ Btu/Hr (maximum the space

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ven- tilation Air From Outdoors, page 9.

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un- confined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilationairbyoneofthemethods described in the National Fuel Gas Code,ANSIZ223.1/NFPA54Section

5.3or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 4). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

can support)

__________ Btu/Hr (actual amount of

Btu/Hr used)

Example: 63,360 Btu/Hr (maximum

the space can support)

79,000 Btu/Hr (actual amount of Btu/Hr used)

Ventilation

 

Grills

 

Into

Or

Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

 

Room,

 

Option

 

3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

12"

Figure 3 - Ventilation Air from Inside

Building

8

www.desatech.com

115254-01A

Image 8
Contents VL32HN, LHN VL36EN, LENVL32HP, LHP VL36EP, LEPTable of Contents Safety Information Product Features Blower AccessoryLocal Codes OperationProduct Specifications Locating FireboxPlanning Models42 Models Determining FRESH-AIR Flow for Heater Location AIR for Combustion VentilationProviding Adequate Ventilation Ventilation AIR Ventilation Air From Inside BuildingInstallation Installation ClearancesVentilation Air From Outdoors Minimum Wall and Ceiling Clearances see ,Minimum 16 inches from Side Wall BUILT-IN Firebox InstallationExample Rough Opening for Installing Wall Nails or Wood Screws Nailing FlangesInstalling Firebox Using Optional Accessory Mantels Installing Cabinet MantelDuplex Electrical Outlet Installing Optional Blower AccessoriesLower Louver Panel Wiring Diagram Decal 12 Front of Blower Place control knob, provided, onto control shaft see FigureHARD-WIRING Firebox Installing Fireplace Hood and ScreenDuplex Box Handy Box Strain Relief Top View of Rod LayoutVent Pointing Down Connecting to GAS SupplyInstallation Items Needed Natural Checking GAS ConnectionsPropane/LP Test Pressures In Excess Of 1/2 Psig 3.5 kPa Test Pressures Equal To or Less Than 1/2 Psig 3.5 kPaSupply Tank Correct all leaks at onceInstalling Logs Vintage Oak Two-Piece Log SetLog #2 Log #1 Front Post Chassis PostEmber Bed Base Assembly MetalPost Metal PostOperating Fireplace Place top left log on middle log as shown in FigureTop Left Log Top Right Log Middle Left Front Log Right Front LogLighting Instructions Press in control knob and turn counterControl Knob Ignitor ButtonManual Lighting Procedure REMOTE-READY Models For Your Safety Read Before LightingVariable Control Operation To Turn OFF GAS To ApplianceBe hot if heater has been running Follow instructions included with the remote control Control Knob Flame Adjustment On PositionOptional Remote Control Optional HAND-HELD Remote OperationON/OFF Series Model Ghrcb Thermostat Series Model GhrctbFront Burner Flame Pattern Inspecting BurnersPilot Flame Pattern Burner Injector Holder and Pilot AIR Inlet Hole Cleaning MaintenanceCleaning Logs Troubleshooting Observed Problem Possible Cause RemedyClean ODS/pilot see Low gas pressure AssemblyLeased Long enoughWhen burners are lit Position when burners are Observe minimum installaBurner backfiring during com Bustion DamagedGas leak. See Warning Specifications Wiring DiagramMaximum Minimum Shipping Weight 104 lbs 184 lbs REMOTE-READY Models onlyService Hints Technical ServiceReplacement Parts Parts Under WarrantyAccessories Illustrated Parts Breakdown Parts List Parts Available not Shown46 39 Parts List 23/24 Not Shown Illustrated Parts Breakdown and Parts List 110314-05 Crossover LogKEY LOG Part Numbers VL36 Models VL42 Models Description QTY Limited Warranty VENT-FREE Fireplace Warranty InformationKeep this Warranty