Vermont Casting DVT38S2 Restrictor Plate Guide, Horizontal Termination, Vertical Termination

Page 12

Chateau™ Decorative Gas Appliance

proper sealing. Be sure to always attach straps on up- per elbow to a structural framing member.

For vertical installations, continue installing the pipe as required until pipe is installed up through the ceiling. At this point, you must install a firestop spacer.

Pipe Section

 

Pipe

UP

Rim

 

 

Hem

 

Lance

 

Pipe

 

Rim

installed before any offset. A maximum of 20’ (6.1 m) horizontal and three (3) 90° elbows may be installed with a minimum of 12’ (3.66 m) vertical section above the flue collar of the unit. Refer to Page 13, Figure 15 for more information.

A vertically terminated vent system must also conform to the following criteria:

No more than three (3) 90° elbows may be used.

Two (2) 45° elbows may be substituted for one (1) 90° elbow. No more than six (6) elbows may be used.

Vent must rise a minimum of 2’ (610 mm) before offset is used.

Termination height must conform to roof clearance as specified in Figure 35.

FP1468

Fig. 13 Install pipe, listening for the snap-lock to fasten.

Restrictor Plate Guide

 

 

 

 

Application

NG

LP

SK8DVSK or

 

 

2’ (610mm) vertical elbow,

 

 

2’ (610mm) horizontal

None

None

4’ (1.2m) vertical elbow

 

4¹⁄” flue

10’ (3m) horizontal elbow

None

restrictor

8’ (2.4m) vertical

 

 

12’ (3.7m) vertical & greater

6³⁄” flue

6³⁄” flue

 

restrictor

restrictor

Horizontal Termination

The vent must rise vertically a minimum of 24”

(610 mm) off the top of the unit, before the first elbow. The horizontal run may extend up to 20’ (6 m) and include a vertical rise of up to 40’ (12 m). (Fig. 14) Hori- zontal termination must also meet the criteria shown in Figures 11 & 12.

Approved vent systems must terminate above and

including the heavy line in Figure 14.

Two 45° elbows may be substituted for each single

90° elbow.

With a rise between 2’ - 4’, one (1) 90° or two (2) 45°

elbows may be used.

Vertical Run (in feet) (Measured from the appliance flue collar to the top of the vent pipe.)

May use one (1) elbow only

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

May

use up to

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

three (3) 90°

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

elbows, but must

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

not have two (2)

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

consecutive 90°

-

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

elbows in horizon

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

tal plane

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

���

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unacceptable

vent

-

 

 

 

���

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ing configuration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

� �

� � � � � � � �� �� �� �� �� �� �� �� �� �� ��

Vertical Termination

A vertical vent system must terminate no less than 12’ (3.66 m) and no more than 40’ (12 m) above the appli- ance flue collar. A 2’ (610 mm) vertical section must be

Horizontal Run (in feet)

Fig. 14 Horizontal vent termination window.

FP1359

12

20009543

Image 12
Contents INSTALLER/CONSUMER Safety Information What to do if YOU Smell GASTable of Contents Installation & Operating Instructions Locating Your FireplacePlease Review the Following Carefully Dimension Standard FramingMantel Surround Framing CriticalClearance to Combustibles MantelsHearth Framing and Finishing Nailing flangesGas Line Installation Final FinishingGas Specifications Gas Inlet and Manifold PressuresRemote ON/OFF Switch Electrical Junction Box E Units OnlyElectronic Gas Control Valve General Venting Location of Vent TerminationCanadian Installations1 US Installations2 General Venting Information Termination LocationCanadian Installations USA InstallationsGeneral Information Assembling Vent Pipes SK8 Venting Pipes Restrictor Plate Guide Horizontal TerminationVertical Termination ApplicationSidewall Applications Mm on the bottomSidewall Installation Always install horizontal venting on a level planeStep Sidewall Installation with Stationary Glass Facing Outside Horizontal length requirementInstalling the 38S2VDK Door Installation ProcedureRestrictor plate use in straight up installation Turn shutter plate over to cover opening Vertical Through-the-Roof Installation Installing firestop spacerMin 610mm Chimney Components Component Description Model NumberGlass Frame Assembly Removal Glass CleaningRestrictor Plates Installation Operating InstructionsCeramic Refractory Installation Log, Lava Rock and Ember PlacementLava rock and ember placement Position the log front right. Hold the log Flame & Temperature Adjustment Flame CharacteristicsRN/RP & EN/EP Models Trim Installation Trim frame in placeLighting and Operating Instructions To Turn Off Gas To HeaterLighting and Operating Instructions Lighting InstructionsTurning Off the Gas to the Appliance ValveTroubleshooting the Gas Control System SIT Nova 820 Millivolt ValveSIT 822 Valve with a Honeywell Electronic Ignitor Conversion Precautions Conversion ProcedureFuel Conversion Instructions Allow unit to cool if it has been operatingPilot Flame Adjustment Replace regulatorMaintenance Cleaning the Standing Pilot Control SystemCleaning Electronic Ignition System Battery Replacement for Ignitor ModuleDVT38S2 Decorative Gas Appliance DVT38S2 DVT38S2DVT38 Fuel Conversion KitsAccessories Remote ControlsFull Surround Mantel Model Functions ControlledLimited Lifetime Warranty Product Covered by this WarrantyEfficiency Ratings Model EnerGuide Ratings Fireplace Efficiency %