Chateau™ Decorative Gas Appliance
| Clearance to Combustibles |
|
|
|
|
|
|
| |||||
Top of Unit to Ceiling |
| 36” (914 mm) |
|
|
|
|
|
|
| ||||
Front of Unit to Combustibles (both sides) ... | 36” (914 mm) |
|
|
|
|
|
|
| |||||
Appliance |
|
|
|
|
|
|
|
|
|
|
| ||
Top Standoffs |
| 0” (0 mm) |
|
|
|
|
|
|
| ||||
Bottom |
|
| 0” (0 mm) |
|
|
|
|
|
|
| |||
Side Standoffs |
| 0” (0 mm) |
|
|
|
|
|
|
| ||||
Back Standoffs |
| 0” (0 mm) |
|
|
|
| � | � | � | ||||
Venting |
|
|
|
|
|
|
|
|
|
|
| ||
Horizontal Termination |
|
|
|
|
|
| � | ||||||
|
| Mantel Leg |
|
|
| � | |||||||
Vertical Sections: |
|
|
|
|
|
|
|
|
| ||||
Sides |
|
| 2¹⁄₂” (64 mm) | CFM164c |
|
|
|
|
|
| |||
Horizontal Sections: |
|
|
|
|
|
|
|
|
| � | |||
Top |
|
| 3¹⁄₂” (89 mm) |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| � | |||||
Bottom |
|
| 1¹⁄₂” (38 mm) |
|
|
|
|
|
| � | |||
|
|
| Side of Fireplace |
|
| � | |||||||
Sides |
|
| 2¹⁄₂” (64 mm) |
|
|
| � |
| |||||
|
|
|
|
|
|
|
| ||||||
Vertical Vent Application: |
|
|
|
|
|
|
|
|
|
| |||
Sides |
|
| 1¹⁄₂” (38 mm) |
|
|
|
|
|
|
| |||
|
| Mantels |
|
|
|
|
|
|
|
|
| ||
The height that a combustible mantel is fitted above the |
|
| Noncombustible |
|
|
| |||||||
fireplace is dependent on the depth of the mantel. This |
|
|
|
|
| ||||||||
also applies to the distance between the mantel leg (if |
|
| Finish Material |
|
|
| |||||||
|
|
|
|
|
|
| |||||||
fitted) and the fireplace. |
|
|
|
|
|
|
|
|
|
| |||
For the correct mounting height and widths refer to |
|
|
|
|
|
|
| ||||||
Figs. 3a and 3b, the following Mantel Charts. |
|
|
|
|
|
|
| ||||||
Noncombustible mantels and legs may be installed at |
|
|
|
|
|
| CFM170a | ||||||
any height and width around the appliance. |
|
| Mantel |
| Mantel Leg from Side | ||||||||
When using paint or lacquer to finish the mantel, such |
|
|
| ||||||||||
Ref. | Leg Depth | Ref. | of Comb. Opening | ||||||||||
paint or lacquer must be heat resistant to prevent | |||||||||||||
F | 12” | (305 mm) | K | 12” |
| (305 mm) | |||||||
discoloration. |
|
|
|
|
| ||||||||
|
|
|
| G | 9” | (229 mm) | L | 9” |
| (229 mm) | |||
|
|
|
|
|
|
| |||||||
|
|
|
|
| Combustible | H | 6” | (152 mm) | M | 6” |
| (152 mm) | |
|
|
|
|
| Framing and | I | 4” | (102 mm) | N | 4” |
| (102 mm) | |
|
|
|
|
| Finish Wall Above |
| |||||||
|
|
|
|
| J | 3” | (76 mm) | O | 3” |
| (76 mm) | ||
|
| � |
|
| Standoffs |
| |||||||
|
|
|
|
| May use com- | Fig. 3b Combustible mantel leg minimum installation. | |||||||
|
| � |
|
| bustible facing | ||||||||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
| material in this |
|
|
|
|
|
|
| |
|
| � |
|
| area |
|
| Hearth |
|
|
| ||
|
|
|
| Standoff |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| � |
|
|
| A hearth is not mandatory but is recommended for | |||||||
|
| � |
|
|
| aesthetic purposes. We recommend a noncombustible | |||||||
|
|
|
|
| hearth which projects out 12” (305 mm) or more from | ||||||||
|
|
|
|
|
| ||||||||
� | � | � � � |
|
|
| the front of the fireplace. The hearth cannot exceed 1¹⁄₂” | |||||||
|
|
| (38 mm) in height from bottom of fireplace for ease of | ||||||||||
|
|
|
|
|
| ||||||||
Noncombustible Finish Material |
|
|
| door accessibility. (Fig. 4) |
|
|
|
| |||||
|
|
| Cold climate installation recommendation: | ||||||||||
(Such as Dura Rock) |
| Top of Sheet Metal | |||||||||||
CFM146d |
| Fireplace Front |
|
|
| When installing this unit against a non- | |||||||
|
| Mantel Chart |
|
| insulated exterior wall or chase, it is | ||||||||
| Mantel Shelf |
| Mantel from Top |
| mandatory the outer walls be insulated to | ||||||||
Ref. | or Breast Plate | Ref. | of Comb. Chamber |
| conform to applicable insulation codes. | ||||||||
|
| Depth |
|
|
|
|
|
|
|
|
|
| |
V | 10” | (254 mm) | A | 10” | (254 mm) |
|
|
|
|
|
|
| |
W | 9” | (229 mm) | B | 9” | (229 mm) |
|
|
|
|
|
|
| |
X | 8” | (203 mm) | C | 8” | (203 mm) |
|
|
|
|
|
|
| |
Y | 7” | (178 mm) | D | 7” | (178 mm) |
|
|
|
|
|
|
| |
Z | 6” | (152 mm) | E | 6” | (152 mm) |
|
|
|
|
|
|
| |
Fig. 3a Combustible mantel minimum installation. |
|
|
|
|
|
| 5 |