Vermont Casting DVT38S2 installation instructions Sidewall Applications, Mm on the bottom

Page 13

Sidewall Applications

Since it is very important that the vent- ing system maintain its balance between the combustion air intake and the flue gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.

The vent graph showing the relationship between verti- cal and horizontal side wall venting will help to deter- mine the various dimensions allowable.

Chateau™ Decorative Gas Appliance

18” (45 cm). This does not apply if the 45° elbows are installed on the vertical part of the vent system. For each 90° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by 36” (914 mm).

The maximum number of elbow degrees in a system is 270°. (Fig. 18)

3'

(914mm)

Minimum clearance between vent pipes and combustible materials is 3¹⁄” (89 mm) on top, 2¹⁄” (64 mm) on both sides and 1¹⁄

2'

(610mm)

C Wall Opening

L

6'9���"

(38 mm) on the bottom.

When the vent termination exits through foundations less than 20” (508mm) below siding outcrop, the vent pipe must be flush with the siding.

 

20’ (6m)

 

 

 

Unitized Elbow

 

 

 

(SK890)

 

 

 

 

 

Pipe

 

 

 

Straps

(4.3m)

 

 

Every 3’

Pipe Straps

(914mm)

 

Every 3’

 

 

14’

 

 

(914mm)

Firestop/Zero

 

 

 

 

Minimum 2’

Clearance Sleeve

 

 

 

 

(610mm) Section

 

NOTE: Apply high temperature sealant or UL approved high temperature metal adhesive tape as directed on Page

11.

FP1453

Fig. 15 Support straps for horizontal runs.

It is always best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length of vent pipe from the flue collar of the fire- place to the face of the outer wall.

Horizontal plane means no vertical rise exists on this portion of the vent assembly.

The maximum number of 90° elbows per side wall installation is three (3), but must not have two (2) consecutive elbows in the horizontal plane.

A minimum of 2’ (610mm) vertical section off the top of the unit is required, an elbow and a 1’ (305mm) maximum horizontal run to get through a wall. (Fig. 16)

The maximum number of 45° elbows permitted per side wall installation is two (2). These elbows can be installed in either the vertical or horizontal run. (Fig. 16)

For each 45° elbow installed in the horizontal run, the length of the horizontal run MUST be reduced by

(2080mm)

FP1454

Fig. 16 Minimum vertical run / maximum horizontal run.

 

A

10'

B

 

(3m)

 

 

A + B = 17' (5.2m)

FP1238

Fig. 17 Maximum vent run with elbows.

Example:

 

 

 

 

 

 

 

 

 

 

Elbow 1

=

 

90°

 

 

 

 

 

Elbow 2

=

 

45°

4

 

Elbow 3

=

 

45°

 

 

 

 

 

Elbow 4

=

 

90°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total angular variation =

270°

 

 

 

 

 

 

 

 

1

 

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FP1455

Fig. 18 Maximum number of elbow degrees.

20009543

13

Image 13
Contents What to do if YOU Smell GAS INSTALLER/CONSUMER Safety InformationTable of Contents Locating Your Fireplace Installation & Operating InstructionsPlease Review the Following Carefully Standard Framing DimensionMantel Surround Framing CriticalMantels Clearance to CombustiblesHearth Nailing flanges Framing and FinishingFinal Finishing Gas Line InstallationGas Specifications Gas Inlet and Manifold PressuresElectrical Junction Box E Units Only Remote ON/OFF SwitchElectronic Gas Control Valve Location of Vent Termination General Venting General Venting Information Termination Location Canadian Installations1 US Installations2USA Installations Canadian InstallationsGeneral Information Assembling Vent Pipes SK8 Venting Pipes Horizontal Termination Restrictor Plate GuideVertical Termination ApplicationMm on the bottom Sidewall ApplicationsAlways install horizontal venting on a level plane Sidewall InstallationStep Horizontal length requirement Sidewall Installation with Stationary Glass Facing OutsideInstallation Procedure Installing the 38S2VDK DoorRestrictor plate use in straight up installation Turn shutter plate over to cover opening Installing firestop spacer Vertical Through-the-Roof InstallationMin 610mm Component Description Model Number Chimney ComponentsGlass Cleaning Glass Frame Assembly RemovalRestrictor Plates Installation Operating InstructionsLog, Lava Rock and Ember Placement Ceramic Refractory InstallationLava rock and ember placement Position the log front right. Hold the log Flame Characteristics Flame & Temperature AdjustmentRN/RP & EN/EP Models Trim frame in place Trim InstallationTo Turn Off Gas To Heater Lighting and Operating InstructionsLighting Instructions Lighting and Operating InstructionsTurning Off the Gas to the Appliance ValveSIT Nova 820 Millivolt Valve Troubleshooting the Gas Control SystemSIT 822 Valve with a Honeywell Electronic Ignitor Conversion Procedure Conversion PrecautionsFuel Conversion Instructions Allow unit to cool if it has been operatingReplace regulator Pilot Flame AdjustmentCleaning the Standing Pilot Control System MaintenanceCleaning Electronic Ignition System Battery Replacement for Ignitor ModuleDVT38S2 Decorative Gas Appliance DVT38S2 DVT38S2Fuel Conversion Kits DVT38Remote Controls AccessoriesFull Surround Mantel Model Functions ControlledProduct Covered by this Warranty Limited Lifetime WarrantyModel EnerGuide Ratings Fireplace Efficiency % Efficiency Ratings